PD6100 Strain Gauge, Load Cell, & mV Meter Instruction Manual
17
4-20 mA Output Connections
Connections for the 4-20 mA transmitter output are made to the connector terminals labeled MA OUT.
The 4-20 mA output may be powered internally or from an external power supply.
Figure 17. 4-20 mA Output Connections
Analog Output Power Supply
If the analog output is not using the 24 VDC supply to power the output loop, it can be used for other
things. The I+ Terminal is the +24 V and the R terminal is the return.
F4 Digital Input Connections
A digital input, F4, is standard on the meter. This digital input is connected with a normally open contact
across F4 and COM, or with an active low signal applied to the F4.
The functionality of the F4 input is set up in the Advanced Features,
User
menu.
Figure 18. F4 Digital Input Connections
12-35 VDC
Power
Supply
+
4-20 mA
Input Meter
-
+
R
I-
I+
1
3
2
RELAY1
3
2
1
24 V
-
4-20 mA Input
Remote Display,
Chart Recorder, Etc.
-
+
R
I-
I+
MA OUT
1
3
2
RELAY1
3
2
1
24 V
MA OUT
EX+
2
1
3
4
F4
SG+
SG-
INPUT SIGNAL
5
6
COM
EX-