13
Water Heater Start-Up
Navigation: Home Screen>Main Menu>EZ Setup>DHW EZ Setup
Domestic Hot Water EZ Setup allows the installer to quickly customize the
domestic hot water settings for the application.
Select DHW Demand
Default: Sensor
Select DHW Demand prompts the installer to select the type of device which will
generate a DHW call. Press the
UP
or
DOWN
buttons to select the DHW Demand
type then press the
OK
button to store the setting. The Select DHW Demand
options are:
•
Switch
– A domestic hot water call from an aquastat or dry contact switch will
enable the Prestige with a fixed setpoint for a domestic hot water call.
•
Sensor
– The Prestige Excellence utilizes an Indirect Water Heater Sensor.
The Prestige will monitor the DHW storage temperature and generate a
domestic hot water call when the temperature drops below the DHW Storage
Setpoint by 6ºF [3ºC].
DHW Storage Setpoint
Default: 140°F [60°C]
DHW Storage Setpoint prompts the installer to enter the domestic hot water storage
setpoint temperature when the Sensor option is chosen in Select DHW Demand.
Press the
LEFT
or
RIGHT
buttons to adjust the DHW Storage Setpoint then press
the
OK
button to store the setting.
The Boiler DHW Setpoint will automatically be set 46°F [25°C] higher
than the DHW Storage Setpoint setting.
DHW Priority Timeout
Default: Off
DHW Priority Timeout prompts the installer to enter an optional time limit that a
domestic hot water call has priority over a central heating call. Press the
LEFT
or
RIGHT
buttons to adjust the DHW Priority Timeout then press the
OK
button to
store the setting.
NOTICE
Domestic Hot Water EZ Setup
Select DHW Demand
Switch
Sensor
Sensor
68ºF
150ºF
140ºF
DHW
Storage Setpoint
Off
120 min.
Off
DHW Priority Timeout
Содержание Excellence
Страница 26: ...19 Boiler Piping Fig 6 Piping Component Legend ...
Страница 36: ...29 Internal Wiring Fig 19 PRESTIGE Excellence Boiler Factory Wiring ...
Страница 40: ...33 External Wiring Diverter Valve CH 1 Pump AUX Fig 20 Multiple Zone Field Wiring Using Zone Valves ...
Страница 41: ...34 External Wiring Diverter Valve CH 1 Pump AUX Fig 21 Multiple Zone Field Wiring using Zone Circulators ...
Страница 112: ...Water Heater Specifications 22 Performance ...
Страница 113: ...Notes ...