background image

 

 

 

No 
frost

Compressor

Check the frost 
on the cabinet 

liner surface

Leakage 
check

Cut off the 

low preesure pipe

No refrigerant 
air spurt out

Leakage 
point ?

On the 
pipe joint

Refrigerant 
Leaks

Cut off the low pressure 
pipe and spurt out the 
residual refrigerant

Repair the welding, 
clean the pipe and 
replace the dry filter

Vacuuming and 
recharging

Leakage 
check again

Refrigerant 
air spurt out

Cut off the high 
pressure pipe

Normal suction of 

the comressor low 
pressure pipe

Charge the 
nitrogen to the 
condenser pipe

No air on the 

low pressure side

Pipe 
clogged

Replace the dirty and 
clogged parts and 
clean the system pipe

Little 
frost

No air suction on 

the compressor 
low pressure pipe

Cut off the high 
pressure pipe

Bad compression 
of the compressor

Replace the 
compressor

Leakage 
checking

Detected

Leakage 
point

 ?

Cut off the 

low preesure pipe

A little 
refrigerant air 

spurt out

Leaks 

slowly

A little 
refrigerant air 

spurt out

Repair the welding, 
clean the pipe and 
replace the dry filter

Vacuuming and 
recharging

Leakage 
check again

Big quantity 
refrigerant air 

spurt out

Cut off the high 
pressure pipe

Normal suction of 

the comressor low 
pressure pipe

No air suction or weak 

suction on the compressor 
low pressure pipe

Compressor 
breaks down

Replace the 
compressor

Charge the 
nitrogen to the 
condenser pipe

Not sufficient nitrogen 
air return back the low 
pressure side

Pipe is 
clogged 

slightly

Replace the dirty and 
clogged parts and 
clean the system pipe

Condensate dew 
but no frost

Check the high 
pressure side pipe 
and compressor

Too high 
temperature

Check low 
pressure pipe

Frost

Too more 
refrigerant

Frost

Recharge appropriate 
quantity refrigerant

Cooling 
discontinuously

Pipe is clogged 
with ice

Replace the dry filter 
and clean the system 
pipe with warm nitrogen

Compressor 
not working

Check the electrical parts such 
as PTC starter,capacitor,overload 
protector, thermostat etc.

Broken-down

Replace the 
broken-down parts

Good

Measure the 
resistance of the 

compressor winding 

Abnormal 
resistance

Normal

Replace the 
compressor

Overload 
protector acts

Over large 
current

Replace the 
compressor

Compressor 
goes wrong

Yes

No

Problem and check point Cause Solution

Содержание PRF047XW

Страница 1: ...Service Manual for Single Door Fridge PREMIUM MODEL PRF047XW PRF071XW PRF3X PRF3XT...

Страница 2: ...ng System Diagram 5 6 Part Lists and explanation 5 7 Disassembling and replacing of the components 6 8 Check the breakdowns of the cooling system 7 9 Table for quick answer for the field problem 9 10...

Страница 3: ...al and simple beautifu recessed handle Recessed door gasket seal easy to be discharged and cleaned Plastic material simple and practically One shelf and one drip tray inside Front Left and right side...

Страница 4: ...t keep the room good air circulation condition When cutting the suction pipe or discharging pipe of the compressor pay attention to the surplus refrigerant and internal pressure in cooling system pipe...

Страница 5: ...ce and assembly must use the multi meter to measure the insulation resistance if it is greater than 1 million ohm then you can plug on the unit 8 Grounding test After maintenance use the multimeter to...

Страница 6: ...sed compressor model 5 Cooling System Diagram Note Arrow direction means the flowing direction of the refrigerant 6 Part Lists and explanation PRF047XW PRF071XW PRF3X PRF3XT Capillary Dry Filter Evapo...

Страница 7: ...starter or overload protector then fix back the terminal box cover and its clamp 3 Replace the door gasket seal Remove the old door gasket seal from the groove of the door linear then install the new...

Страница 8: ...7 8 Check the breakdowns of the cooling system Following the next illustration to check the problem...

Страница 9: ...ter Vacuuming and recharging Leakage check again Big quantity refrigerant air spurt out Cut off the high pressure pipe Normal suction of the comressor low pressure pipe No air suction or weak suction...

Страница 10: ...re vacuum and recharge the refrigerant at last do the leakage detecting again B If big quantity refrigerant spurt out cut off the high pressure pipe to check the suction of the compressor low pressur...

Страница 11: ...ed of the circuit or turn the thermostat to the coldest point the compressor can run Thermostat is breakdown There is sound when turning the knob of the thermostat The knob is broken or is not install...

Страница 12: ...d of refrigerant flowing in cooling system and it leaves oil on the welding point Leakage of refrigerant There is no sound of refrigerant flowing in cooling system and no oil on the welding point Insi...

Страница 13: ...tly The unit is not placed at good position The freezer is inside direct sunshine The unit can not dissipate the heat because sunshine The back of the unit is too close to the wall Too close will affe...

Страница 14: ...stem and control it more strictly Left water quantity control a If the cooling system parts like condenser evaporator compressor or the dry filter etc need to be replaced the replaced parts should be...

Страница 15: ...t condition And ensure to use a little as enough as possible Check the compressor is pressurized or not when opening When storing the R134a refrigerant must keep it sealed and not touch with atmospher...

Страница 16: ...happens again then should service again 12 Maintenance parts list No Parts name PCS unit Note 1 Compressor 1 2 Thermal protector of compressor 1 3 PTC starter 1 4 Feet of compressor 4 5 Refrigerant d...

Отзывы: