Chapter 5 Function parameter
42
Ch
ap
ter 5
161 F4.07 Multipoint V/F frequency point 3
F4.05 to b0.04 (rated motor
frequency)
0.00Hz
★
162 F4.08 Multipoint V/F voltage point 3
0.0% to 100.0%
0.0%
★
163 F4.09 Slip compensation coefficient
0% to 200.0%
0.0%
☆
164 F4.10 Overexcitation gain
0 to 200
80
☆
165 F4.11 Oscillation suppression gain
0 to 100
0
☆
166 F4.12 V/F separation voltage source
0 to 9
0
☆
167 F4.13 V/F separation voltage digital setting 0V to rated motor voltage
0V
☆
168 F4.14 V/F separation voltage rise time
0.0s to 1000.0s
0.0s
☆
5-1-7.F5 Group - Vector control parameters
No. Code
Parameter name
Setting range
Factory
setting
Chan-
ge
169 F5.00 Speed loop ratio G1
1 to 100
30
☆
170 F5.01 Speed loopintegral T1
0.01s to 10.00s
0.50s
☆
171 F5.02 switching frequency 1
0.00 to F5.05
5.00Hz
☆
172 F5.03 Speed loop ratio G2
0 to 100
20
☆
173 F5.04 Speed loop integral T2
0.01s to 10.00s
1.00s
☆
174 F5.05 switching frequency 2
F5.02 to F0.19(max. frequency) 10.00Hz
☆
175 F5.06 Speed loop integral
0: invalid 1: valid
0
☆
176 F5.07 Torque limit upper limit source
0: Function code F5.08 setting
1: AI1
2: AI2
3: Panel potentiometer setting
4: High-speed pulse setting
5: Communication setting
6: Min(AI1, AI2)
7: Max(AI1, AI2)
8: AI3 setting
0
☆
177 F5.08 Upper limit digital setting for torque 0.0% to 200.0%
150.0%
☆
178 F5.09 Vector control differential gain
50% to 200%
150%
☆
179 F5.10 Speed loop filter time constant
0.000s to 0.100s
0.000s
☆
180 F5.11 Vector control overexcitation gain
0 to 200
64
☆
181 F5.12
Excitation regulator proportional
gain
0 to 60000
2000
☆
182 F5.13 Excitation regulator integral gain
0 to 60000
1300
☆
183 F5.14 Torque regulator proportional gain
0 to 60000
2000
☆
184 F5.15 Torque regulator integral gain
0 to 60000
1300
☆
5-1-8.F6 Group - Keyboard and display
No. Code
Parameter name
Setting range
Factory
setting
Chan-
ge
185 F6.00 STOP/RESET key functions
0: STOP/RES key is enabled only