![PRECISION DIGITAL PD6200 Скачать руководство пользователя страница 71](http://html1.mh-extra.com/html/precision-digital/pd6200/pd6200_instruction-manual_1594044071.webp)
Model PD6200 Analog Input Rate/Totalizer
Instruction Manual
71
Select Menu (
SElEct
)
The
Select
menu is used to select the math function applied to the input
(linear, square root, programmable exponent, or round horizontal tank),
low-flow cutoff, and analog output programming. The multi-point lineari-
zation is part of the linear function selection.
AoutPr
Select
Calib
AoutPr
Underrange
Break
Max
Min
O-rang
AoutPr
Source
AoutPr
select
Functn
Select
Cutoff
Select
Square
Functn
Prog E
Functn
rHt
Functn
Program
cutoff
value
Linear
Functn
Math Function Selection (
Functn
)
The
Function
menu is used to select the math function applied to the
input: linear, square root, programmable exponent, or round horizontal
tank volume calculation. The multi-point linearization is part of the linear
function selection.
Meters are set up at the factory for linear function with 2-point lineariza-
tion. The linear function provides a display that is linear with respect to
the input signal.
Square Root Linearization (
Square
)
The square root function can be used to linearize the signal from a diffe-
rential pressure transmitter and display flow rate in engineering units.