664Y3300
INSTALLATIoN
chImney connectIon
- The chimney connections must comply with the NBN D51-003
standard and in accordance with current regulations.
- Thanks to its built-in gas/air ratio regulator, the
Prestige
is, to
a large extent, independent of pressure drops in the air intake
and flue-gas exhaust systems. However, the maximum pressure
drop of this system may not be exceeded; otherwise, the
pressure would diminish, and in the case of the Prestige 120,
the air pressure switch would lock out the boiler. However, the
gas/air ratio regulator always guarantees optimal combustion
with very low emissions.
- The horizontal flue gas exhaust ducts must be installed with a
sufficient degree of slope towards the boiler: 3° of slope = 5 mm
per meter of duct.
- There must be no obstructions or inlets to other appliances within
a radius of 0.5 meters around the terminal of the
Prestige
.
-
The maximum pressure drop of the chimney is 150 Pascal.
You can calculate this value using the following table:
(please see
sample calculation as well).
- The C33s configuration enables airtight operation in a
pre-existing chimney. The combustion air crosses the space
between the tubing and the pre-existing chimney. Make sure to
clean the pre-existing chimney thoroughly prior to installation,
especially if there is soot or tar residue. Make sure that there
is a clearance area for the combustion air at least equivalent to
the area that would have been provided by separate concentric
ducts or air intake ducts.
prestige
1000 mm
1000 mm
2000 mm
2000 mm
Sample calculation
Prestige Solo 50/75:
The diagram below consists of the
following parts: pipe with a moni-
toring s 2 90° pipe bends
+ 2 meters of horizontal pipe +
2 45° pipe bends + (2 + 1 + 1)
meters of vertical and sloped pipe
+ one vertical terminal unit.
The resistance of this system is
as follows:
3 + (2 x 12) + (2 x 6) +
(2 x 5,5) + (4 x 6) + 25 = 99 Pa.
As this value is lower
than the maximum
authorised resistance,
this installation is com-
pliant.
Table of chimney pressure drop in Pascal (1 Pascal
= 0.01 mbar)
Prestige Solo 50 - 75
Prestige Solo 120
Concentric pipe
Ø 100 / 150 mm
Separate
air inlet
Ø 100 mm
Separate
flue gas
exhaust
Ø 100 mm
Concentric pipe
Ø 100 / 150 mm
Separate
air inlet
Ø 100 mm
Separate
flue gas
exhaust
Ø 100 mm
Straight pipe 1 m
6
1,7
2,5
—
4,0
6,0
Pipe with monitoring
feature
3
—
1,3
—
—
3,0
90° bend
12
5,1
7
—
13
18
45° bend
5,5
2,1
3
—
5,4
8,0
Vertical terminal
25
—
—
65
25
50
Horizontal terminal
20
—
—
65
20
50
This table is based on ACV equipment and cannot be applied elsewhere.