Model PD6262 Analog Dual-Input Rate/Totalizer Instruction Manual
20
Transmitter Supply Voltage Selection (P+, P-)
All meters, including models equipped with the 12/24 VDC power
option, are shipped from the factory configured to provide 24 VDC
power for the transmitter or sensor.
If the transmitter requires 5 or 10 VDC excitation, the internal
jumper J4 must be configured accordingly.
To access the voltage selection jumper:
1. Remove all the wiring connectors.
2. Unscrew the back cover.
3. Slide out the back cover by about 1 inch.
4. Configure the J4 jumper, located behind the input signal
connector, for the desired excitation voltage as shown.
Figure 6. Transmitter Supply Voltage Selection
Connections
All connections are made to removable screw terminal connectors
located at the rear of the meter.
!
Caution!
Use copper wire with 60°C or 60/75°C insulation for all line
voltage connections. Observe all safety regulations.
Electrical wiring should be performed in accordance with
all applicable national, state, and local codes to prevent
damage to the meter and ensure personnel safety.