Powtier Controls Limited

Air Curtain Controller

Instruction Manual

Description

The Air Curtain Controller (ACC) consists of a base unit and a remote unit. The base unit
houses the power supply, sensor input conditioning circuitry, microcontroller, output drive to
heaters and fan, thermal trip protection, Building Management System (BMS) control logic
and interface to the remote unit.

The remote unit forms the operator panel which consists of three 7-segment Light Emitting
Diode (LED) display for temperature and parameters indication and three push buttons for
control and setting adjustments.

All the connections to the controller are via screw terminals.

Power supply

The ACC requires 3 phase 4 wire 415Vac 50/60Hz supply.

Sensor input

A high accuracy Negative Temperature Coefficient (NTC) temperature sensor is supplied as
standard.

Control output

Opto-triac  outputs   are  used  for  the  control  of  heater  output.  The   rating   is  3  phase 3  wire
415Vac, up to 24KW max.

Relay outputs are used for the control of the fan speed; high, medium, low or off.

User interface

The user interface comprises of 3 digits 7-segment red LED display and 3 push buttons.

The 7-segment display is used to indicate measured temperature, setpoint temperature, heater
On/Off setting, fan  speed setting. It  is also used to show other engineering parameters (in
engineering   view   mode)   such   as   proportional   band,   current   output   power,   heatsink
temperature, zero and span reference, air alarm setting, heatsink alarm setting and minimum
power setting.

One push button is used to scroll the parameter display. Two adjustment push buttons "UP"
and "DOWN" are used to increment and decrement the parameters settings. 

Please   note   after   3   minutes   of   inactivity   on   the   push   buttons,   the   display   will   revert   to
showing air temperature or alarm.

ACCIM

Page 4

5 March 2007

Issue 1.4

Содержание ACC-12-00

Страница 1: ...rts thereof may not be reproduced in any form without written permission of the publishers The information in this document is subject to change without notice and should not be construed as a commitm...

Страница 2: ...llation 5 Base unit 5 Remote unit 5 Communication 5 Protection 6 Connection diagram 6 Connection terminals base unit 7 Connection terminals remote unit 8 Layout diagram base unit 9 Layout diagram remo...

Страница 3: ...rol the air curtain ACC When the measured temperature is lower than the setpoint temperature the output will cycle between its minimum and maximum output settings All user adjustments are by means of...

Страница 4: ...supplied as standard Control output Opto triac outputs are used for the control of heater output The rating is 3 phase 3 wire 415Vac up to 24KW max Relay outputs are used for the control of the fan sp...

Страница 5: ...act is connected to a 2 way connector marked BMS The input is normally closed to enable the fan and heater output The connection is not polarity sensitive The external thermal trip volt free contact i...

Страница 6: ...st switch to On and the rest to Off To change the address to 8 set the right most switch to On and the rest to Off The base unit is shipped with a default address of 0 Protection There are two high sp...

Страница 7: ...w speed Md Fan medium speed Hi Fan high speed BMS BMS control logic normally closed volt free contact BMS BMS control logic normally closed volt free contact AIR Air sensor non polarised AIR Air senso...

Страница 8: ...urtain Controller Instruction Manual Connection terminals remote unit Terminal Description 7V Supply from base unit 0V Supply from base unit B RS485 Comms to base unit A RS485 Comms to base unit ACCIM...

Страница 9: ...Powtier Controls Limited Air Curtain Controller Instruction Manual Layout diagram base unit ACCIM Page 9 5 March 2007 Issue 1 4...

Страница 10: ...Powtier Controls Limited Air Curtain Controller Instruction Manual Layout diagram remote unit ACCIM Page 10 5 March 2007 Issue 1 4...

Страница 11: ...Powtier Controls Limited Air Curtain Controller Instruction Manual Dimensional drawing base unit ACCIM Page 11 5 March 2007 Issue 1 4...

Страница 12: ...3 Minimum Power setting 0 99 0 The default display on the remote unit is the air sensor temperature Air temperature t This will change to alarm display if there is active alarm The unit address ranged...

Страница 13: ...trol will be lifted by several degrees depending on the Fan setting For example when the setpoint is 20 and the fan is set at high speed 3 the control setpoint will be 20 8 28 Internal setpoint lift d...

Страница 14: ...the heatsink sensor detects the temperature of the heatsink above 65 C Heatsink sensor failure Code 16 this is triggered when the heatsink sensor is open circuit typically when the heatsink sensor is...

Страница 15: ...rotection of the heater switching devices Fan Output 3 off Relay for High Medium and Low Fan setting 3A max 240Vac Display Three 7 segment LED red for parameter display Push buttons 3 positive feedbac...

Страница 16: ...n controller with 415V supply and 12KW load maximum or ACC 6 00 is an Air Curtain controller with 240V supply and 6KW load maximum Ambirad Part numbers Remote Unit 900306 Base Unit 6KW to be confirmed...

Отзывы: