Installation 

 

JC-13D2 Indicator Mounting: 

The JC-13D2 Indicator is designed for flush mounting in an 

enclosure located in an indoor NEMA 12 environment.  

 
The JC-13D2 should not be subjected to excessive vibration. 

Continuous operation is guaranteed over the 32-131 F  
(0-55C) ambient operating range.  

 
See Full Size Cutout Template on the last page 
 

 
Wiring: 

Warning 

Disconnect all sources of power before installing or servicing this equipment. Multiple Disconnects may be required. 
Burner interface wiring must be performed by an experienced burner service technician.  

 

All wiring must comply with all local and national electrical codes. Tighten all terminals to 4.4 in-lb. Wire must be stranded copper, 
12-24 ga., 150V / 75 C insulation minimum. AC and DC wiring must be separated to prevent electrical noise coupling. Do not run 
AC and DC wires in the same conduits. Use shielded cables where shown, connect shields only where shown, insulate all other 
shields to prevent accidental grounding. Ignition transformer and motor VFD wiring are particularly electrically noisy and should be 
kept away from the thermocouple extension wire, and also all other AC and DC wiring. 

 

If the 4-20 mA output will not be used, jumper terminal 40 to 41 to prevent the OUTPUT FAILURE error message. 

 

Relay contacts are shown with power removed from the JC-13D2.  

 

All DC wiring is isolated from Ground. All DC wiring '-' terminals are connected together internally.  

 

RS485 is electrically Isolated from all other DC and AC wiring. 

 

Terminals 1-9 are Line Voltage AC. Terminals 31-50 are low voltage DC. 

 

 An external Line Voltage supply switch or circuit breaker, marked as the disconnect for this instrument, suitably located 
and easily reached, and complying with IEC 60947-1 and -3 must be provided. 

 

Fuse:

 

3.15 amp Slo-Blo, 250 V, 5x20mm (Littlefuse 02153.15HXP, Belfuse 5ST 3.15-R, Preferred Utilities 16740-3.15S) 

Caution

: To reduce the risk of fire, only replace fuse with the same type. 

 

 

 

Panel Cutout

3.61 x 7.65

3.88

8.00

Touch

Screen

8.74

Pl

ug

-in

 T

er

m

in

al

s

1.00

4.88

Pl

ug

-in

 T

er

m

in

al

s

Содержание JC-13D2

Страница 1: ...sensor Units totalizer Units 50 pt Alarm Event History Time Date Stamped Only 4 7 8 deep fits in most existing burner control cabinets Plug in field wiring terminals Modbus TCP Ethernet Modbus RTU RS...

Страница 2: ...ntinuously indicate the AIN Process Variable PV value The alarm setpoints are indicated on the bargraph with tic marks If the PV exceeds a Hi or HiHi Setpoint for more than 30 seconds adjustable the b...

Страница 3: ...ms Alarms will not be displayed on the Main and Menu screens All active Alarms are displayed on this screen High Alarm High High Alarm etc The PV and time date shown occurred when the Alarm time delay...

Страница 4: ...elds only where shown insulate all other shields to prevent accidental grounding Ignition transformer and motor VFD wiring are particularly electrically noisy and should be kept away from the thermoco...

Страница 5: ...ts 45 47 49 RS485 RS485 Common Ethernet 43 24 Vdc 7 ACDIN 1 8 ACDIN 2 37 24V 32 2 5Vref 38 AIN 3 39 DC 44 DCDIN 1 46 DCDIN 2 DC 24 Vdc 120 Vac 1 2 3 Relay 1 6 5 4 Relay 2 Channel 3 35 24V 32 2 5Vref 3...

Страница 6: ...r Fuse JC 10D2 31 34 33 A D 2 Wire 4 20 mA Xmtr INPUT TYPE mA Thermistor Fuse 24V JC 10D2 Thermocouple and Thermistor Field Wiring Notes Do not run in conduits with AC wiring Do not run in conduits wi...

Страница 7: ...nction DC DIN 2 Function Discrete Outputs ROUT 1 Function ROUT 2 Function DOUT 1 Function DOUT 2 Function 4 20 mA Outputs AOUT 0 1 Channel AOUT 0 1 4 mA AOUT 0 1 20 mA AOUT 0 2 Channel AOUT 0 2 4 mA A...

Страница 8: ...ow Cutoff Alarm 1 2 Types Alarm 1 Type Alarm 1 Reset Type Alarm 2 Type Alarm 2 Reset Type Bargraph Setup Tick Decimal Places Bargraph Top Bargraph Bottom Analog Input Setup Input Name Input Type Smoot...

Страница 9: ...t Types 6 0 0 15 0 15 0 Temperature Adjust degrees The displayed value is offset from the measured value by this amount for all temperatures Used to calibrate out minor temperature differences due to...

Страница 10: ...ion Totalized values can be reset to zero when User presses this button 28 Hour Day Minute Rate Time Base Minute Hour Day Examples gpm use Minute gph use Hour gal day use Day 29 x1 x1000000 x1 Rate Mu...

Страница 11: ...ed AIN Error Disabled DOUT 2 Function Disabled Alarm 1 Alarm 2 Common Alarm Horn AIN Error NOTE Horn is Off after Alarm s are silenced AIN Error means mA Vdc Out of Range T C Open Thermistor Shorted o...

Страница 12: ...H 2 Alarm 2 Setpoint 40117 RO UINT8 Enumeration CH 2 Alarm 2 Type 0 Disabled 1 LoLo 2 Lo 3 Hi 4 HiHi 40118 RO UINT32 CH 2 Totalizer Count 40120 RO FLOAT CH 3 Process Variable 40122 RO FLOAT CH 3 Alarm...

Страница 13: ...EL D4B Adapter Plate Panel Cutout 8 00 X 10 75 Specifications Mechanical Enclosure Nema 12 Faceplate Indoor Locations Bezel 3 7 8 w x 8 h x 1 d Rear Case 3 1 2 w x 7 9 16 h x 4 7 8 d Panel Cutout 3 6...

Страница 14: ...SDI JC 13D2 rev 8 22 22 page 14 of 14 Preferred Utilities Mfg Corp Preferred Instruments div 31 35 South Street Danbury CT 06810 203 743 6741 www preferred mfg com...