background image

Chapter 5 Function parameter 

60

 

 

Ch
ap

ter 5

 

fault 

482  y1.14 

Current of the second 
fault 

● 

483  y1.15 

Bus voltage of the 
second fault 

● 

484  y1.16 

Input terminal status of 
the second fault 

● 

485  y1.17 

Output terminal status of 
the second fault 

● 

486  y1.18  Reserved 

 

 

487  y1.19 

Power-on time of the 
second fault 

 

● 

488  y1.20 

Running time of the 
second fault 

● 

489  y1.21  Reserve 

 

 

490  y1.22  Reserve 

 

 

 

491  y1.23 

Frequency of the first 
fault 

 

● 

492  y1.24  Current of the first fault 

● 

493  y1.25 

Bus voltage of the first 
fault 

● 

494  y1.26 

Input terminal status of 
the first fault 

● 

495  y1.27 

Output terminal status of 
the first fault 

● 

496  y1.28  Reserved 

 

 

497  y1.29 

Power-on time of the 
first fault 

 

● 

498  y1.30 

Running time of the first 
fault 

● 

Содержание PI500 004G1

Страница 1: ...requency converter please carefully read this manual before installing it For any problem when using this product please contact your local dealer authorized by this company or directly contact this c...

Страница 2: ...ying function code 14 3 5 2 The way to read parameters in various status 15 3 5 3 Password settings 15 3 5 4 Motor parameter auto turning 15 Chapter 4 Installation and commissioning 16 4 1 Installatio...

Страница 3: ...wing 76 Chapter 8 Maintenance and repair 78 8 1 Inspection and maintenance 78 8 2 Parts for regular replacement 78 8 3 Storage 79 8 4 Capacitor 79 8 4 1 Capacitor rebuilt 79 8 5 Measuring and readings...

Страница 4: ...running 101 V 6 External potentiometer speed 102 V 7 Keyboard potentiometer speed 103 V 8 Rise Fall Control Speed 103 V 9 External analog speed control external 0 10V voltage signal given 104 V 10 Ext...

Страница 5: ...verter to ensure that the product you have received is right the one you ordered 1 1 1 Instructions on nameplate Input Source Spec Output Power Spec Production Sequence Number POWTRAN Inverter model P...

Страница 6: ...sunlight When two or more converters are installed in a cabinet please pay attention to the installation location ensure the good heat dissipation effect Before energizing Note Must comply with this...

Страница 7: ...ofessional personnel is not allowed to detect signal when operating Doing so may cause personal injury or damage to this unit When the inverter is operating you should avoid that objects fall into thi...

Страница 8: ...inverter should be turned on off without output status otherwise which easily lead to damage to the inverter module 8 Use other than the ratedvoltage PI series inverter is not suitable for use beyond...

Страница 9: ...ged fully otherwise there is a danger of electric shock 3 Body static electricity will seriously damage the internal MOS field effect transistors etc if there are not anti static measures do not touch...

Страница 10: ...18 5 PI500 022G2 22 0 97 7 90 22 0 PI500 030G2 30 0 122 1 110 30 0 PI500 037G2 37 0 157 4 152 37 0 PI500 045G2 45 0 185 3 176 45 0 PI500 055G2 55 0 214 210 55 0 PI500 075G2 75 307 304 75 PI500 093G2 9...

Страница 11: ...F3R 560 630 1010 1160 950 1100 560 630 PI500 630G3R PI500 700F3R 630 700 1160 1310 1100 1250 630 700 AC 3PH 480V 10 PI500 0R7G4 0 75 4 1 2 5 0 75 PI500 1R5G4 1 5 4 9 3 7 1 5 PI500 2R2G4 2 2 5 7 5 0 2...

Страница 12: ...00G6 PI500 220F6 200 220 235 247 215 245 200 220 PI500 220G6 PI500 250F6 220 250 247 265 245 260 220 250 PI500 250G6 PI500 280F6 250 280 265 305 260 299 250 280 PI500 280G6 PI500 315F6 280 315 305 350...

Страница 13: ...control W O PG Torque boost Automatic torque boost manual torque boost 0 1 to 30 0 DC braking DC braking frequency 0 0Hz to max frequency braking time 0 0 to 100 0 seconds braking current value 0 0 t...

Страница 14: ...trol terminals and serial communication port They can be switched through a variety of ways Frequency source Total 10 frequency sources digital analog voltage analog current multi speed and serial por...

Страница 15: ...in Chinese English text Copy parameter Can upload and download function code information of frequency converter rapid replication parameters Key lock and function selection Lock part or all of keys d...

Страница 16: ...l operation and remote operation communication control ON terminal control working status OFF keyboard control working status Flashing remote control working status FWD REV Forward reverse running lig...

Страница 17: ...ard control status Stop Reset Key For stopping running in the running status for resetting the operation in fault alarm status The function of the key is subject to F6 00 Enter key Enter into levels o...

Страница 18: ...the two keys ENTER will be back to the level 2 menu and save parameter setting before back and transfer to the next function code automatically PRG will be back to the level 2 menu directly not save p...

Страница 19: ...l display One must input the correct password to go to regular menu otherwise inaccessible To cancel the password protection function firstly enter correct password to access and then set y0 01 to 0 3...

Страница 20: ...ment 0 75 11kW A 100mm B 10mm 15 22kW A 200mm B 10mm 30 75kW A 200mm B 50mm 93 400kW A 300mm B 50mm Figure 4 1 PI500 Series Each power level installation space requirement PI500 Series frequency inver...

Страница 21: ...wind Figure 4 2 Heat insulation deflector up and down installation diagram 4 2 Wiring Diagram Frequency inverter wiring is divided by main circuit and control circuit Users must properly connect freq...

Страница 22: ...Chapter 4 Installation and commissioning 18 Chapter 4 4 2 1 Wiring diagram Main circuit Control circuit Figure 4 3 Wiring diagram...

Страница 23: ...e 4 4 0 75 4kW G3 main circuit terminal 2 5 5 11kW G3 main circuit terminal R S T RB U V W P Figure 4 5 5 5 11kW G3 main circuit terminal 3 15kW G3 main circuit terminal Figure 4 6 11 15kW G3 main cir...

Страница 24: ...g 20 Chapter 4 6 45 75kW G3 main circuit terminal Figure 4 9 45 75kW G3 main circuit terminal 7 93 110kW G3 main circuit terminal Figure 4 10 93 110kW G3 8 132kW main circuit terminal 132G3 160F3 Figu...

Страница 25: ...terminal 10 250 400kW G3 main circuit terminal Figure 4 13 250 400kW G3 main circuit terminal 11 450 630kW G3 main circuit terminal Figure 4 14 450 630kW G3 main circuit terminal Note P standard is c...

Страница 26: ...nit P DC reactor terminals Connect to DC reactor remove the shorting block 4 4 Control circuit terminals 4 4 1 Control circuit terminals arrangement 1 Control panel control circuit terminals Figure 4...

Страница 27: ...digital input 2 DI3 Multi function digital input 3 DI4 Multi function digital input 4 DI5 Multi function digital input 5 DI6 Multi function digital input 6 DI7 Multi function digital input 7 DI8 Multi...

Страница 28: ...tput signal transmission generally use the shielded cable and wiring short distance as far as possible good grounding and shielding layer on the inverter side try not to over 20 m transmission distanc...

Страница 29: ...e using an external power supply PLC and 24 v jumper cap must be removed otherwise it will damage the product 4 5 Wiring Precautions Danger Make sure that the power switch is in the OFF state before w...

Страница 30: ...und by using 1000 volt megger so as to ensure the measured value is no less than 4 megohms When the inverter need to be started frequently do not directly turn power off only the control terminal or k...

Страница 31: ...ing Commission ing Select control manner setting F0 00 Set b0 00 b0 05 b0 28 etc Set b0 00 b0 05 Select appropriate ac deceleration time Set F0 13 F0 14 Select appropriate ac deceleration time Set F0...

Страница 32: ...etc F0 Basic function group Frequency setting control mode acceleration and deceleration time F1 Input terminals group Analog and digital input functions F2 Output terminals group Analog and digital...

Страница 33: ...peed Motor actual running speed 16 d0 15 PID setting Reference value percentage when PID runs 17 d0 16 PID feedback Feedback value percentage when PID runs 18 d0 17 PLC stage Stage display when PLC ru...

Страница 34: ...age before correction Input voltage value before AI2 linear correction 0 01V 40 d0 39 AI3 voltage before correction Input voltage value before AI3 linear correction 0 01V 41 d0 40 Reserve 42 d0 41 mot...

Страница 35: ...requency command UP DOWN reference when running 0 Running frequency 1 Set frequency 0 54 F0 11 Command source selection 0 Keyboard control LED off 1 Terminal block control LED on 2 Communications comm...

Страница 36: ...ncy F0 23 lower limit frequency to F0 19 maximum frequency 50 00Hz 65 F0 22 Upper limit frequency offset 0 00Hz to F0 19 maximum frequency 0 00Hz 66 F0 23 Lower limit frequency 0 00Hz to F0 21 upper l...

Страница 37: ...controlled by the inverter This way is same as the principle of free stop described in F3 07 9 Fault reset RESET The function make use of terminal for fault reset It has same function with RESET key...

Страница 38: ...h count input Input terminal of the length count 28 Length reset Clear length 29 Torque control prohibited When the inverter torque control is prohibited the inverter will enter speed control mode 30...

Страница 39: ...est speed and the current maintains at the set upper limit during the parking process This function is used to meet the requirements that the inverter needs to stop as soon as possible when the system...

Страница 40: ...orresponding setting 100 0 to 100 0 0 0 99 F1 28 HDI Maximum input F1 26 to 100 00kHz 50 00kHz 100 F1 29 F1 28 corresponding setting 100 0 to 100 0 100 0 101 F1 30 DI filter time 0 000s to 1 000s 0 01...

Страница 41: ...to 40 0 120 F2 02 Relay 1 output function selection TA1 TB1 TC1 2 121 F2 03 Undefined 122 F2 04 SPA output function selection collector open circuit output terminals 1 123 F2 05 Relay 2 output functio...

Страница 42: ...limiting Drive under the speed control mode when the output torque reaches the torque limit the inverter is stall protection status while the output ON signal 15 Ready to run When the inverter main c...

Страница 43: ...aches the lower limit frequency output ON signal In shutdown state of the signal is also ON 38 Alarm output When the inverter failure and the failure of the process to continue to run mode the inverte...

Страница 44: ...DO output delay time 0 0s to 3600 0s 0 0s 131 F2 13 SPA output delay time 0 0s to 3600 0s 0 0s 132 F2 14 Relay 2 output delay time 0 0s to 3600 0s 0 0s 133 F2 15 DO output terminal active status sele...

Страница 45: ...tart section 0 0 to 100 0 to F3 15 30 0 153 F3 15 Proportion of S curve end section 0 0 to 100 0 to F3 14 30 0 5 1 6 F4 Group V F control parameters No Code Parameter name Setting range Factory settin...

Страница 46: ...peed loop integral T2 0 01s to 10 00s 1 00s 174 F5 05 switching frequency 2 F5 02 to F0 19 max frequency 10 00Hz 175 F5 06 Speed loop integral 0 invalid 1 valid 0 176 F5 07 Torque limit upper limit so...

Страница 47: ...0 Product series number Frequency inverter series number 196 F6 11 Software version number Control board software version 197 F6 13 Communication read write data selection Bit CRC error response selec...

Страница 48: ...F7 03 Jog priority 0 Invalid 1 Valid 1 208 F7 04 Jump frequency 1 0 00Hz to F0 19 maximum frequency 0 00Hz 209 F7 05 Jump frequency 2 0 00Hz to F0 19 maximum frequency 0 00Hz 210 F7 06 Jump frequency...

Страница 49: ...uency 0 0 230 F7 26 Frequency detection value FDT2 0 00Hz to F0 19 maximum frequency 50 00Hz 231 F7 27 Frequency detection hysteresis value FDT2 0 0 to 100 0 FDT2 level 5 0 232 F7 28 Random arrivals f...

Страница 50: ...frequency dormancy frequency F7 48 to maximum frequency F0 19 0 00Hz 251 F7 47 Awakens delay time 0 0s to 6500 0s 0 0s 252 F7 48 Dormancy frequency 0 00Hz to awakens requency F7 46 0 00Hz 253 F7 49 Do...

Страница 51: ...1 Enable 1 267 F8 09 Short to ground protection 0 Invalid 1 Valid 1 268 F8 10 Number of automatic fault reset 0 to 32767 0 269 F8 11 Fault DO action selection during automatic fault reset 0 OFF 1 ON...

Страница 52: ...units digit Hundreds digit Power on time arrival Err 29 same as F8 17 units digit Thousands digit Reserved Ten thousands digit PID feedback loss when running Err 31 same as F8 17 units digit 00000 278...

Страница 53: ...parity 8 N 1 0 292 F9 02 This unit address 1 250 0 for broadcast address 1 293 F9 03 Response delay 0ms 20ms 2ms 294 F9 04 Communication timeout time 0 0 Invalid 0 1 60 0s 0 0 295 F9 05 Dataprotocolse...

Страница 54: ...Invalid 1 enable 1 307 FB 01 Under voltage point setting 50 0 to 140 0 100 0 308 FB 02 Over voltage point setting 200 0V to 2500 0V 810V 309 FB 03 Deadband compensation mode selection 0 no compensati...

Страница 55: ...ange Factory setting Chan ge 331 E1 00 0 stage speed setting 0X 100 0 to 100 0 0 0 332 E1 01 1 stage speed setting 1X 100 0 to 100 0 0 0 333 E1 02 2 stage speed setting 2X 100 0 to 100 0 0 0 334 E1 03...

Страница 56: ...o 6500 0s h 0 0s h 358 E1 27 4 stage ac deceleration time selection 0 to 3 0 359 E1 28 5 stage running time T5 0 0s h to 6500 0s h 0 0s h 360 E1 29 5 stage ac deceleration time selection 0 to 3 0 361...

Страница 57: ...board set frequency F0 01 setting UP DOWN can be modified 7 Analog AI3 given 0 5 1 17 E2 Group PID function No Code Parameter name Setting range Factory setting Chan ge 383 E2 00 PID setting source 0...

Страница 58: ...ditions 0 no switching 1 switching via terminals 2 automatically switching according to deviation 0 403 E2 20 PID parameter switching deviation 1 0 0 to E2 21 20 0 404 E2 21 PID parameter switching de...

Страница 59: ...it Virtual VDI2 Hundreds digit Virtual VDI3 Thousands digit Virtual VDI4 Tens of thousands Virtual VDI5 11111 423 E3 07 AI1 terminal as a function selection of DI 0 to 50 0 424 E3 08 AI2 terminal as a...

Страница 60: ...0 1kW to 1000 0kW Depends on models 440 b0 02 Rated voltage 1V to 2000V Depends on models 441 b0 03 Rated current 0 01A to 655 35A inverter power 55kW 0 1A to 6553 5A inverter rate 55kW Depends on mod...

Страница 61: ...uto tunning 0 no operation 1 asynchronous motor parameters still auto tunning 2 asynchronous motor parameters comprehensive auto tunning 11 synchronous motor parameters still auto tunning 12 synchrono...

Страница 62: ...lay selection Units digit d group display selection 0 not displays 1 displays Tens digit E group display selection the same above Hundreds digit b group display selection the same above Thousands digi...

Страница 63: ...8 Custom fault 2 29 Power on time arrival 30 Load drop 31 PID feedback loss when running 40 Fast current limiting timeout 41 Switch motor when running 42 Too large speed deviation 43 Motor overspeed 4...

Страница 64: ...ed 487 y1 19 Power on time of the second fault 488 y1 20 Running time of the second fault 489 y1 21 Reserve 490 y1 22 Reserve 491 y1 23 Frequency of the first fault 492 y1 24 Current of the first faul...

Страница 65: ...time is too short 2 manual torque boost or V F curve is not suitable 3 the voltage is low 4 the short circuit or earthing of inverter output happens 5 the control mode is vector and without identific...

Страница 66: ...and brake resistor 7 Err 07 Constant speed overvoltage 1 there is external force to drag the motor to run when running 2 the input voltage is high 1 cancel the external force or install braking resist...

Страница 67: ...ult Input external fault signal through the multi function terminal DI Reset run 16 Err 16 Communicati on fault 1 the communication cable is not normal 2 the settings for communication expansion card...

Страница 68: ...the load is removed or not or the settings for parameter F8 31 F8 32 accord with the Actual operating conditions 31 Err 31 PID feedback loss when running fault PID feedback is less than the set value...

Страница 69: ...must comply with the requirements of electromagnetic interference and anti electromagnetic interference Our existing products adopt the latest international standards IEC EN61800 3 2004 Adjustable sp...

Страница 70: ...nd the other is the conduction interference of the inverter These two types of interference cause that the surrounding electric equipment suffer from the affect of electromagnetic or electrostatic ind...

Страница 71: ...olution is to reduce the carrier frequency or install output reactor It is recommended that the thermal relay shall not be installed in the front of the motor when using the inverter and that electron...

Страница 72: ...eplate Cooling fan operation panel Upper cove plate Upper cover plate retaining screw Cable inlet Air duct inlet Figure 7 1 15kW G3 above Product outside drawing installation dimension 7 1 2 PI500 ser...

Страница 73: ...PI500 0R4G2 0 4 PI500 0R7G1 0 75 PI500 0R7G2 0 75 PI500 0R7G3 0 75 PI500 0R7G4 0 75 PI500 1R5G2 1 5 PI500 1R5G3 1 5 PI500 1R5G4 1 5 PI500 2R2G3 2 2 PI500 2R2G4 2 2 PI500 1R5G1 1 5 163 185 90 166 174...

Страница 74: ...Chapter 7 Dimension 70 Chapter 7 A B d H1 H W D D1 Figure 7 4 15 220kW G3 Dimension A 2 A D D1 H W B d H1 Figure 7 5 250 400kW G3 Dimension...

Страница 75: ...0 045G3N 45 PI500 030G4 037F4 30 37 PI500 037G4 045F4 37 45 PI500 045G4N 45 PI500 022G2 22 500 520 300 275 283 220 500 10 42 PI500 030G2 30 PI500 037G2 37 PI500 045G3 055F3 45 55 PI500 055G3 55 PI500...

Страница 76: ...220F4 200 220 PI500 220G4 220 PI500 132G6 160F6 132 160 PI500 160G6 187F6 160 187 PI500 250F3 250 940 980 560 410 418 415 945 13 153 PI500 250G3 280F3 250 280 PI500 280G3 280 PI500 250F4 250 PI500 250...

Страница 77: ...ension 73 Chapter 7 7 1 3 PI500 series With DC reactor base H H1 W D1 D A B d Figure 7 6 132 220kW G3 With DC reactor and base Dimension D A B d H W H1 D1 Figure 7 7 250 400kW G3 With DC reactor and b...

Страница 78: ...200 220 PI500 220G4R 220 PI500 250F3R 250 1419 1460 560 410 418 500 310 13 205 PI500 250G3R 280F3R 250 280 PI500 280G3R 280 PI500 250F4R 250 PI500 250G4R 280F4R 250 280 PI500 280G4R 280 PI500 315F3R...

Страница 79: ...3R 200F3R PI500 200G3R 220F3R PI500 220G3R PI500 160G4R 187F4R PI500 187G4R 200F4R PI500 200G4R 220F4R PI500 220G4R PI500 250F3R 560 1460 410 947 164 330 208 208 530 13 24 15 PI500 250G3R 280F3R PI500...

Страница 80: ...200 600 612 680 550 17 PI500 450G3R 500F3R 450 500 PI500 500G3R 560F3R 500 560 PI500 560G3R 630F3R 560 630 PI500 630G3R 700F3R 630 700 Note With the letter R means with a DC reactor product installati...

Страница 81: ...7 11 keyboard size chart size mm PI500 keyboard installation opening size 82 126 5 84 129 4 R9 T 1 0 1 5mm T 1 0 1 5mm Installation panel Installation panel Outside installation panel open inlet dimen...

Страница 82: ...nce Whether appearance is abnormal or not Visually check No abnormal Wires and conduct ing bar Whether they are loose or not Visually check No abnormal Termina ls If screws or bolts are loose or not T...

Страница 83: ...5 rated power 30minutes Last 100 rated power 30minutes More than 3 years Use adjustable power to charge the frequency inverter 25 rated power 2hours 50 rated power 2 hours 75 rated power 2hours Last 1...

Страница 84: ...the current at the input terminal generally the deviation is not more than 10 that is normal If the deviation exceeds 30 please inform the original manufacturer to replace rectifier bridge or check i...

Страница 85: ...acket Insulation Insulation Note If conductivity of the cable shield can not meet the requirements you must use a separate PE conductor To play a protective role of conductor when the shield wire and...

Страница 86: ...nt malfunction Wireless interference The high frequency electromagnet wave emitted by the inverter and cables will interfere with the nearby wireless device and make it noise when receiving signal Ins...

Страница 87: ...Users beyond the standard specifications require the use of the inverter caused by product failure 2 4 Users to buy and then fell loss or damage caused by improper handling 2 5 Because the user use a...

Страница 88: ...is 0 to 247 and 0 refers to broadcast communication address The address of slave for network must be exclusive Figure I 3 is the single inverter and PC set up MODBUS field wiring diagram Because compu...

Страница 89: ...1 2 Protocol description PI500 series inverter communication protocol is a asynchronous serial master slave communication protocol in the network only one equipment master can build a protocol known a...

Страница 90: ...t in an error because the value in the final CRC field is not right RTUframe format Frame header START Time interval of 3 5characters Slave address ADR Communication address 1 to 247 Command code CMD...

Страница 91: ...The receiving device recalculates the value of the received CRC and compares the calculated value to the Actual value of the received CRC field if the two values are not equal then there is an error...

Страница 92: ...ss High byte F0 to FB F group A0 to AF E group B0 to BF B group C0 to C7 Y group 70 to 7F d group low byte 00 to FF this should be written EPPROM For example address F3 12 indicates F30C Note L0 group...

Страница 93: ...0000 to10000 Decimal 1011 PID feedback 1001 Running frequency 1012 PLC step 1002 Bus voltage 1013 High speed pulse input frequency unit 0 01kHz 1003 Output voltage 1014 Feedback speed unit 0 1Hz 1004...

Страница 94: ...Command content 2001 BIT0 SPA output control BIT1 RELAY2 output control BIT2 RELAY1 output control BIT3 Manufacturer reserves the undefined BIT4 SPB switching quantity output control Analog output DA...

Страница 95: ...p 001F PID feedback loss when running 0028 Fast current limiting timeout 0029 Switch motor when running fault 002A Too large speed deviation 002B Motor overspeed 002D Motor overtemperature 005A Encode...

Страница 96: ...sponse delay is less than the system processing time delayed response to system processing time shall prevail such as response delay is longer than the system processing time system processed data to...

Страница 97: ...rd with 1 1 frequency dividing output 5V 12V 24V voltage is optional please provide voltage and pulse input mode information when ordering Terminal wiring III 2 Description of mechanical installation...

Страница 98: ...Swappable NO Wire gauge 22AWG 0 3247mm Resolution 12 bit Excitation frequency 10kHz VRMS 7V VP P 3 15 27 PI500_PG4 terminal description No Label No Description No Label No Description 1 EXC1 Rotary t...

Страница 99: ...ol document IV2 Mechanical installation and terminal functions IV 2 1 Mechanical installation modes Figure IV 1 CAN bus communication card s installation on SCB IV 2 2 Terminal function Class Terminal...

Страница 100: ...dress 6 Binary Consisting of 64 bit binary address more than 64 outside the address can be set only by function code The following lists some slave address and switch settings Address switch settings...

Страница 101: ...DP Card and inverter connected to the normal state of the LED is lit flashing indicates the connection is intermittent for interference and drive off when a serial connection is unsuccessful You can c...

Страница 102: ...tting No Code Parameter name Setting range F0 03 Frequency source master setting PID control setting 8 F0 11 Command source selection Terminal block control LED on 1 E2 00 PID setting source E2 01sett...

Страница 103: ...ed by the function code E2 27 In this case PID operation must be stopped E2 27 1 E2 01 The method of calculating the signal value given by the keyboard E2 01 Set the pressure of the full scale of the...

Страница 104: ...0 5V signal output you need to set the parameters as follows No Code Parameter name Setting range F2 07 DA1output function selection Running frequency 0 F2 16 DA1 zero bias coefficient 100 0 100 0 0...

Страница 105: ...ntrol LED on 1 F1 02 DI3 terminal function selection Forward JOG FJOG 4 F1 03 DI4 terminal function selection Reverse JOG RJOG 5 V 5 Multi speed running V 5 1 electrical diagram S1 S2 S3 S4 380V 50 60...

Страница 106: ...election Multi speed terminal 3 14 E1 00 0 stage speed setting 0X 0 stage speed frequency setting percentage 20 0 E1 01 1 stage speed setting 1X 1 stage speed frequency setting percentage 40 0 E1 02 2...

Страница 107: ...potentiometer X2 0 100 00 1 00 Note F1 42 is used to adjust the rate of change of panel potentiometer rotation frequency The smaller this value is the more sensitive the panel potentiometer rotation f...

Страница 108: ...ge signal given V 9 1 electrical diagram Circuit breaker 380V 50 60Hz Three phase input power supply Motor M 0 10V DC Default FWD STOP REV STOP External simulation speed regulation External 0 10V volt...

Страница 109: ...rter and the AI2 jumper cap to the I terminal V 10 3 Parameter setting No Code Parameter name Setting range F0 03 Frequency source master setting AI2analog quantity setting 3 F0 11 Command source sele...

Страница 110: ...Command source selection Terminal block control LED on 1 F0 13 Acceleration time 1 0 0s 6500s 50 0s F0 14 Deceleration time 1 0 0s 6500s 50 0s F0 18 Carrier Frequency 0 5kHz 16 0 kHz 4 0 kHz F0 21 Upp...

Страница 111: ...ing No Code Parameter name Setting range F0 03 Frequency source master setting Panel potentiometer setting 4 F0 04 Frequency source auxiliary setting AI1analog quantity setting 2 F0 11 Command source...

Страница 112: ...dback For your convenience please visit our website http www powtran com and then click Technologies and Services and Download columns to submit your feedback information 1 Download the update product...

Отзывы: