PD6100 Strain Gauge, Load Cell, & mV Meter Instruction Manual
32
Setting the Relay Action
Operation of the relays is programmed in the
Action
menu.
The relays may be set up for any of the following modes of
operation:
1. Automatic reset (non-latching)
2. Aut manual reset at any time (non-latching)
3. Latching (manual reset only, at any time)
4. Latching with Clear (manual reset only after alarm condition has cleared)
5. Pump alternation control (automatic reset only)
6. Sampling (the relay is activated for a user-specified time)
7. Off (relay state controlled by Interlock feature)
The following graphic shows relay 1 action setup; relay 2-8 are set up in a similar fashion.