ADG-L Series Programmable DC Power Supply
105
Parameter
Start address
(hex)
Byte count
Data type
Unit
Precision
Abnormal sta-
tus 02
00 1A
1
Status flag
-
-
Bit-7
Fatal memory data error
Bit-6
Hardware over current protection
Bit-5
Hardware over voltage protection
Bit-4
Hardware over power protection
Bit-3
Reserved
Bit-2
FAN Error
Bit-1
Reserved
Bit-0
Programmable parameter error
Function code available
:
03
Example
:
Given the slave ID is 01 and fan error and HW-OVP occur
Send: 01 03 01 00 1A C9 8F
Receive: 01 03 00 01 24 18 0F