RECOMMENDATION         

S-DOME 2.0 SYSTEM

LIGHTNING PROTECTION RECOMMENDATIONS

GB

Mounting systems for solar technology

Summary of Contents for S-DOME 2.0

Page 1: ...RECOMMENDATION S DOME 2 0 SYSTEM LIGHTNINGPROTECTIONRECOMMENDATIONS GB Mounting systems for solar technology ...

Page 2: ...facturer Dehn Söhne and are to be installed together with the S Dome 2 0 system as follows RECOMMENDATIONS FOR LIGHTENING PROTECTION CONNECTION ELEMENTS FOR THE S DOME 2 0 SYSTEM M K2 Slot nut with clip Material stainless steel PA K2 Allen bolt with serrated under head M8x30 DIN EN ISO 4762 Material stainless steel A2 WS 6 mm 1001643 2001730 Lightning Rod Material aluminium 101000 Round Wire Mater...

Page 3: ...mesh structure on the roof No additional components in the module row direction are necessary as the lightning current carrying capability and connection is via the windbreaker Tightening torque 16 Nm Required items K2 slot nut underlay plate earthing clamp round wire Allen bolt with serrated under head M8x30 1 of3 INSTALLING THE LIGHTNING ROD Position quantity and length of the lightning rods can...

Page 4: ...ot nut underlay plate earthing clamp round wire Allen bolt with serrated under head M8x30 3 of3 K2 Systems GmbH expressly points out that the use of the listed components is only a recommendation Alterna tively lightning protection components from other manufacturers may also be used Please follow all instructions given by the module and inverter manufacturers Effective operation of existing light...

Page 5: ...mendation S Dome 2 0 GB1 0816 Subject to change Product illustrations are exemplary and my differ from the original Mounting systems for solar technology SERVICE HOTLINE 49 0 7159 42059 0 Info k2 systems de ...