Form #44201150
Sept 2010
-31-
13.0)
ELECTRICAL CONNECTIONS
Failure to do so may result in death or serious injury.
This appliance must be connected to earth.
Disconnect electrical power and gas supply before servicing.
ELECTRIC SHOCK HAZARD
a.
The electrical wiring to this heater must be installed in accordance with the latest or current National
Regulations and any Local Regulations, which apply.
Electrical
supply
230V~50Hz
125W
Current
rating
0.55
Fuse
externally
3A
b.
Twin core and earth PVC covered flexible supply cable (0.5mm2-to National or Local standard specification)
must be used, with connection made as follows:
Single Heaters per Thermostat connection diagram
GREEN/YELLOW
BLUE
BROWN
Thermostat
Service
Switch
Heater 1
Continue To
Additional
Heaters
Thermostat
Service
Switch
Heater 2
L
N
E
1
2
7
1
2
7
Fig. 33
Multiple Heaters per Thermostat connection diagram
GREEN/YELLOW
BLUE
BROWN
Thermostat
Service
Switch
Heater 1
Continue To
Additional
Heaters
Service
Switch
Heater 2
E
N
L
1
2
7
1
2
7
Fig. 34
Notes: The method of connection to the electrical supply must facilitate complete isolation and should
preferably be via a fused double pole isolator having a constant separation of at least 3mm in all poles and
supplying the appliance ONLY.
Alternatively, connection may be made via a fused 3 pin plug and un-switched, shuttered socket, both
complying with the requirements of National or Local Regulations. Neither thermostat nor switch are
supplied as standard equipment. NOTE: In the event of an electrical fault after installation of the appliance,
preliminary system checks are required to be carried out i.e. earth continuity, polarity and resistance to earth.