9107QF01
LERBAKKEN 10, 8410 RØNDE DENMARK
Revision date:
2019-04-04
Version Revision
V3 R0
Prepared by:
PB
Page:
2/2
Warning
: To prevent ignition of the explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
Warning:
Do not install or remove modules from the Power Rail when an explosive gas mixture is present.
CH1 (terminal 41,42)
CH2 (terminal 51,52)
U
o
,Voc:
28 V
I
o
, Isc:
93 mA
P
o
:
0.65 W
IIC or A,B
IIB or C,E,F IIA or D,G
C
o.
0.08
F
0.650
F
2.15
F
L
o.
4 mH
16 mH
32 mH
-20 ≤Ta ≤ +60ºC
Simple Apparatus or
Intrinsic safe apparatus
with entity parameters:
Vmax (Ui) ≥ Vt (Uo)
Imax (Ii) ≥ It (Io)
Pi ≥ Pt (Po)
Ca ≥ C
cable
+ Ci
La ≥ L
cable
+ Li
44
43
42
41
54
53
52
51
34
33
32
31
14
13
12
11
9107
CH1
CH2
_
+
+
_
mA
mA
91 92 93 94 95
Power Rail
4501
(terminal 11,12,13,14)
(terminal 31,32,33,34)
(terminal 91,92,93,94,95)
Um: 253 V, max 400 Hz
Hazardous Classified Location Unclassified Location or
Class I/II/III, Division 1, Group A,B,C,D,E,F,G
Hazardous Classified Location
or Class I, Zone 0/1 Group IIC, [AEx ia] IIC Class I, Division 2, Group A,B,C,D T4
or Group IIC, [Ex ia Ga] IIC Gc
or Class I Zone 2 Group IIC T4 Gc
26