ADG-L Series Programmable DC Power Supply
99
5.4.2
Read register (error)
The master requests to read the slave (ID 01 hex) output voltage (start address 00 00
hex), but CRC check failed. Below is the query frame.
ID
01
The slave ID
Function code
03
Read the register data from the slave
Byte count
04
The byte cocunt of the output voltage is 4 bytes.
Start address (hi)
00
The start address of the output voltage (hi)
Start address (lo)
00
The start address of the output voltage (lo)
CRC check (lo)
58
The CRC value after checking 01 03 04 00 00 hex (lo)
CRC check (hi)
00
The CRC value after checking 01 03 04 00 00 hex (hi).
Below is the response frame sent by the slave,
ID
01
The slave ID
Function code
03
Read the register data from the slave.
Frame status
01
CRC check failed
Byte count
00
The byte count of the requested data is 0 byte
CRC check (lo)
F0
The CRC value after checking 01 03 01 00 hex (lo)
CRC check (hi)
48
The CRC value after checking 01 03 01 00 hex (hi)
Содержание ADG-L Series
Страница 24: ...ADG L Series Programmable DC Power Supply 16 Figure 2 1 The required space for the device...
Страница 77: ...ADG L Series Programmable DC Power Supply 69 Figure 3 32 Ethernet setting Figure 3 33 RS 232 RS 485 USB setting...
Страница 98: ...ADG L Series Programmable DC Power Supply 90 Figure 4 10 Export report CSV and TXT format...
Страница 127: ...ADG L Series Programmable DC Power Supply 119 Figure 6 9 Process to output reading voltage and setting voltage...
Страница 133: ...ADG L Series Programmable DC Power Supply 125 Figure 6 19 Current indicated value and set value calibration page...
Страница 135: ...ADG L Series Programmable DC Power Supply 127 Figure 6 22 Output power calibration page...