Powtier Controls Limited

Air Curtain Controller

Instruction Manual

Control

The   ACC   is   designed   such   that   when   the   measured   temperature   is   below   the   setpoint
temperature, depending on the Proportional Band (proband) setting, the output will assume
the value shown in the table below.

Percentage of full heat

Proband

Setpoint & above

-1°C

-2°C

-3°C

-4°C

-5°C

5

Minimum Power%

20%

40%

60%

80%

100%

4

Minimum Power%

25%

50%

75%

100%

3

Minimum Power%

33%

66%

100%

2

Minimum Power%

50%

100%

1

Minimum Power%

100%

The setpoint temperature can be adjusted between 16 to 35 on the Remote unit through the
parameter [Setpoint - S]. Due to air chill factor, the actual setpoint used internally for control
will be lifted by several degrees depending on the Fan setting. For example, when the setpoint
is 20, and the fan is set at high speed (3), the control setpoint will be 20+8=28.

Internal setpoint lift due to air chill factor

High = 8°C
Medium = 6°C
Low = 5°C

The   proband   can   be   adjusted   between   1   to   5   on   the   Remote   unit   through   the   parameter
[Proportional band - b]

The heater output can be switched off from the Remote panel by selecting the parameter [Heat
Off/On - H]; Off [=0], On [=1]. This will also switch off the heatsink fan unless the heatsink
temperature is higher than 50°C.

There is also a fan control selection [Fan off,low,mid,high  - F] on the Remote unit which
enables the fan to switch between high speed [=3], medium speed [=2], low speed [=1] and
off [=0].

The output cycle time for the heater output is fixed at 0.3s and cannot be changed.

ACCIM

Page 13

5 March 2007

Issue 1.4

Содержание ACC-12-00

Страница 1: ...rts thereof may not be reproduced in any form without written permission of the publishers The information in this document is subject to change without notice and should not be construed as a commitm...

Страница 2: ...llation 5 Base unit 5 Remote unit 5 Communication 5 Protection 6 Connection diagram 6 Connection terminals base unit 7 Connection terminals remote unit 8 Layout diagram base unit 9 Layout diagram remo...

Страница 3: ...rol the air curtain ACC When the measured temperature is lower than the setpoint temperature the output will cycle between its minimum and maximum output settings All user adjustments are by means of...

Страница 4: ...supplied as standard Control output Opto triac outputs are used for the control of heater output The rating is 3 phase 3 wire 415Vac up to 24KW max Relay outputs are used for the control of the fan sp...

Страница 5: ...act is connected to a 2 way connector marked BMS The input is normally closed to enable the fan and heater output The connection is not polarity sensitive The external thermal trip volt free contact i...

Страница 6: ...st switch to On and the rest to Off To change the address to 8 set the right most switch to On and the rest to Off The base unit is shipped with a default address of 0 Protection There are two high sp...

Страница 7: ...w speed Md Fan medium speed Hi Fan high speed BMS BMS control logic normally closed volt free contact BMS BMS control logic normally closed volt free contact AIR Air sensor non polarised AIR Air senso...

Страница 8: ...urtain Controller Instruction Manual Connection terminals remote unit Terminal Description 7V Supply from base unit 0V Supply from base unit B RS485 Comms to base unit A RS485 Comms to base unit ACCIM...

Страница 9: ...Powtier Controls Limited Air Curtain Controller Instruction Manual Layout diagram base unit ACCIM Page 9 5 March 2007 Issue 1 4...

Страница 10: ...Powtier Controls Limited Air Curtain Controller Instruction Manual Layout diagram remote unit ACCIM Page 10 5 March 2007 Issue 1 4...

Страница 11: ...Powtier Controls Limited Air Curtain Controller Instruction Manual Dimensional drawing base unit ACCIM Page 11 5 March 2007 Issue 1 4...

Страница 12: ...3 Minimum Power setting 0 99 0 The default display on the remote unit is the air sensor temperature Air temperature t This will change to alarm display if there is active alarm The unit address ranged...

Страница 13: ...trol will be lifted by several degrees depending on the Fan setting For example when the setpoint is 20 and the fan is set at high speed 3 the control setpoint will be 20 8 28 Internal setpoint lift d...

Страница 14: ...the heatsink sensor detects the temperature of the heatsink above 65 C Heatsink sensor failure Code 16 this is triggered when the heatsink sensor is open circuit typically when the heatsink sensor is...

Страница 15: ...rotection of the heater switching devices Fan Output 3 off Relay for High Medium and Low Fan setting 3A max 240Vac Display Three 7 segment LED red for parameter display Push buttons 3 positive feedbac...

Страница 16: ...n controller with 415V supply and 12KW load maximum or ACC 6 00 is an Air Curtain controller with 240V supply and 6KW load maximum Ambirad Part numbers Remote Unit 900306 Base Unit 6KW to be confirmed...

Отзывы: