Model PD6200 Analog Input Rate/Totalizer
Instruction Manual
77
Tips:
•
Low and high input signals can be any valid value within the
range of the meter.
•
Observe minimum input span requirements between input 1
and input 2.
•
Low input should be less than high input signal.
Error Message (
Error
)
An error message indicates that the calibration or scaling process was not
successful.
After the error message is displayed, the meter reverts to
input 2 during
calibration or scaling and to input 1 during internal calibration, allowing
the appropriate input signal to be applied or programmed.
The error message might be caused by any of the following conditions:
1. Input signal is not connected to the proper terminals, or it is con-
nected backwards.
2. Wrong signal selection in
Setup
menu.
3. Minimum input span requirements not maintained.
Minimum Input Span
The minimum input span is the minimum difference between input 1 and
input 2 signals required to complete the calibration or scaling of the meter.
Input range
Input 1 & input 2 span
4-20 mA
0.15 mA
±
10 VDC
0.10 VDC