INPUT CONFIGURATION PARAMETERS
The indicator needs to be appropriately configured for sensor Input type PV indication, digital filter etc. The
PAGE-12
parameters are listed below in Table 6.1.
Table 6.1
Settings
(Default Value)
Parameter Description
DIGITAL FILTER
Sets the time constant, in Seconds, for the low-pass digital filter
applied to the measured PV. The filter helps smoothing /
averaging the signal input and removing the undesired noise. The
higher the filter value the lower the indication response to the PV
changes and vice-a-versa.
0.5 to 60.0 Seconds
(in steps of 0.5 Seconds)
(Default : 2.0 sec.)
(Default :
)
EU
Refer Table 6.2
Refer Table 6.3
(Default : 0.1)
Select Input type in accordance with the type of Thermocouple or
RTD, sensor or Transducer output connected for process value
measurement. Ensure proper hardware jumper settings.
INPUT TYPE
Set the Process Value indication resolution (decimal point). All the
resolution based parameters (hysteresis, alarm setpoints etc.)
then follow this resolution setting.
RESOLUTION
Select Temperature units in °C or °F for Thermocouple or Pt100
sensor.
For DC Linear inputs (mA/mV/V), select appropriate Units from
the list in Table 6.2. Note however that the selected Units are for
the purpose of Lower Readout indication only.
UNITS
Refer Table 6.3
(Default : Type K)
DC RANGE HIGH
(Available for DC Linear Inputs)
Sets process value corresponding to maximum DC Linear signal
input.
(e.g., 5 V, 10 V, 20 mA, etc.)
OFFSET
This value is algebraically added to the measured PV to derive the
final PV that is displayed and used for Alarm / Retransmission.
Final PV = Measured PV + Offset
-19999 to 30000
(Default : 100.0)
DC RANGE LOW
(Available for DC Linear Inputs)
Sets process value corresponding to minimum DC Linear signal
input.
(e.g., 0 V, 0 mA, 4 mA, etc.)
-19999 to 30000
(Default : 0.0)
For DC Lin. Volts/Current
-19999 to 30000 Counts
For Thermocouple/RTD
-1999 to 3000 or
-1999.9 to 3000.0
(Default : 0)
User Manual
neuro 100EX
Section 6