9107QU01
LERBAKKEN 10, 8410 RØNDE DENMARK
Revision date:
2019-11-26
Version Revision
V1 R0
Prepared by:
PB
Page:
1/5
UL Installation drawing
For safe installation of the Process Control Equipment (Associated Apparatus) 9107 the following
must be observed. The module shall only be Installed by qualified personnel who are familiar with
the national and international laws, directives and standards that apply to this area.
For Installation in Div2 / Zone2 the following must be observed.
The 4501 programming module is to be used solely with PR electronics modules. It is important that
the module is undamaged and has not been altered or modified in any way. Only 4501 modules free
of dust and moisture shall be installed.
9107AA-U9:
1 channel HART
-transparent driver
9107BA-U9:
1 channel HART
-transparent driver
9107AB-U9:
2 channel HART
-transparent driver
9107BB-U9:
2 channel HART
-transparent driver
Marking:
Proc. Cont. Eq. for Use in Haz. Loc.
Install in CL I DIV2 GP A-D T4 provide
IS circuits to CL I-III DIV 1 GP A-G
or CL I Zn2 Gp IIC T4 provides IS
E233311 circuits for CL I Zn0 Gp IIC/Zn20 Gp IIIC
Um=253V [Exia] Installation Drawing: 9107QU01
Proc. Cont. Eq. for Use in Haz. Loc.
Install in CL I DIV2 GP A-D T4
or CL I Zn2 Gp IIC T4
E233311 Installation Drawing: 9107QU01
Standards:
UL 121201 NONINCENDIVE ELECTRICAL EQUIPMENT FOR USE IN CLASS I AND II,
DIVISION 2 AND CLASS III, DIVISIONS 1 AND 2 HAZARDOUS (CLASSIFIED) LOCATIONS
Edition 9 - Revision Date 2018/08/31
CSA C22.2 NO. 213 NONINCENDIVE ELECTRICAL EQUIPMENT FOR USE IN CLASS I
AND II, DIVISION 2 AND CLASS III, DIVISIONS 1 AND 2 HAZARDOUS (CLASSIFIED)
LOCATIONS- Edition 3 - Issue Date 2017/09/01
UL 913 STANDARD FOR INTRINSICALLY SAFE APPARATUS AND ASSOCIATED
APPARATUS FOR USE IN CLASS I, II, III, DIVISION 1, HAZARDOUS (CLASSIFIED)
LOCATIONS- Edition 8 - Revision Date 2015/10/16
CSA C22.2 NO. 60079-0 EXPLOSIVE ATMOSPHERES — PART 0: EQUIPMENT —
GENERAL REQUIREMENTS- Edition 3 - Issue Date 2015/10/01
CSA C22.2 NO. 60079-11:14 EXPLOSIVE ATMOSPHERES — PART 11: EQUIPMENT
PROTECTION BY INTRINSIC SAFETY “I”- Edition 2 - Issue Date 2014/02/01
The 9107Axx equipment is intended for
installation in non-hazardous locations or
Class I,Division 2, Groups A – D or Zone 2
Croup IIC hazardous locations.
The 9107Bxx is galvanically isolating
associated apparatus intended for installation
in non-hazardous locations or Class I, Division
2, Groups A – D hazardous locations with
intrinsically safe connections to Class I, II and
III hazardous locations.
UL Installation Drawing
9107 - Product version 9107-002
27