9202QI01
LERBAKKEN 10, 8410 RØNDE DENMARK
Revision date:
2009-05-03
Version Revision
V3 R6
Prepared by:
PB
Page:
2/2
Terminal (31,32)
Supply:
Voltage
19.2 – 31.2 VDC
Power max.
3 W
Terminal (33,34)
Status Relay:
Non Hazardous location
Zone 2 installation
Voltage max.
125 VAC / 110 VDC
32 VAC / 32 VDC
Power max.
62.5 VA / 32 W
16 VA / 32 W
Current max.
0.5 AAC / 0.3 ADC
0.5 AAC / 1 ADC
Terminal CH1(11,12) CH2(13,14)
Digital output:
NPN output:
Voltage max.
30 VDC
Current max.
80 mA
Terminal CH1(11,12) CH2(13,14)
Relay output:
Non Hazardous location
Zone 2 installation
Voltage max.
250 VAC / 30 VDC
32 V AC / 30 VDC
Power max.
500 VA / 60 W
64 VA / 60 W
Current max.
2 AAC / 2 ADC
2 AAC / 2 ADC
Installation notes:
For installation in Zone 2, the module must be installed in an outer enclosure having an IP protection of
at least IP54 according to type of protection Ex-n or Ex-e.
For installation on Power Rail in Zone 2, only Power Rail type 9400 supplied by Power Control Unit type
9410 is allowed.
In type of protection “intrinsic safety iD” the parameters for intrinsic safety for gas group IIB are
applicable.
If the sensor circuits (Terminals 41…44, 51...54) have been installed in a type of protection other than
“intrinsic safety”, the module shall not be re-installed in type of protection ”intrinsic safety”.
Do not separate connectors when energized and an explosive gas mixture is present.
Do not mount or remove modules from the Power Rail when an explosive gas mixture is present.