ProtEX-MAX PD8-6310-WM Explosion-Proof NTEP Certified Batch Controller Instruction Manual
12
Note:
Testing was conducted on PD8-6300 series meters installed through the covers of grounded metal
enclosures with cable shields grounded at the point of entry representing installations designed to
optimize EMC performance. All hardware is identical to the PD6310 controllers.
Declaration of Conformity available at www.predig.com
Safety Information
WARNINGS
•
Read complete instructions prior to installation and operation of the instrument.
•
Installation and service should be performed only by trained service personnel. Service
requiring replacement of internal sub-components must be performed at the factory.
•
Disconnect from supply before opening enclosure. Keep cover tight while circuits are alive.
Conduit seals must be installed within 18" (450mm) of the enclosure or within 2" (50mm) for
Zone installations.
•
Verify that the operating atmosphere of the instrument is consistent with the appropriate
hazardous locations certifications.
•
If the instrument is installed in a high voltage environment and a fault or installation error
occurs, high voltage may be present on any lead
•
Read all product labels completely and follow all instructions and requirements listed on the
labels for installation or service.
Installation
Install in accordance with applicable local and national regulations (e.g. NEC).
For Installation in USA:
The ProtEX-MAX must be installed in accordance with the National Electrical
Code (NEC) NFPA 70.
For Installation in Canada:
The ProtEX-MAX must be installed in accordance with the Canadian Electri-
cal Code CSA 22.1. All power supplies below 36 V and input circuits must be derived from a CSA Ap-
proved Class 2 source.
For European Community:
The ProtEX-MAX must be installed in accordance with the ATEX directive
94/9/EC and the product certificate Sira 12ATEX1182.
WARNING
Disconnect from supply before opening enclosure. Keep
cover tight while circuits are alive. Conduit seals must be in-
stalled within 18" (450mm) of the enclosure or within 2"
(50mm) for Zone installations.
Wiring connectors are accessed by opening the enclosure. To access electrical connectors, remove the 2
captive screws and then remove the electronics module. Connectors are on the rear of the electronics
module.