Loop Leader PD6620 Series Loop-Powered Rate/Totalizer Instruction Manual 

 

 

43

 

Programmable Function Keys User Menu (

USER

The 

User 

menu allows the user to assign the front panel function keys F1, F2, and F3, and the digital in-

put (located on the signal input connector) to access some of the menus or to activate certain functions 

immediately (e.g. reset max & min, hold relay states, etc.). This allows the meter to be greatly customized 

for use in specialized applications. 

 

Function Keys & Digital Input Available Settings 

Refer to the following table for descriptions of each available function key or digital input setting.  

Display 

Description 

DISP FN

 

Set the function key or digital input to dis-

play a value 

  DISPLAY

 

Cycle max, min, rate, total, and grand total 

  D RATE

 

Display the rate 

  D TOTAL

 

Display the total 

  DISP GT

 

Display the grand total 

  PCT.RATE

 

Display the rate’s percentage of max (20 

mA) 

  D UNITS

 

Display rate, total, and grand total units 

  D TAG

 

Display the tags 

  DISPMIN

 

Display the minimum rate value 

  DISPMAX

 

Display the maximum rate value 

  MIN MAX

 

Display the minimum and maximum rate 

value 

  D mA IN

 

Display the current mA input value 

  D mAOUT

 

Display the current mA output value 

MENU FN

 

Set the function key or digital input to ac-

cess a menu 

  RLYINFO

 

Go to relay information menu (

INFO

  MANCTRL

 

Go to output control menu (

CONTROL

)

 

  TIMR OC1 

Open collector 1 timer 

  TIMR OC2 

Open collector 2 timer  

  TIMER R1 

Relay 1 timer 

  TIMER R2 

Relay 2 timer 

TIMER.FN

 

Set the function key or digital input to start 

or stop a timer 

  STRT.ALL

 

Start all timers 

  STOP.ALL

 

Stop all timers 

  S.STP.ALL

 

Start or stop all timers 

  OC1

 

Start/stop open collector 1 timer 

  OC2

 

Start/stop open collector 2 timer 

  RLY1

 

Start/stop relay 1 timer 

  RLY2

 

Start/stop relay 2 timer 

    START

 

Start the selected timer output 

    STOP

 

Stop the selected timer output 

    STR-STP

 

Start or stop the selected timer output 

Display 

Description 

BATCH.FN 

Set the function key or digital input to 

batch control 

  START 

Start a batch 

  STOP 

Stop a batch 

  STR-STP 

Start or stop a batch 

  PRESET 

Preset batch amount 

ALARM.FN 

Set the function key or digital input to 

acknowledge an alarm 

  ACK 

Acknowledge all active alarms 

  SETPOINT 

View all output set points 

  SETPT.OC1 

View open collector 1 set points 

  SETPT.OC2 

View open collector 2 set points 

  SETPT.R1 

View relay 1 set points 

  SETPT.R2 

View relay 2 set points 

SWATCH.FN 

Set the function key or digital input to 

activate stopwatch 

  START 

Start the stopwatch 

  STOP 

Pause/Stop the stopwatch 

  STR-STP 

Start or stop the stopwatch 

HOLD FN 

Set the function key or digital input to hold 

an output 

  HOLD.OUT 

Hold all outputs 

  HLD.UNHLD 

Hold or un-hold all outputs 

  OC1+2 

Hold/un-hold open collector outputs 

  RLY1+2 

Hold/un-hold relay outputs 

  mAOUT 

Hold/un-hold 4-20 mA output 

    HOLD 

Hold selected output 

    HLD.UNHLD 

Hold or un-hold selected output 

DISABLE 

Disable function key or digital input 

RST FN 

Set the function key or digital input to reset 

a value 

  RESET 

Reset min, max, or max/min PV value 

  R MIN.MAX 

Reset max and min PV value 

  RST T 

Reset the total 

  RST GT 

Reset the grand total 

  RST T.GT 

Reset the total and grand total 

 

 

USER

USER

F1

USER

F2

USER

F3

USER

DI

USER

HINT

F1

DISP FN

F1

MENU FN

F1

TIMER.FN

F1

BATCH.FN

F1

HOLD FN

F1

RST FN

F1

DISABLE

HINT

OFF

HINT

ON

F1

ALARM.FN

Содержание Loop Leader PD6620 Series

Страница 1: ...to 75 C Safe Area Operating Temperature Range Free PC Based USB Programming Software 5 Digit Alphanumeric Top Line 8 Digit Alphanumeric Bottom Line 8 Digit Total Grand Total Display with 13 Digits Usi...

Страница 2: ...ult in personal injury or property loss Anyone using this product for such applications does so at his her own risk Precision Digital Corporation shall not be held liable for damages re sulting from s...

Страница 3: ...Units UNITS 26 Changing the Decimal Point Location DEC PT 26 Enabling or Disabling the Comma on the Bottom Display COMMA 26 Programming the Bargraph PD6624 PD6628 Only 26 Changing What is Displayed T...

Страница 4: ...backlight so they add very little burden to the loop Additional features that allow these instruments to be installed virtually anywhere include a NEMA 4X IP65 front panel an operating temperature ra...

Страница 5: ...ruments Loop Leader PD6626 Standard Decimal Models Hazardous Area Model Description PD6626 LNN Loop Powered Hazardous Area No Options PD6626 L2N Loop Powered Hazardous Area Two Solid State Relays PD66...

Страница 6: ...Update Second Ambient 20 C 1 Update 2 Seconds From 20 C to 40 C the update rate slows down 1 second for every 2 C e g at 24 C 1 update 4 seconds Overrange Top 99999 Bottom 99 999 999 flashing Underra...

Страница 7: ...gle or dual relay batching with optional preclose for dual stage operation Batch Preset Set via F2 function key anywhere between 0 0001 to 99 999 based on batch total deci mal point If batch total is...

Страница 8: ...ce Rate total re transmit reverse scaling allowed Scaling Range 1 00 to 23 0 mA Disable High impedance state less than 1 mA Calibration Factory calibrated 4 00 to 20 00 mA Underrange 1 0 mA 3 5 mA or...

Страница 9: ...IEC 61010 1 2010 Third Edition Safety requirements for electrical equipment for measurement control and laboratory use Additional Standards UL 50E Hazardous Area Approvals ATEX Certificate Number CML...

Страница 10: ...erate an ignition capable level of electrostatic charge Therefore the equipment shall not be installed in a location where the external conditions are conducive to the build up of electrostatic charge...

Страница 11: ...transmitter PD6626 PD6628 loop powered meter and associated apparatus barrier must be compatible PD6626 PD6628 Series Loop Powered meters do not add capacitance or inductance to the loop under normal...

Страница 12: ...ackets provided with the meter back off the two screws so that there is 6 4 mm or less through the bracket Slide the bracket toward the front of the case and remove Insert meter into the panel cutout...

Страница 13: ...ontrol Drawing LIM6600 2 in order to meet agency approval ratings Use copper wire with 60 C or 60 75 C insulation for all line voltage connections Observe all safety regulations Electrical wiring shou...

Страница 14: ...loop There are no switches or jumpers to set up for the input Setup and programming is performed through the front panel buttons or PC based software Figure 5 4 20 mA Input Connection without Backligh...

Страница 15: ...OUT The 4 20 mA output must be powered from an external power supply Figure 8 4 20 mA Output Connections Safe Area Solid State Relay Connections Relay connections are made to a four terminal connecto...

Страница 16: ...ruction Manual 16 Safe Area Open Collector Outputs Open collector output 1 and 2 connections are made to terminals labeled O1 and O1 and O2 and O2 Connect the alarm or pulse input device as shown belo...

Страница 17: ...6624 PD6628 Button Symbol Description LCD Status Menu Alarm Indicator PD6622 Only Right Arrow F1 Password Protection Indicator PD6622 Only Up Arrow F2 G Grand Total Indicator PD6622 Only Enter F3 T To...

Страница 18: ...se The meter connects to the PC via a provided micro USB cable and is powered by the USB connection so no additional power is needed during programming For detailed software instructions or to downloa...

Страница 19: ...Open collector 1 setup OUTPUT2 Open collector 2 setup DISABLE Disable the open collector PULSE Program the open collector for pulse output ALARM Program the open collector for alarm output TIMER Prog...

Страница 20: ...econds OFF Turn filter off BYPASS Set filter bypass 0 0 to 99 9 FS PASSWRD Set a password for the meter MAIN Program the main meter password TOTAL Program the total reset password Parameter Action Set...

Страница 21: ...or disable the totalizer ENABLE Enable the totalizer Default DISABLE Disable the totalizer see PD6602 manual BACKLITE Enable or disable the display back light Parameter Action Setting Description ENA...

Страница 22: ...AG Display the rate and its tag alter nating R UNITS Display the rate units T UNITS Display the total units TAG Display the tag Parameter Action Setting Description UNITS Display the units PRESET Disp...

Страница 23: ...igit and Up Arrow to increment digit value The selected digit will flash Press and hold Up Arrow to auto increment the display value If you have made a mistake or would like to enter a new value selec...

Страница 24: ...NIST standards A calibrated signal source is not needed to scale the meter Enter the Input menu to scale the meter to display the 4 20 mA input The input is capable of accepting any signal from 4 to 2...

Страница 25: ...ld the Right Arrow while no character is being edited to erase all characters to the right of the flashing character Press and hold Up or Right Arrow to auto increment or decrement a selected characte...

Страница 26: ...nt is dis played and then it moves to the leftmost position Pressing the Up Arrow moves the decimal point one place to the left The decimal point location is set independently for the rate total and g...

Страница 27: ...g alternating Total its units and the rate units alternating Grand total with units or tag alternating Grand total units and rate units alternating Rate with units or tag alternating Rate and the tota...

Страница 28: ...uts two solid state relays and one 4 20 mA output The Output menu will only show options for the available out puts See Ordering Information on page 5 for details SETUP OUTPUT OPEN COLLECTR OUT RELAY...

Страница 29: ...R turns the open collector on and off at the specified time intervals The timer can be set as single shot or continuous timer A total reset output generates a pulse whenever the total is reset regardl...

Страница 30: ...per unit of measure For example if the k factor is 0 001 and the units are gallons one pulse will be generated for every 1 000 gallons The maximum fre quency is 1 000 Hz Setting output 2 to quadrature...

Страница 31: ...point is the display value at which the alarm will turn on and the reset point is the display value at which the alarm will turn off If the set point is lower than the reset point the alarm will be a...

Страница 32: ...o 99 hrs 59 min and 59 seconds The stopwatch function may be assigned to any open collector There are three settings needed to use the function effectively 1 Assign stopwatch to either top or bottom d...

Страница 33: ...le shot or continuous timer For use in batch control applications the meter relays may be set to batch This will enable the batch control features of the meter The stopwatch output STPWATCH allows the...

Страница 34: ...The set point is the display value at which the alarm will turn on and the reset point is the display value at which the alarm will turn off If the set point is lower than the reset point the alarm w...

Страница 35: ...rogram the Off Delay OFF DLAY from 1 second to 99 hours 59 minutes and 59 seconds This is the time it takes from selecting START to turning on the output and for how long the output is off in continuo...

Страница 36: ...on MANUAL or AUTO If setting batching to automatic a delay before the next batch is started must be programmed The PRESET amount is the value at which the batch will stop and can be programmed up to t...

Страница 37: ...topwatch function is used to open and close a solenoid valve to know the exact amount of time needed to complete the desired sample Once this is determined the timer function can be used to automatica...

Страница 38: ...responding mA output signals Rate or Total RATE or TOTAL To scale the analog output enter display value 1 and a corresponding analog output value for this display then enter display value 2 and a corr...

Страница 39: ...AL The Advanced Rate menu contains options to apply signal input conditioning functions to the input and scale calibrate the input signal The Advanced Total and Advanced Grand Total menus contain opti...

Страница 40: ...display for non linear signals to convert level to flow using weirs and flumes with complex expo nent Advanced Total and Grand Total Programming ADV TOTAL ADV GTOTAL The advanced total and grand tota...

Страница 41: ...rce is strongly recommended 1 After accessing the SCALE CAL menu press the Right Arrow button to scroll to the Calibration menu CAL RATE and press Enter 2 Select the appropriate units for the desired...

Страница 42: ...ere are three password types available Main Total and Grand Total The Main password prevents access to the meter Programming Mode Total and Grand Total passwords prevent resetting of and changes to th...

Страница 43: ...tart all timers STOP ALL Stop all timers S STP ALL Start or stop all timers OC1 Start stop open collector 1 timer OC2 Start stop open collector 2 timer RLY1 Start stop relay 1 timer RLY2 Start stop re...

Страница 44: ...art the setup process from the factory defaults To load factory defaults enter the DEFAULT menu under the SYSTEM menu and press enter twice in quick succession The meter will load the default settings...

Страница 45: ...art of the Advanced menu Internal Calibration is performed as follows 1 Press the Menu button to enter Programming Mode 2 Press the Right Arrow button twice and press Enter to access the Advanced menu...

Страница 46: ...the Function Key Hint Feature HINT on page 44 Digital Input Operation A digital input is standard on the meter This digital input is programmed identically to function keys F1 F2 and F3 The input is...

Страница 47: ...access the Advanced menu 3 Press the Up Arrow button and press Enter to access the System menu 4 Press the Right Arrow button and press Enter to access the Default menu 5 Press Enter twice in quick su...

Страница 48: ...Flash PV FLASH ON Alarm Message MSG ON Message Text MSG EDIT ALARM 3 Sample Count TOTAL COUNT 1 000 gallons Sample Time TOTAL TIME 10 seconds Parameter Display Default Setting Batch Count BATCH COUNT...

Страница 49: ...ease Display response is too slow Check filter and bypass values Display reading is not accurate Check 1 Signal input conditioner selected Linear square root etc 2 Scaling or calibration Display does...

Страница 50: ...ormity with the European Union Directives shown below 2014 35 EU Low Voltage Directive 2014 30 EU EMC Directive 2011 65 EU RoHS Directive This conformity is based on compliance with the application of...

Страница 51: ...n of harmonized or applicable technical stand ards and when applicable or required a European Union notified body certification Standards EN 55011 2016 EN 60079 0 2012 A11 2013 EN 60079 11 2012 EN 610...

Страница 52: ...IM6622_F SFT124 Ver 2 000 up 04 18 How to Contact Precision Digital For Technical Support please Call 800 610 5239 or 508 655 7300 Fax 508 655 8990 Email support predig com For Sales Support or to pla...

Отзывы: