SDI-JC-13D2   rev 8-22-22

 

 

page 2  of  14 

SAFETY 

 

 

DANGER

 

Electric Shock Hazard

 

Multiple power sources may be present.  

Disconnect all electric power sources, local and remote, before servicing 

 

WARNING 

This product is intended for use in Commercial and Industrial installations,  

it is NOT intended for Residential use. 

This product is intended to be used by Trained Operators.  

 

Installation, start-up, and troubleshooting is intended to be done by  

Experienced Technicians familiar with Industrial Safety Codes  

and all Safety Codes specific to burners and boilers. 

  

This product is NOT a Primary Safety Interlock rated device.  

The Shutdown Relay Output should only be used as an  

additional auxiliary Operating limit and should not replace or bypass 

 any Primary Safety Interlock devices required by Safety Codes.  

 

Incorrect wiring connections to burner/boiler Flame Safeguard controls  

can cause Equipment Damage, Injury, or Death 

 

 
 

 
 

Alarm Sequence 

Alarm sequence is common to all three channels. Each channel has 2 programmable alarms. The Bargraph and Numeric display 
continuously indicate the AIN Process Variable (PV) value. The alarm setpoints are indicated on the bargraph with tic marks. If 
the PV exceeds a Hi (or HiHi) Setpoint for more than 30 seconds (adjustable), the bargraph blinks, the High (or High-High) Alarm 
message appears, the Common Alarm Relay energizes, and the current PV is logged with a time/date stamp. Similarly, for a Lo 
or LoLo Alarm. Pressing the ALARM SILENCE button de-energizes a Common Alarm output ROUT or 24 Vdc sinking DOUT.   
 
The Common Alarm output can be used to activate an external bell or horn. If the 

JC-13D2

 is alarm is configured as Auto Reset, 

the Alarm Output and Common Alarm output de-energize automatically when the PV drops below the (Alarm setpoint - the user 
set Deadband). Alternately, pressing the 

JC-13D2 

Alarm Silence pushbutton, or energizing an Alarm Silence input or sending a 

Modbus command will de-energize the Common Alarm Relay in order to silence an audible alarm.  
 
The Lo and LoLo alarms work in a similar manner. When PV drops below the SP the alarm is triggered. When PV rises above  
(SP + user set Deadband), the Alarm is cleared. 
 
If the Manual Reset option is selected, an alarm will not clear BOTH the PV returns to normal AND the user presses the RESET 
“button” on the touchscreen.

 

 

 

Содержание JC-13D2

Страница 1: ...sensor Units totalizer Units 50 pt Alarm Event History Time Date Stamped Only 4 7 8 deep fits in most existing burner control cabinets Plug in field wiring terminals Modbus TCP Ethernet Modbus RTU RS...

Страница 2: ...ntinuously indicate the AIN Process Variable PV value The alarm setpoints are indicated on the bargraph with tic marks If the PV exceeds a Hi or HiHi Setpoint for more than 30 seconds adjustable the b...

Страница 3: ...ms Alarms will not be displayed on the Main and Menu screens All active Alarms are displayed on this screen High Alarm High High Alarm etc The PV and time date shown occurred when the Alarm time delay...

Страница 4: ...elds only where shown insulate all other shields to prevent accidental grounding Ignition transformer and motor VFD wiring are particularly electrically noisy and should be kept away from the thermoco...

Страница 5: ...ts 45 47 49 RS485 RS485 Common Ethernet 43 24 Vdc 7 ACDIN 1 8 ACDIN 2 37 24V 32 2 5Vref 38 AIN 3 39 DC 44 DCDIN 1 46 DCDIN 2 DC 24 Vdc 120 Vac 1 2 3 Relay 1 6 5 4 Relay 2 Channel 3 35 24V 32 2 5Vref 3...

Страница 6: ...r Fuse JC 10D2 31 34 33 A D 2 Wire 4 20 mA Xmtr INPUT TYPE mA Thermistor Fuse 24V JC 10D2 Thermocouple and Thermistor Field Wiring Notes Do not run in conduits with AC wiring Do not run in conduits wi...

Страница 7: ...nction DC DIN 2 Function Discrete Outputs ROUT 1 Function ROUT 2 Function DOUT 1 Function DOUT 2 Function 4 20 mA Outputs AOUT 0 1 Channel AOUT 0 1 4 mA AOUT 0 1 20 mA AOUT 0 2 Channel AOUT 0 2 4 mA A...

Страница 8: ...ow Cutoff Alarm 1 2 Types Alarm 1 Type Alarm 1 Reset Type Alarm 2 Type Alarm 2 Reset Type Bargraph Setup Tick Decimal Places Bargraph Top Bargraph Bottom Analog Input Setup Input Name Input Type Smoot...

Страница 9: ...t Types 6 0 0 15 0 15 0 Temperature Adjust degrees The displayed value is offset from the measured value by this amount for all temperatures Used to calibrate out minor temperature differences due to...

Страница 10: ...ion Totalized values can be reset to zero when User presses this button 28 Hour Day Minute Rate Time Base Minute Hour Day Examples gpm use Minute gph use Hour gal day use Day 29 x1 x1000000 x1 Rate Mu...

Страница 11: ...ed AIN Error Disabled DOUT 2 Function Disabled Alarm 1 Alarm 2 Common Alarm Horn AIN Error NOTE Horn is Off after Alarm s are silenced AIN Error means mA Vdc Out of Range T C Open Thermistor Shorted o...

Страница 12: ...H 2 Alarm 2 Setpoint 40117 RO UINT8 Enumeration CH 2 Alarm 2 Type 0 Disabled 1 LoLo 2 Lo 3 Hi 4 HiHi 40118 RO UINT32 CH 2 Totalizer Count 40120 RO FLOAT CH 3 Process Variable 40122 RO FLOAT CH 3 Alarm...

Страница 13: ...EL D4B Adapter Plate Panel Cutout 8 00 X 10 75 Specifications Mechanical Enclosure Nema 12 Faceplate Indoor Locations Bezel 3 7 8 w x 8 h x 1 d Rear Case 3 1 2 w x 7 9 16 h x 4 7 8 d Panel Cutout 3 6...

Страница 14: ...SDI JC 13D2 rev 8 22 22 page 14 of 14 Preferred Utilities Mfg Corp Preferred Instruments div 31 35 South Street Danbury CT 06810 203 743 6741 www preferred mfg com...

Отзывы: