background image

PD6720 Field-Mount Loop-Powered Rate/Totalizer 

Instruction Manual 

 

23

 

Troubleshooting 

Due to the many features and functions of the meter, it’s possible that the setup of the meter does not agree with 
what an operator expects to see. If the meter is not working as expected, refer to the 

Diagnostics 

menu and consult 

the recommendations described below. 

Troubleshooting Tips 

Symptom 

Check/Action 

No display or faint display 

Check input signal connections.  

Perform hard reset by shorting S+ and S- terminals. 

Rate display unsteady 

Increase filter setting in 

Advanced

 menu. 

Meter displays error message during calibration  
(

Span

 

eRROR

Check signal connections. 

Verify minimum input span requirements. 

Meter flashes 99999 or -9999 

Check input signal is within scaled range of 99999 and -9999. 

Display stuck displaying 

MAXIMUM

 or 

MINIMUM

 

Press 

Menu

 to exit Max/Min display readings.  

Display response is too slow 

Check filter setting to see if it can be lowered to 

LO

 or 

OFF

.

 

If the display locks up or the meter does not  
respond at all  

Perform hard reset by shorting S+ and S- terminals. 

Backlight does not appear. 

Backlight is intended for viewing assistance in dim lighting 
conditions. It may not be noticeable under good lighting conditions. 

Check connections are as shown in 

Figure 5. Connections with 

Loop-Powered Backlight

 or 

Figure 6. Connections with Externally-

Powered Backlight 

on page 

9

. 

SafeTouch buttons do not respond

 

Service menu was selected, or mechanical button was pushed. 
The SafeTouch

 

buttons will be re-enabled automatically  

60 seconds 

after the last button push. 

If slide switch on connector board is in Lock position,  
switch to Unlock. 

Sunlight can interfere with the sensors. It is recommended to shield 
the window from sunlight while operating the buttons by standing so 
as to block direct sunlight. 

Other symptoms not described above 

Call Technical Support for assistance. 

Содержание PD6720 Series

Страница 1: ...Display Rate in Units per Second Minute Hour or Day Display Open Channel Flow with Programmable Exponent Feature Open Collector Pulse or Alarm Output Display Mountable at 0 90 180 270 SafeTouchTM Thro...

Страница 2: ...Terms Conditions on www predig com for complete details 2020 Precision Digital Corporation All rights reserved Introduction The PD6720 is a rugged field mount loop powered rate totalizer fully featur...

Страница 3: ...ime Base t base 15 Setting the Total Conversion Factor totCF 15 Manual or Automatic Total Reset Function t rST 16 Setting the Tag Display tag 16 Setting Up the Password PASSWRD 17 Locking the Meter 17...

Страница 4: ...Enclosure Dimensions Side Cross Section View 7 Figure 3 Connector Board 8 Figure 4 Connections without Backlight 9 Figure 5 Connections with Loop Powered Backlight 9 Figure 6 Connections with Externa...

Страница 5: ...Environmental Operating temperature range 40 to 75 C Storage temperature range 40 to 75 C Relative humidity 0 to 90 non condensing Connections Screw terminals accept 12 to 22 AWG wire Enclosure NEMA...

Страница 6: ...able from 0 to 99 999 seconds Open Collector Output Rating Isolated open collector sinking NPN 30 VDC 150 mA max Alarm Output Assign to rate for high or low alarm trip point Assign to total for total...

Страница 7: ...and set the display module aside Unpacking Remove the meter from box Inspect the packaging and contents for damage Report damages if any to the carrier If any part is missing or the meter malfunction...

Страница 8: ...t from external supply OUTPUT NPN open collector output positive OUTPUT NPN open collector output negative RESET Contact closure alarm acknowledge pull up to 3 VDC RESET Contact closure alarm acknowle...

Страница 9: ...ions are made to two terminals labeled RESET Connect to a contact closure source such as a relay or a pushbutton as shown in Figure 7 Figure 7 Reset Connections Open Collector Output Connections Outpu...

Страница 10: ...sors are disabled when a mechanical button is pressed and will automatically be re enabled after 60 seconds of inactivity The SafeTouch buttons are designed to filter normal levels of ambient interfer...

Страница 11: ...nds to access the Advanced features of the meter Right Reset Button Press the Right arrow button to move to the next digit or decimal position during programming Up Display Button Press the Up arrow b...

Страница 12: ...ogram menu sCalE Scale Enter the Scale menu Cal Calibrate Enter the Calibrate menu Inpt1 Input 1 Calibrate input 1 signal or program input 1 value DspL1 Display 1 Program display 1 value Inpt2 Input 2...

Страница 13: ...w to select next digit and Up arrow to increment digit The digit being changed blinks Press the Enter button at any time to accept a setting or MENU button to exit without saving changes The decimal p...

Страница 14: ...functions are exclusive of each other The meter uses the last function programmed Only one of these methods can be employed at a time The Scale and Calibrate functions can use up to 32 points default...

Страница 15: ...complete the calibration or scaling of the meter The minimum span is 0 10 mA If the minimum span is not maintained the meter reverts to input 2 allowing the appropriate input signals to be applied Re...

Страница 16: ...on choose man dsabl To reset total upon total alarm set point choose auto enter a time delay t dly and proceed to programming the set point see Alarm Output alrm on page 19 Press the Enter button at a...

Страница 17: ...returns to its password protected condition Disabling Password Protection To disable the password protection access the Password menu and enter the correct password twice as shown below The meter is n...

Страница 18: ...total Set Set Point Program set point Reset Reset Point Program reset point Pulse Pulse Output Program pulse output Scaler Count MAX HZ Frequency Program pulse output maximum frequency Funct Function...

Страница 19: ...deadband is one display count If set and reset points are programmed the same output will reset one count below set point Total alarm trip point program total set point Alarm reset is triggered by tot...

Страница 20: ...rent source instead of using input scaling This process will override previously programmed scaling points Apply a live signal using a known accurate signal source InP 1 32 and then enter the correspo...

Страница 21: ...ging time and so the longer the display may take to find its final value The filter contains a noise filter bypass feature so that while small variations in the signal will be filtered out large abrup...

Страница 22: ...he factory defaults Instructions to load factory defaults Enter the Advanced features menu Press and hold Reset button when INFO is shown Press Enter when RESET DFALTS prompt is shown Note If Enter is...

Страница 23: ...exit Max Min display readings Display response is too slow Check filter setting to see if it can be lowered to LO or OFF If the display locks up or the meter does not respond at all Perform hard rese...

Страница 24: ...on or increment digit Cycle through maximum minimum and mA display mode ENTER Accept selection value and move to next selection Acknowledge alarms Max Min Mode While in Run Mode pressing Up Arrow will...

Страница 25: ...990 www predig com LIM6720_C SFT049 Ver 1 200 up 07 20 Contact Precision Digital Technical Support Call 800 610 5239 or 508 655 7300 Fax 508 655 8990 Email support predig com Sales Support Call 800 34...

Отзывы: