9202 - Product Version 9202-002
31
c FM us ....................................................... FM 3600, 3611, 3810
CSA E60079-0, -15
CSA 22.2 -25, -142, -213
ANSI/ISA-12.00.01 / 12.12.02
UL, Standard for Safety .............................. UL 61010-1
SIL ............................................................... IEC 61508
Configuration of cable fault check
Diagnostics
Cable fault detection
Cable fault detection (CA.BR, CA.SH):
Input
Event
Readout
Limit
All
Cable break
CA.BR
< 0.1 mA
All
Short-circuited cable
CA.SH
> 6.5 mA
Cable fault check, independent detection and visualisation for each channel:
Module:
Configuration, common for both channels
Cable fault detection:
9202
CA.BR = Yes or CA.SH = Yes
ON
Else:
OFF