protection in cooling mode, defrosting mode and the current protection.
7.4.2.3 Indoor fan running rules
In cooling mode, indoor fan runs all the time and the speed can be selected as high, medium, low
and auto.
The auto fan:
T1-Ts
High
Low
Medium
7.4.2.4 Low evaporator coil temperature T2 protection
T2
On
Off
When the evaporator coil temp.T2 keeps lower than setting value, the compressor and outdoor
fan will shut off.
7.4.2.5 High condenser temperature T3 protection(only for MS12F-21HR-NB8W)