Model PD6200 Analog Input Rate/Totalizer
Instruction Manual
72
Programmable Exponent Linearization (
Prog E
)
The programmable exponent can be used to linearize the signal from
level transmitters in open-channel flow applications using weirs and
flumes.
Multi-Point Linearization (
Linear
)
Meters are set up at the factory for linear function with 2-point lineariza-
tion. Up to 32 linearization points can be selected under the linear func-
tion.
The multi-point linearization can be used to linearize the display for
non-linear signals such as those from level transmitters used to measure
volume in odd-shaped tanks or to convert level to flow using weirs and
flumes with complex exponent.
Program
Number of
Points
Linear
Functn
no Pts
Linear
scALE
Select
Round Horizontal Tank Linearization (
rHt
)
This function automatically calculates the volume in a round horizontal
tank with flat ends.
Set the display for the desired decimal point and engineering units be-
fore entering the round horizontal tank function. Enter the diameter and
the length in inches and the results are given in US gallons.
The meter can be scaled to display the volume in any engineering unit.
rht
Functn
diamr
rht
LEngth
rht
04
8
.000
diamr
Scale
Select
12
0
.000
Length
940.02
GAL-US