Model PD6200 Analog Input Rate/Totalizer
Instruction Manual
73
Low-Flow Cutoff (
CutofF
)
The low-flow cutoff feature allows the meter to be programmed so that
the often-unsteady output from a differential pressure transmitter, at low
flow rates, always displays zero on the meter.
The cutoff value may be programmed from 0 to 999999. The meter will
display zero below the cutoff value. Programming the cutoff value to zero
disables the cutoff feature.
Analog Output Programming (
AoutPr
)
The
Analog Output Programming
menu is used to program the behavior
of the 4-20 mA output. The following parameters and functions are pro-
grammed in this menu:
1. Source: Source for generating the 4-20 mA output (e.g. PV)
2. Overrange: Analog output value with display in overrange condition
3. Underrange: Analog output value with display in underrange condition
4. Break: Analog output value when loop break is detected
5. Max: Maximum analog output value allowed regardless of input
6. Min: Minimum analog output value allowed regardless of input
7. Calibrate: Calibrate the internal 4-20 mA source reference used to
scale the 4-20 mA output
Analog Output Source
The source for generating the 4-20 mA output may be assigned to the
rate/process variable, total, grand total, maximum or minimum value
reached by the rate/process, or one of the set points.
rate
Source
Source
AoutPr
Set Points
1 - 8
tot
Source
gtotal
Source
min
Source
max
Source
Analog Output Calibration
To perform the analog output calibration it’s recommended to use a mil-
liamp meter with a resolution of at least 0.1 µA to measure the output
current. The values saved internally during this procedure are used for
scaling the 4-20 mA output in the
Setup
menu.