Form #44201150
-24- Sept
2010
i.
Once all the heater body sections are attached, make sure that the heater system is level. If it is not, slight
adjustments can be made using the turnbuckles. (See Section 7.0) Fig. 23
10.2) INSERTING TURBULATORS
Failure to do so may result in death, serious injury, property damage or illness
from Carbon Monoxide poisoning.
The heater must be assembled with the correct number of turbulator sections
and tube length for the rated heat input.
The turbulators must be installed in the tube sections as shown below.
POISONOUS GAS AND SOOT HAZARD
1.
Assemble the turbulators together by interlocking the slotted end portions.
2.
Slide these into the last tube sections located at the U-bend as shown for U-Models or into the last tube
section located at the fan as shown for Linear Model heaters.
3.
Align turbulator end flush with end of tube.
Note: Refer to the table below for quantities of turbulators required for each heater model.
Radiant Tube
a. 76.2mm
b. 101.6mm
Turbulators
(insert in flat position)
a. 65mm wide x 572mm long
b. 90mm wide x 610mm long
Bottom View
LINEAR MODEL HEATERS
Turbulators at Fan End
Bottom View
U-MODEL HEATERS
Turbulators on Burner Leg
at U-Bend End
Turbulators on Fan Leg
at U-Bend End
End View
Fig. 24
INCORRECT
INSTALLATION
CORRECT
INSTALLATION
Force
Bars
Reaction
Block
Interference
Pins
Bolt
Band
Important: NEVER reuse a coupling. Always install a new coupling only and
torque as per instructions above and the diagrams above.
Содержание PHS 25