      Check the frost on the cabinet liner surface, if find like following: 
  1) No frost, then do the leakage detecting. 

A). If the leakage point is found, then first cut off the low pressure pipe to discharge the left 

refrigerant  in  the  system,  then  clean  the  pipe,  replace  with  a  new  dry  filter  and  welding  again, 
again recharge the refrigerant and do the leakage detecting. 

B). If the leakage can not be found, cut off the low pressure pipe, if there is no refrigerant 

omitting, then recharge the refrigerant and do the leakage detecting again; If there is refrigerant 
omitting,  cut  off  the  high  pressure  pipe(means  that  compressor  suction  is  normal),  charge  the 
condenser  pipe  with  pressurized  nitrogen,  if  no  air  at  low  pressure  side,  means  the  pipe  is 
blocked, then replace the blocked parts and clean the system pipe; If no air suction at compressor 
low pressure side, cut off the high pressure pipe, means air compression of the compressor is not 
good, please replace the compressor. 
2). A little frost on the surface, also do the leakage detecting first. 

A)    If  the  leakage  point  is  confirmed,  then  cut  off  the  low  pressure  pipe,  if  a  little 

refrigerant  air  spurt  out,  means  that  the  system  leaks  slowly  on  the  leakage  point,  you  should 
repair  the  welding  of  cut  pipe  and  the  leakage  point  and  clean  the  system  pipe  by  the  high 
pressure nitrogen, replace the dry filter, after completion these work, re-vacuum and recharge the 
refrigerant, at last do the leakage detecting again. 

B). If big quantity refrigerant spurt out, cut off the high pressure pipe to check the suction of 

the compressor low pressure pipe is  normal  or not: if no suction or weak suction, it means  not 
good compression and need to replace the compressor; if normal suction, then charge the clean 
and warm nitrogen to  the condenser pipe, if  you find the returned nitrogen of the low pressure 
side is not sufficient, it means that the system pipe is clogged lightly, please replace the clogged 
parts and clean the pipe. 
3). No frost, but have condensate water on the surface on the cabinet liner, check the temperature 
of the high pressure side pipe and the compressor,  you will find it is  too  high temperature and 
check  the  low  pressure  pipe  with  frost,  if  like  this,  means  too  more  refrigerant  in  the  system, 
please recharge with appropriate quantity refrigerant once more. 
4) The unit works discontinuously, maybe the system is clogged with ice, please replace the dry 
filter and clean the system with clean and warm nitrogen. 
5) Compressor doesn’t run. 
    Please check the electrical parts, such as PTC starter, capacitor, overload protector, thermostat 
etc., if you find the parts go wrong, then replace a new one with same type and specification. If 
all  of  these  parts  are  good,  please  measure  the  resistance  of  the  compressor  winding,  if  the 
resistance is abnormal, must replace the compressor; otherwise check the overload protector act 
or not, means the over large current and compressor goes wrong, also replace the compressor. 
         
 
 
 
 
 
 

Содержание PRF047XW

Страница 1: ...Service Manual for Single Door Fridge PREMIUM MODEL PRF047XW PRF071XW PRF3X PRF3XT...

Страница 2: ...ng System Diagram 5 6 Part Lists and explanation 5 7 Disassembling and replacing of the components 6 8 Check the breakdowns of the cooling system 7 9 Table for quick answer for the field problem 9 10...

Страница 3: ...al and simple beautifu recessed handle Recessed door gasket seal easy to be discharged and cleaned Plastic material simple and practically One shelf and one drip tray inside Front Left and right side...

Страница 4: ...t keep the room good air circulation condition When cutting the suction pipe or discharging pipe of the compressor pay attention to the surplus refrigerant and internal pressure in cooling system pipe...

Страница 5: ...ce and assembly must use the multi meter to measure the insulation resistance if it is greater than 1 million ohm then you can plug on the unit 8 Grounding test After maintenance use the multimeter to...

Страница 6: ...sed compressor model 5 Cooling System Diagram Note Arrow direction means the flowing direction of the refrigerant 6 Part Lists and explanation PRF047XW PRF071XW PRF3X PRF3XT Capillary Dry Filter Evapo...

Страница 7: ...starter or overload protector then fix back the terminal box cover and its clamp 3 Replace the door gasket seal Remove the old door gasket seal from the groove of the door linear then install the new...

Страница 8: ...7 8 Check the breakdowns of the cooling system Following the next illustration to check the problem...

Страница 9: ...ter Vacuuming and recharging Leakage check again Big quantity refrigerant air spurt out Cut off the high pressure pipe Normal suction of the comressor low pressure pipe No air suction or weak suction...

Страница 10: ...re vacuum and recharge the refrigerant at last do the leakage detecting again B If big quantity refrigerant spurt out cut off the high pressure pipe to check the suction of the compressor low pressur...

Страница 11: ...ed of the circuit or turn the thermostat to the coldest point the compressor can run Thermostat is breakdown There is sound when turning the knob of the thermostat The knob is broken or is not install...

Страница 12: ...d of refrigerant flowing in cooling system and it leaves oil on the welding point Leakage of refrigerant There is no sound of refrigerant flowing in cooling system and no oil on the welding point Insi...

Страница 13: ...tly The unit is not placed at good position The freezer is inside direct sunshine The unit can not dissipate the heat because sunshine The back of the unit is too close to the wall Too close will affe...

Страница 14: ...stem and control it more strictly Left water quantity control a If the cooling system parts like condenser evaporator compressor or the dry filter etc need to be replaced the replaced parts should be...

Страница 15: ...t condition And ensure to use a little as enough as possible Check the compressor is pressurized or not when opening When storing the R134a refrigerant must keep it sealed and not touch with atmospher...

Страница 16: ...happens again then should service again 12 Maintenance parts list No Parts name PCS unit Note 1 Compressor 1 2 Thermal protector of compressor 1 3 PTC starter 1 4 Feet of compressor 4 5 Refrigerant d...

Отзывы: