SDI-JC-13D2 rev 8-22-22
page 9 of 14
Screen Settings
Parameter Default
Max.
Min.
Goto: Menu > Utilities > Screen Settings
1
Enable Enable Disable
Touch Buzzer Enable
Activates faceplate Tone when a screen item is touched
2
Disable Enable Disable
Alarm Buzzer Enable
Activates faceplate Tone when an Alarm is triggered.
Configure / Setup Analog Input Setup
Parameter Default
Max.
Min.
Goto: Menu > Configure/Setup > Ch.x Setup > Analog Input Setup
AinName
Input Name
User entered text, 12 character max, space permitting, use Upper and Lower case letters
3
4-20 mA 2.3 Volt 4-20 mA
Input Type
4-20 mA, 10K Thermistor, Type J Thermocouple, Type K Thermocouple, 10 Volt, 5 Volt,
2.3 Volt
4
2.0
30.0
0.5
Smoothing Filter Seconds
Dampens (smooths) rapid signal variations.
Larger values = more damping. Smaller values = less damping.
AinUnits
Input Units
User entered text, 8 character max, space permitting, use Upper and Lower case letters
5
F
C
F
Temperature F/C
F or C (Only used for T/C and Thermistor Input Types)
6
0.0
+15.0
-15.0
Temperature Adjust
(degrees)
The displayed value is offset from the measured value by this amount for all temperatures.
Used to calibrate out minor temperature differences due to sensor errors. The units are F or C,
as selected above. (Only used for T/C and Thermistor Input Types)
Configure / Setup mA/Vdc Scaling
Parameter Default
Max.
Min.
Goto: Menu > Configure/Setup > Ch.x Setup > Analog Input Setup > mA/Vdc Scaling
NOTE:
None of these Parameters are used for T/C and Thermistor Input Types
7
20.0
23.5
-0.5
Upper Range mA/Vdc
8
4.0
23.5
-0.5
Lower Range mA/Vdc
9
1
3
0
Display Decimal Digits
10
100.0
999999 -999999
Upper Range Scaled Display
.
11
0.0
999999 -999999
Lower Range Scaled Display
12
Disabled
Enabled Disabled
Square Root Option
Disabled, Enabled
Configure / Setup Bargraph Range
Parameter Default
Max.
Min.
Goto: Menu > Configure/Setup > Ch.x Setup > Bargraph Setup
13
0
3
0
Bargraph Tick Dec Pt
14
100.0
999.9
-999.9
Bargraph Top
This is the temperature value at the top of the bargraph.
The units are F or C, as selected above.
15
0.0
999.9
-999.9
Bargraph Bottom
This is the temperature value at the bottom of the bargraph.
The units are F or C, as selected above.