Special requirement during service process

 

(a). Duration of from opening of compressor to vacuuming process must be less than 10 

minutes, and for other parts not more than 12 minutes. 

(b)

  Vacuuming duration should not loess than 20 minutes.   

(c)

  If refrigerant leakage happens, it need to replace the compressor. Before welding, 

dry the cooling system by the nitrogen air.   

(d)

  If the dust blockage happens in cooling system pipe, if can be blow out by the 

nitrogen, don’t need to replace the compressor, otherwise the cabinet is no useful 
(and the evaporator is no useful). 

(e)

If  ice  blockage  happens  in  the  system  pipe,  must  replace  the  compressor. 

f

  Change the dry filter only if the system is opened. 

4) Main point of service

 

The  replaced  compressor  must  return  back  to  the  compressor  manufacturer  to  be 

treated. 

The compressor can’t  be tested through direct absorbing atmosphere, it will damage 

the compressor. 

If  the  system  pipe  is  opened  for  a  long  time  or  leakage  happens,  you  can  dry  the 

system by nitrogen during service. 

All of the welding material must be protected from wet condition. And ensure to use a 

little as enough as possible. 

   

Check the compressor is pressurized or not when opening. 

When  storing  the  R134a  refrigerant,  must  keep  it  sealed  and  not  touch  with 

atmosphere directly. 

 
 
 

11.    The performance testing requirement after service: 

    After completing the service, normally need to be done test  running for 1-2days. When 

proved to be safely and good cooling performance, then move to the customer or user. During 
test running, we suggest that you can do following item:   

1)

Insulation and safety

     

                Before  plugging  in,  use  the  DC  500  meg-ohm  meter  to  measure  the  insulation 

resistance between the live parts and dead metal enclosure, ensure the result is not lower 
than 1 meg-ohm. 

2)

Starting capability

 

The compressor can start smoothly, and can start or stop normally. If the unit can’t 

start  or  stop  normally,  must  find  the  root  cause  and  delete  the  cause,  then  you  can 
plugging it in to let it run. 

3)

Cooling performance

 

                After running for 24 hours, check that the frost on the surface of the cabinet linear is 

oven or not, and there is no frost on the suction pipe. 

4)

Electrical structure and safety

 

          After  service,  check  all  of  the  electrical  parts,  ensure  the  connection  terminal  of 

the electrical parts don’t loose and the grounding wire is ok. 

Содержание PRF047XW

Страница 1: ...Service Manual for Single Door Fridge PREMIUM MODEL PRF047XW PRF071XW PRF3X PRF3XT...

Страница 2: ...ng System Diagram 5 6 Part Lists and explanation 5 7 Disassembling and replacing of the components 6 8 Check the breakdowns of the cooling system 7 9 Table for quick answer for the field problem 9 10...

Страница 3: ...al and simple beautifu recessed handle Recessed door gasket seal easy to be discharged and cleaned Plastic material simple and practically One shelf and one drip tray inside Front Left and right side...

Страница 4: ...t keep the room good air circulation condition When cutting the suction pipe or discharging pipe of the compressor pay attention to the surplus refrigerant and internal pressure in cooling system pipe...

Страница 5: ...ce and assembly must use the multi meter to measure the insulation resistance if it is greater than 1 million ohm then you can plug on the unit 8 Grounding test After maintenance use the multimeter to...

Страница 6: ...sed compressor model 5 Cooling System Diagram Note Arrow direction means the flowing direction of the refrigerant 6 Part Lists and explanation PRF047XW PRF071XW PRF3X PRF3XT Capillary Dry Filter Evapo...

Страница 7: ...starter or overload protector then fix back the terminal box cover and its clamp 3 Replace the door gasket seal Remove the old door gasket seal from the groove of the door linear then install the new...

Страница 8: ...7 8 Check the breakdowns of the cooling system Following the next illustration to check the problem...

Страница 9: ...ter Vacuuming and recharging Leakage check again Big quantity refrigerant air spurt out Cut off the high pressure pipe Normal suction of the comressor low pressure pipe No air suction or weak suction...

Страница 10: ...re vacuum and recharge the refrigerant at last do the leakage detecting again B If big quantity refrigerant spurt out cut off the high pressure pipe to check the suction of the compressor low pressur...

Страница 11: ...ed of the circuit or turn the thermostat to the coldest point the compressor can run Thermostat is breakdown There is sound when turning the knob of the thermostat The knob is broken or is not install...

Страница 12: ...d of refrigerant flowing in cooling system and it leaves oil on the welding point Leakage of refrigerant There is no sound of refrigerant flowing in cooling system and no oil on the welding point Insi...

Страница 13: ...tly The unit is not placed at good position The freezer is inside direct sunshine The unit can not dissipate the heat because sunshine The back of the unit is too close to the wall Too close will affe...

Страница 14: ...stem and control it more strictly Left water quantity control a If the cooling system parts like condenser evaporator compressor or the dry filter etc need to be replaced the replaced parts should be...

Страница 15: ...t condition And ensure to use a little as enough as possible Check the compressor is pressurized or not when opening When storing the R134a refrigerant must keep it sealed and not touch with atmospher...

Страница 16: ...happens again then should service again 12 Maintenance parts list No Parts name PCS unit Note 1 Compressor 1 2 Thermal protector of compressor 1 3 PTC starter 1 4 Feet of compressor 4 5 Refrigerant d...

Отзывы: