PD6720 Field-Mount Loop-Powered Rate/Totalizer 

Instruction Manual 

 

6

 

Rate/Totalizer 

Rate Display

  

0 to 99,999 leading zero blanking 

Total Display 

0 to 9,999,999 leading zero blanking 

Total Decimal 
Point 

Up to six decimal places or none: 
d.dddddd, d.ddddd, d.dddd, d.ddd,  
d.dd, d.d, or ddddddd 

Lower Display 
Configuration 

Can be programmed to display total, 
tag name/engineering units, or to 
alternate between them. 

Totalizer 

Calculates total based on rate, time 
base of second, minute, hour, or day, 
and field programmable multiplier; 
stored in non-volatile memory upon 
power loss.  

Totalizer Reset 

Via front panel SafeTouch button,  
time delay, external contact closure,  
or protected 

Total Conversion 
Factor 

0.000001 to 9,999,999 

Totalizer Rollover 
 

Display rolls over when display 
exceeds 9,999,999. Relay status 
reflects the displayed value. 

Total Reset Delay 

Programmable from 0 to 99,999 
seconds 

 

Open Collector Output 

Rating 

Isolated open collector, sinking NPN 
30 VDC @ 150 mA max. 

Alarm Output 

Assign to rate for high or low alarm trip 
point. 
Assign to total for total alarm trip point. 

Deadband 

0-100% FS, user selectable 

Acknowledge 

Front panel ACK button resets output 
and screen indication. 

Pulse Output  
Scaler (Count) 

The pulse output scaler (count) is 
programmable from 0.0001 to 99999. 
One pulse is generated for every total 
increment selected (e.g. A pulse scaler 
value of 100 will generate one pulse 
every time the total is incremented by 
100 units). 
If the pulse output exceeds the 
programmed output frequency, pulses 
are accumulated as pending and are 
not lost. Pulses will continue to output 
until the buffer is emptied or the total is 
reset from the front panel. 

Pulse Output 
Frequency 

Programmable frequency:  
2, 4, 8, 16, 32, 64, 128 Hz. 
Minimum pulse width: 3.9 ms @ 128 Hz  
Maximum pulse width: 250 ms @ 2 Hz 
Factory default pulse width: 
31 ms @ 16 Hz 

EFT 

±2 kV DC mains, ±1 kV other 

Telco Surge 

±1 kV 

CRFI 

3 V, 0.15-80 MHz, 1 kHz 80% AM 

 

 

Содержание PD6720 Series

Страница 1: ...Display Rate in Units per Second Minute Hour or Day Display Open Channel Flow with Programmable Exponent Feature Open Collector Pulse or Alarm Output Display Mountable at 0 90 180 270 SafeTouchTM Thro...

Страница 2: ...Terms Conditions on www predig com for complete details 2020 Precision Digital Corporation All rights reserved Introduction The PD6720 is a rugged field mount loop powered rate totalizer fully featur...

Страница 3: ...ime Base t base 15 Setting the Total Conversion Factor totCF 15 Manual or Automatic Total Reset Function t rST 16 Setting the Tag Display tag 16 Setting Up the Password PASSWRD 17 Locking the Meter 17...

Страница 4: ...Enclosure Dimensions Side Cross Section View 7 Figure 3 Connector Board 8 Figure 4 Connections without Backlight 9 Figure 5 Connections with Loop Powered Backlight 9 Figure 6 Connections with Externa...

Страница 5: ...Environmental Operating temperature range 40 to 75 C Storage temperature range 40 to 75 C Relative humidity 0 to 90 non condensing Connections Screw terminals accept 12 to 22 AWG wire Enclosure NEMA...

Страница 6: ...able from 0 to 99 999 seconds Open Collector Output Rating Isolated open collector sinking NPN 30 VDC 150 mA max Alarm Output Assign to rate for high or low alarm trip point Assign to total for total...

Страница 7: ...and set the display module aside Unpacking Remove the meter from box Inspect the packaging and contents for damage Report damages if any to the carrier If any part is missing or the meter malfunction...

Страница 8: ...t from external supply OUTPUT NPN open collector output positive OUTPUT NPN open collector output negative RESET Contact closure alarm acknowledge pull up to 3 VDC RESET Contact closure alarm acknowle...

Страница 9: ...ions are made to two terminals labeled RESET Connect to a contact closure source such as a relay or a pushbutton as shown in Figure 7 Figure 7 Reset Connections Open Collector Output Connections Outpu...

Страница 10: ...sors are disabled when a mechanical button is pressed and will automatically be re enabled after 60 seconds of inactivity The SafeTouch buttons are designed to filter normal levels of ambient interfer...

Страница 11: ...nds to access the Advanced features of the meter Right Reset Button Press the Right arrow button to move to the next digit or decimal position during programming Up Display Button Press the Up arrow b...

Страница 12: ...ogram menu sCalE Scale Enter the Scale menu Cal Calibrate Enter the Calibrate menu Inpt1 Input 1 Calibrate input 1 signal or program input 1 value DspL1 Display 1 Program display 1 value Inpt2 Input 2...

Страница 13: ...w to select next digit and Up arrow to increment digit The digit being changed blinks Press the Enter button at any time to accept a setting or MENU button to exit without saving changes The decimal p...

Страница 14: ...functions are exclusive of each other The meter uses the last function programmed Only one of these methods can be employed at a time The Scale and Calibrate functions can use up to 32 points default...

Страница 15: ...complete the calibration or scaling of the meter The minimum span is 0 10 mA If the minimum span is not maintained the meter reverts to input 2 allowing the appropriate input signals to be applied Re...

Страница 16: ...on choose man dsabl To reset total upon total alarm set point choose auto enter a time delay t dly and proceed to programming the set point see Alarm Output alrm on page 19 Press the Enter button at a...

Страница 17: ...returns to its password protected condition Disabling Password Protection To disable the password protection access the Password menu and enter the correct password twice as shown below The meter is n...

Страница 18: ...total Set Set Point Program set point Reset Reset Point Program reset point Pulse Pulse Output Program pulse output Scaler Count MAX HZ Frequency Program pulse output maximum frequency Funct Function...

Страница 19: ...deadband is one display count If set and reset points are programmed the same output will reset one count below set point Total alarm trip point program total set point Alarm reset is triggered by tot...

Страница 20: ...rent source instead of using input scaling This process will override previously programmed scaling points Apply a live signal using a known accurate signal source InP 1 32 and then enter the correspo...

Страница 21: ...ging time and so the longer the display may take to find its final value The filter contains a noise filter bypass feature so that while small variations in the signal will be filtered out large abrup...

Страница 22: ...he factory defaults Instructions to load factory defaults Enter the Advanced features menu Press and hold Reset button when INFO is shown Press Enter when RESET DFALTS prompt is shown Note If Enter is...

Страница 23: ...exit Max Min display readings Display response is too slow Check filter setting to see if it can be lowered to LO or OFF If the display locks up or the meter does not respond at all Perform hard rese...

Страница 24: ...on or increment digit Cycle through maximum minimum and mA display mode ENTER Accept selection value and move to next selection Acknowledge alarms Max Min Mode While in Run Mode pressing Up Arrow will...

Страница 25: ...990 www predig com LIM6720_C SFT049 Ver 1 200 up 07 20 Contact Precision Digital Technical Support Call 800 610 5239 or 508 655 7300 Fax 508 655 8990 Email support predig com Sales Support Call 800 34...

Отзывы: