™ PD6310-WM NTEP Certified Pulse Input Batch Controller
Instruction Manual
31
Setting the Display Parameter &
Intensity (
dsplay
)
Display line 1 (
line 1
) can be programmed to
display:
1. Display total
2. Display grand total
3. Toggle rate and total
4. Toggle rate and grand total
5. Display batch count
6. Relay set points
7. Toggle preset and rate
8. Toggle rate and units
9. Toggle total and units
10. Toggle grand total and units
11. Display max and min values
12. Display Modbus input
13. Display rate value
Display line 2 (
line 2
) can be programmed to
display:
1. Toggle rate and units
2. Toggle total and units
3. Toggle grand total and units
4. Display max and min values
5. Display Modbus input
6. Off (no display)
7. Display rate units
8. Display rate
9. Display total
10. Display grand total
11. Toggle rate and total
12. Toggle rate and grand total
13. Display batch count
14. Relay set points
15. Toggle preset and rate
After setting up the input and the display, press the
Menu button to exit programming and skip the rest of
the setup menu. Press the Menu button again and the
Up arrow to reach the
Program
menu and complete
the scaling or calibration of the controller.
Display Menu
Display Intensity (
d-Inty
)
The controller has eight display intensity levels to give
the best performance under various lighting
conditions. Select intensity 8 for outdoor applications.
The default intensity setting is 6.
For direct sunlight readability, Sunbright display
models are highly recommended. See
Display Configurations
The upper and lower displays may be assigned to
rate, total, grand total, batch count, preset, set points,
units (lower display only), alternating R & T, R & GT,
preset & rate, max & min, or a Modbus display
register. Any rate/total/grand total display may be
programmed to alternate with a custom unit or tag.
The default display configuration consists of an upper
display of batch total and a lower display of the batch
preset.
The display can also be set up, so batch total is on
the upper display and rate is on the lower display.