Model PD6262 Analog Dual-Input Rate/Totalizer Instruction Manual
9
NOISE FILTER
Programmable from 2 to 199 (0 will disable filter)
FILTER BYPASS
Programmable from 0.1 to 99.9% of calibrated span
RECALIBRATION
All ranges are calibrated at the factory. Recalibration is
recommended at least every 12 months.
NON-VOLATILE
MEMORY
All programmed settings are stored in non-volatile memory
for a minimum of ten years if power is lost.
POWER
OPTIONS
85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max
or jumper selectable 12/24 VDC
10%, 15 W max
FUSE
Required external fuse: UL Recognized, 5 A max, slow
blow; up to 6 meters may share one 5 A fuse
ISOLATED
TRANSMITTER
POWER SUPPLY
Terminals P+ & P-: 24 VDC
10%.
Selectable for 24, 10, or 5 VDC supply (internal jumper J4).
ProVu Series (PD6262):
85-265 VAC models rated @ 200 mA max, 12/24 VDC powered
models rated @ 100 mA max, @ 50 mA max for 5 or 10 VDC
supply.
ProtEX-MAX (PD8 Series):
All models transmitter supply rated @ 25 mA max.
NORMAL MODE
REJECTION
Greater than 60 dB at 50/60 Hz
ISOLATION
4 kV input/output-to-power line
500 V input-to-output or output-to-P+ supply
OVERVOLTAGE
CATEGORY
Installation Overvoltage Category II:
Local level with smaller transient overvoltages than
Installation Overvoltage Category III.
ENVIRONMENTAL
ProVu Series (PD6262):
Operating temperature range: -40 to 65°C
Storage temperature range: -40 to 85°C
Relative humidity: 0 to 90% non-condensing
ProtEX-MAX (PD8 Series):
T6 Class operating temperature range Ta = -40 to 60°C
T5 Class operating temperature range Ta = -40 to 65°C
See LIM8 ProtEX-MAX instruction manual for details.
MAX POWER
DISSIPATION
ProtEX-MAX (PD8 Series): Maximum power dissipation
limited to 15.1 W. See LIM8 ProtEX-MAX instruction
manual for additional details.
CONNECTIONS
Removable screw terminal blocks accept 12 to 22 AWG
wire, RJ45 for external relays, digital I/O, and serial
communication adapters.