™ PD6310-WM NTEP Certified Pulse Input Batch Controller
Instruction Manual
53
Factory Defaults & User Settings
The following table shows the factory setting for the
major programmable parameters on the controller.
Factory Defaults & User Settings
Parameter
Display
Default Setting
Input type
Input
Pulse
Total
yes
Total enabled
Units
units
Rate / total / G total
Pulse / Pulse / Pulse
Rate decimal
point
ddd.ddd
1 Place
Total decimal
point
ddddd.d
1 Place
Grand Total
decimal point
dddddd
0 Places
K-Factor
Factor
1.000
Function
Functn
Linear
Number of points
No Pts
2
Programming
prog
Scale
Input 1
InP 1
00000.0
Display 1
Dis 1
00000.0
Input 2
InP 2
10000.0
Display 2
Dis 2
10000.0
Display line 1
Line 1
Display batch total
Display line 2
Line 2
Display preset
Display intensity
d-Inty
6
Total time base
T tb
Second
Total conversion
factor
T CF
1.000
Batch mode
nmode
Manual
Grand total time
base
GT tb
Second
Grand total
conversion factor
T CF
1.000
Grand total reset
T rst
Manual
Relay 1
assignment
Asign1
Total
Relay 2
assignment
Asign2
Total
Relay 2 pre-
close
preCls
No
Relay 3
assignment
Asign3
Rate
Relay 4
assignment
Asign4
Rate
Relay 1 action
Act 1
Automatic
Batch preset
Preset
100.0
Relay 2 action
Act 2
Automatic
Relay 2 set point
Set 2
200.0
Relay 3 action
Act 3
Automatic
Relay 3 set point
Set 3
3.000
Relay 3 reset
point
RSt 3
2.500
Factory Defaults & User Settings
Parameter
Display
Default Setting
Relay 4 action
Act 4
Automatic
Relay 4 set point
Set 4
4.000
Relay 4 reset
point
RSt 4
3.500
Fail-safe relay 1
Fls 1
Off
Fail-safe relay 2
Fls 2
Off
Fail-safe relay 3
Fls 3
Off
Fail-safe relay 4
Fls 4
Off
On delay relay 1
On 1
0.0 sec
Off delay relay 1
Off 1
0.0 sec
On delay relay 2
On 2
0.0 sec
Off delay relay 2
Off 2
0.0 sec
On delay relay 3
On 3
0.0 sec
Off delay relay 3
Off 3
0.0 sec
On delay relay 4
On 4
0.0 sec
Off delay relay 4
Off 4
0.0 sec
Display 1 analog
out
Dis 1
0
Output 1 value
Out 1
4.000 mA
Display 2 analog
out
Dis 2
1000.0
Output 2 value
Out 2
20.000 mA
Source analog
output
Source
Rate/process
Overrange
output
O-rang
21.000 mA
Underrange
output
u-rang
3.000 mA
Loop break
output
break
1.000 mA
Filter
filter
Hi Speed
Cutoff value
CutofF
0.000 (disabled)
Maximum output
nmAx
23.000 mA
Minimum output
nmin
1.000 mA
Slave ID
(Address)
SlaVId
247
Baud rate
baud
9600
Transmit delay
Tr dly
50 ms
Parity
Parity
Even
Byte-to-byte
timeout
t-byt
010 (0.1 sec)
F1 function key
F1
Start
F2 function key
F2
Preset
F3 function key
F3
Stop
F4 function
F4
Start/Stop
Digital input 1
dI 1
Menu
Digital input 2
dI 2
Right arrow
Digital input 3
dI 3
Up arrow
Digital input 4
dI 4
Enter
Digital output 1-4
dO 1
Alarm 1-4