INSTALLATION
EATON
Powerware
®
Energy Management System (EMS) Upgrade Kit User’s Guide
S
164201724 Rev 1
www.powerware.com
32
4.
Configure the following settings for the selected panel:
Panel Setting
Description
Panel Rating
Specify the panel breaker rating (in amps).
NOTE
Setting the panel breaker rating to 0 silences all
main panel breaker alarms and zeroes the panel percent
current levels.
Panel Warn (%)
Specify the warning threshold level (in percent load).
Panel Alarm (%)
Specify the alarm threshold level (in percent load).
Num Brkr Positions
Specify the number of breakers in the panel.
Panel Name
Specify a panel name (up to 19 characters).
Panel Serial Number
Specify the panel’s serial number (up to 19 characters).
Panel Layout
Specify the panel numbering style.
NOTE
Changing panel layout erases all branch circuit
breaker configurations.
NOTE
To revert any changes made on the current page back to default settings before
saving, click
Reload Panel Config
.
5.
Click
Save Panel Config
to save the settings to the EMS−UGK.
Depending on communication speed, updates take effect within
15–20 seconds.
6.
Repeat Steps 3 through 5 to configure the remaining panels.
7.
Click the
Breaker Config
tab to display the Breaker Settings page.
The tool automatically updates the default breaker schedule with
the latest information from the EMS−UGK. Depending on
communication speed, updates take effect within 15–20 seconds.
8.
Select the
Panel Number
of the panel containing the breakers to
configure. The tool automatically updates the selected breaker
schedule with the latest information from the EMS−UGK.
Depending on communication speed, updates take effect within
15–20 seconds.