Loop Leader PD6620 Series Loop-Powered Rate/Totalizer Instruction Manual

 

 

 

6

 

Specifications 

Except where noted all specifications apply to operation at +25°C. 

 

Input 

Input

 

4-20 mA 

Accuracy

 

±0.02% of span ±1 count, Square root and  

programmable exponent: 10-100% FS 

Voltage Drop 

 

Without Backlight

: 1.5 V maximum, 

With backlight

: 4.7 V maximum 

Equivalent  

Resistance

 

With backlight off

: 75 Ω @ 20 mA 

With backlight on

: 225 Ω @ 20 mA 

Input Overload

 

Over current protection to 1 A maximum

 

 

Over voltage protection to 30 VDC max  
(between mA+ and mA-/BL-) 

Temperature Drift 

25 PPM/°C from -40 to 75°C ambient 

Function 

Linear, square root, or programmable  

exponent 

Low-Flow Cutoff 

0.0 to 999,999.9 

HART  

Transparency 

Analog input will not interfere with existing 

HART communications on the wired 4-20 mA 

signal 

Display 

Display 

Dual-line LCD with backlight. Both lines 14-

segment alphanumeric. Top: 0.7" (17.8 mm), 

Bottom: 0.4" (10.2 mm). Display may be pro-

grammed to turn red and flash a user-defined 

message on alarm condition. 

Backlight 

Powered by 4-20 mA loop. Intensity varies with 

signal level 

Top Line 

5 digits (-9999 to 99999) or 5 characters (all 

capital & most lower-case letters) 

Bottom Line 

8 digits (-9,999,999 to 99,999,999; separated 

by commas) or 8 characters (all capital & most 

lower-case letters) 

Bargraph 

20 segments, numeric percent indication at top 

(PD6624 & PD6628 only) 

Decimal Point 

Up to four decimal places on top line and  

up to seven decimal places on bottom line 

Commas 

Commas to indicate 1000s (e.g. 88,987,628) 

on bottom line 

Dual-Scale  

Feature 

The input can be displayed in different scales 

on the top and bottom lines. For instance, the 

top line could display the flow in GPM and the 

bottom line could display that same input in 

CFM. 

Alarm Indication 

Red backlight, flashing display, alarm symbol 

(!); Symbols are not available on bargraph 

models. Bargraph segment flashes on alarm. 

Alarm Message 

On or Off; user programmable, 8 characters 

maximum. Displayed every 10 seconds for 1 

second on bottom line. 

Display Update 

Rate 

Ambient > -10°C: 1 Update/Second 

Ambient = -20°C: 1 Update/2 Seconds 

From -20°C to -40°C the update rate slows 

down 1 second for every -2°C (e.g. at -24°C, 1 

update/4 seconds). 

Overrange 

Top: 99999; Bottom: 99,999,999 (flashing) 

Underrange 

Top: -9999; Bottom: -9,999,999 (flashing) 

General 

Environmental

 

Operating temperature range: 

-40 to 75°C for safe area products 
-40 to 70°C for hazardous area products  

Storage temperature range:

 -40 to 85°C 

Relative humidity:

 0 to 90% non-condensing 

Printed circuit boards are conformally coated. 

Programming 

Method

 

Front panel & Free PC-based USB  

programming software 

Enclosure & 

Materials

 

Enclosure: 1/8 DIN, IP65, NEMA 4X front 

panel, high impact plastic, NORYL® polyphe-

nylene ether & polystyrene blend (PPE PS) 

resin, UL 94V-0, Color: gray 

Gasket: Silicone Rubber 

Faceplate: LEXAN® polycarbonate (PC) Film 
Buttons: Silicone rubber 

Noise Filter

 

Averages the input signal over a period of time 

between 1 and 16 seconds to dampen the ef-

fects of a noisy signal that causes a jumpy dis-

play. 

Filter Bypass 

0.0 to 99.9% of full scale. Input signal changes 

greater than bypass value are displayed imme-

diately. 

Recalibration

 

Recalibration is recommended at least every 

12 months. 

Max/Min 

Display

 

Max/min readings reached by the process are 

stored until reset by the user or until power to 

the meter is turned off.  

Password

 

There are three password types available: 

Main, Total, and Grand Total. The Main pass-

word prevents access to the meter Program-

ming Mode. Total and Grand Total passwords 

prevent resetting the total and grand total, re-

spectively. 

Non-Volatile 

Memory

 

All programmed settings and total and grand 

total values are stored in non-volatile memory 

for a minimum of ten years if power is lost. 

Normal Mode  

Rejection

 

64 dB at 50/60 Hz 

Connections

 

Removable screw terminals accept 12 to 22 

AWG wire 

DI Digital Input 

Contacts

 

2.1 VDC on contact. Connect normally open 

contacts across DI+ to DI- 

DI Digital Input 

Logic Levels

 

Logic High: 2.4 to 30 VDC (max) 
Logic Low: 0 to 0.9 VDC 

Tightening Torque

 

Screw terminal connectors:

 4.5 lb-in (0.5 Nm) 

Mounting screws:

 8.0 lb-in max. (0.9 Nm) 

Overall 

Dimensions 

4.68" x 2.45" x 3.79"  

(119 mm x 62 mm x 96 mm) (W x H x D) 

Weight 

8.7 oz (247g) with option board 

Warranty

 

3 years parts and labor 

Содержание Loop Leader PD6620 Series

Страница 1: ...to 75 C Safe Area Operating Temperature Range Free PC Based USB Programming Software 5 Digit Alphanumeric Top Line 8 Digit Alphanumeric Bottom Line 8 Digit Total Grand Total Display with 13 Digits Usi...

Страница 2: ...ult in personal injury or property loss Anyone using this product for such applications does so at his her own risk Precision Digital Corporation shall not be held liable for damages re sulting from s...

Страница 3: ...Units UNITS 26 Changing the Decimal Point Location DEC PT 26 Enabling or Disabling the Comma on the Bottom Display COMMA 26 Programming the Bargraph PD6624 PD6628 Only 26 Changing What is Displayed T...

Страница 4: ...backlight so they add very little burden to the loop Additional features that allow these instruments to be installed virtually anywhere include a NEMA 4X IP65 front panel an operating temperature ra...

Страница 5: ...ruments Loop Leader PD6626 Standard Decimal Models Hazardous Area Model Description PD6626 LNN Loop Powered Hazardous Area No Options PD6626 L2N Loop Powered Hazardous Area Two Solid State Relays PD66...

Страница 6: ...Update Second Ambient 20 C 1 Update 2 Seconds From 20 C to 40 C the update rate slows down 1 second for every 2 C e g at 24 C 1 update 4 seconds Overrange Top 99999 Bottom 99 999 999 flashing Underra...

Страница 7: ...gle or dual relay batching with optional preclose for dual stage operation Batch Preset Set via F2 function key anywhere between 0 0001 to 99 999 based on batch total deci mal point If batch total is...

Страница 8: ...ce Rate total re transmit reverse scaling allowed Scaling Range 1 00 to 23 0 mA Disable High impedance state less than 1 mA Calibration Factory calibrated 4 00 to 20 00 mA Underrange 1 0 mA 3 5 mA or...

Страница 9: ...IEC 61010 1 2010 Third Edition Safety requirements for electrical equipment for measurement control and laboratory use Additional Standards UL 50E Hazardous Area Approvals ATEX Certificate Number CML...

Страница 10: ...erate an ignition capable level of electrostatic charge Therefore the equipment shall not be installed in a location where the external conditions are conducive to the build up of electrostatic charge...

Страница 11: ...transmitter PD6626 PD6628 loop powered meter and associated apparatus barrier must be compatible PD6626 PD6628 Series Loop Powered meters do not add capacitance or inductance to the loop under normal...

Страница 12: ...ackets provided with the meter back off the two screws so that there is 6 4 mm or less through the bracket Slide the bracket toward the front of the case and remove Insert meter into the panel cutout...

Страница 13: ...ontrol Drawing LIM6600 2 in order to meet agency approval ratings Use copper wire with 60 C or 60 75 C insulation for all line voltage connections Observe all safety regulations Electrical wiring shou...

Страница 14: ...loop There are no switches or jumpers to set up for the input Setup and programming is performed through the front panel buttons or PC based software Figure 5 4 20 mA Input Connection without Backligh...

Страница 15: ...OUT The 4 20 mA output must be powered from an external power supply Figure 8 4 20 mA Output Connections Safe Area Solid State Relay Connections Relay connections are made to a four terminal connecto...

Страница 16: ...ruction Manual 16 Safe Area Open Collector Outputs Open collector output 1 and 2 connections are made to terminals labeled O1 and O1 and O2 and O2 Connect the alarm or pulse input device as shown belo...

Страница 17: ...6624 PD6628 Button Symbol Description LCD Status Menu Alarm Indicator PD6622 Only Right Arrow F1 Password Protection Indicator PD6622 Only Up Arrow F2 G Grand Total Indicator PD6622 Only Enter F3 T To...

Страница 18: ...se The meter connects to the PC via a provided micro USB cable and is powered by the USB connection so no additional power is needed during programming For detailed software instructions or to downloa...

Страница 19: ...Open collector 1 setup OUTPUT2 Open collector 2 setup DISABLE Disable the open collector PULSE Program the open collector for pulse output ALARM Program the open collector for alarm output TIMER Prog...

Страница 20: ...econds OFF Turn filter off BYPASS Set filter bypass 0 0 to 99 9 FS PASSWRD Set a password for the meter MAIN Program the main meter password TOTAL Program the total reset password Parameter Action Set...

Страница 21: ...or disable the totalizer ENABLE Enable the totalizer Default DISABLE Disable the totalizer see PD6602 manual BACKLITE Enable or disable the display back light Parameter Action Setting Description ENA...

Страница 22: ...AG Display the rate and its tag alter nating R UNITS Display the rate units T UNITS Display the total units TAG Display the tag Parameter Action Setting Description UNITS Display the units PRESET Disp...

Страница 23: ...igit and Up Arrow to increment digit value The selected digit will flash Press and hold Up Arrow to auto increment the display value If you have made a mistake or would like to enter a new value selec...

Страница 24: ...NIST standards A calibrated signal source is not needed to scale the meter Enter the Input menu to scale the meter to display the 4 20 mA input The input is capable of accepting any signal from 4 to 2...

Страница 25: ...ld the Right Arrow while no character is being edited to erase all characters to the right of the flashing character Press and hold Up or Right Arrow to auto increment or decrement a selected characte...

Страница 26: ...nt is dis played and then it moves to the leftmost position Pressing the Up Arrow moves the decimal point one place to the left The decimal point location is set independently for the rate total and g...

Страница 27: ...g alternating Total its units and the rate units alternating Grand total with units or tag alternating Grand total units and rate units alternating Rate with units or tag alternating Rate and the tota...

Страница 28: ...uts two solid state relays and one 4 20 mA output The Output menu will only show options for the available out puts See Ordering Information on page 5 for details SETUP OUTPUT OPEN COLLECTR OUT RELAY...

Страница 29: ...R turns the open collector on and off at the specified time intervals The timer can be set as single shot or continuous timer A total reset output generates a pulse whenever the total is reset regardl...

Страница 30: ...per unit of measure For example if the k factor is 0 001 and the units are gallons one pulse will be generated for every 1 000 gallons The maximum fre quency is 1 000 Hz Setting output 2 to quadrature...

Страница 31: ...point is the display value at which the alarm will turn on and the reset point is the display value at which the alarm will turn off If the set point is lower than the reset point the alarm will be a...

Страница 32: ...o 99 hrs 59 min and 59 seconds The stopwatch function may be assigned to any open collector There are three settings needed to use the function effectively 1 Assign stopwatch to either top or bottom d...

Страница 33: ...le shot or continuous timer For use in batch control applications the meter relays may be set to batch This will enable the batch control features of the meter The stopwatch output STPWATCH allows the...

Страница 34: ...The set point is the display value at which the alarm will turn on and the reset point is the display value at which the alarm will turn off If the set point is lower than the reset point the alarm w...

Страница 35: ...rogram the Off Delay OFF DLAY from 1 second to 99 hours 59 minutes and 59 seconds This is the time it takes from selecting START to turning on the output and for how long the output is off in continuo...

Страница 36: ...on MANUAL or AUTO If setting batching to automatic a delay before the next batch is started must be programmed The PRESET amount is the value at which the batch will stop and can be programmed up to t...

Страница 37: ...topwatch function is used to open and close a solenoid valve to know the exact amount of time needed to complete the desired sample Once this is determined the timer function can be used to automatica...

Страница 38: ...responding mA output signals Rate or Total RATE or TOTAL To scale the analog output enter display value 1 and a corresponding analog output value for this display then enter display value 2 and a corr...

Страница 39: ...AL The Advanced Rate menu contains options to apply signal input conditioning functions to the input and scale calibrate the input signal The Advanced Total and Advanced Grand Total menus contain opti...

Страница 40: ...display for non linear signals to convert level to flow using weirs and flumes with complex expo nent Advanced Total and Grand Total Programming ADV TOTAL ADV GTOTAL The advanced total and grand tota...

Страница 41: ...rce is strongly recommended 1 After accessing the SCALE CAL menu press the Right Arrow button to scroll to the Calibration menu CAL RATE and press Enter 2 Select the appropriate units for the desired...

Страница 42: ...ere are three password types available Main Total and Grand Total The Main password prevents access to the meter Programming Mode Total and Grand Total passwords prevent resetting of and changes to th...

Страница 43: ...tart all timers STOP ALL Stop all timers S STP ALL Start or stop all timers OC1 Start stop open collector 1 timer OC2 Start stop open collector 2 timer RLY1 Start stop relay 1 timer RLY2 Start stop re...

Страница 44: ...art the setup process from the factory defaults To load factory defaults enter the DEFAULT menu under the SYSTEM menu and press enter twice in quick succession The meter will load the default settings...

Страница 45: ...art of the Advanced menu Internal Calibration is performed as follows 1 Press the Menu button to enter Programming Mode 2 Press the Right Arrow button twice and press Enter to access the Advanced menu...

Страница 46: ...the Function Key Hint Feature HINT on page 44 Digital Input Operation A digital input is standard on the meter This digital input is programmed identically to function keys F1 F2 and F3 The input is...

Страница 47: ...access the Advanced menu 3 Press the Up Arrow button and press Enter to access the System menu 4 Press the Right Arrow button and press Enter to access the Default menu 5 Press Enter twice in quick su...

Страница 48: ...Flash PV FLASH ON Alarm Message MSG ON Message Text MSG EDIT ALARM 3 Sample Count TOTAL COUNT 1 000 gallons Sample Time TOTAL TIME 10 seconds Parameter Display Default Setting Batch Count BATCH COUNT...

Страница 49: ...ease Display response is too slow Check filter and bypass values Display reading is not accurate Check 1 Signal input conditioner selected Linear square root etc 2 Scaling or calibration Display does...

Страница 50: ...ormity with the European Union Directives shown below 2014 35 EU Low Voltage Directive 2014 30 EU EMC Directive 2011 65 EU RoHS Directive This conformity is based on compliance with the application of...

Страница 51: ...n of harmonized or applicable technical stand ards and when applicable or required a European Union notified body certification Standards EN 55011 2016 EN 60079 0 2012 A11 2013 EN 60079 11 2012 EN 610...

Страница 52: ...IM6622_F SFT124 Ver 2 000 up 04 18 How to Contact Precision Digital For Technical Support please Call 800 610 5239 or 508 655 7300 Fax 508 655 8990 Email support predig com For Sales Support or to pla...

Отзывы: