Form #44201150
Sept 2010
-39-
k.
To shut down the appliance for longer periods of time, switch of the electricity supply to the appliance and
turn off the gas supply at the gas isolation valve.
NOTE: The lighting and shutdown instructions are also shown on a permanent label attached adjacent to the
controls for the heater (see section 9.2).
COMMISSIONING
The chart below shows the sequence of operation for the normal operating cycle.
T0 T1
T2
T3
T4
Call for heat, Thermostat on
Thermostat
Blower
Amber neon indicator
Ignition
Air switch
Gas valve
Flame sensing
Function ON
Function OFF
Red neon indicator
20 secs pre-purge
10 secs trial for ignition
Normal operation flame sensing
Thermostat off, Heater OFF
T5
Fig. 39
If the flame is not sensed during sequence T3 then the heater will go to lockout.
It is essential that all new pipework installations are purged and tested for soundness with a suitable leak
detection fluid prior to attempting to ignite any appliance. This work should be carried out in accordance with
National or Local regulations.
NOTE: DO NOT TEST FOR SOUNDNESS BY USE OF NAKED FLAMES.
16.0)
CLEANING AND ANNUAL MAINTENANCE
ELECTRIC SHOCK & EXPLOSION HAZARD
Disconnect electrical power and gas supply before
servicing.
Failure to do so may result in death or serious injury.
This heater must be cleaned and serviced annually by a qualified contractor before the start of each heating
season and at any time excessive accumulation of dust and dirt is observed. Maximum heating efficiency and
clean combustion will be maintained by keeping the heater clean.
It is essential that at least once a year, preferably before the heating season, a qualified person service the
appliance. In exceptionally dirty conditions, more frequent servicing may be desirable.
IMPORTANT:
a.
Do not rest anything, especially ladders, against the appliance.
b.
Gas and Electricity supplies must be isolated before commencing servicing work or replacement of
components.