INSTALLATION
EATON
Powerware
®
Energy Management System (EMS) Upgrade Kit User’s Guide
S
164201724 Rev 1
www.powerware.com
30
11.
Click the
Feature Settings
tab to display the EMS Feature Settings
page.
12.
Configure the following Miscellaneous Features:
Feature Setting
Description
Audible Horn Disabled
Select to disable the audible horn. If enabled, the horn
sounds for each new alarm and can be turned off by
pressing any key on the display.
Meter Simulation Mode
Enabled
Select to enable demonstration mode for use with a
simulator.
LCD Displays Input 1 V as L to L
LCD Displays Input 2 V as L to L
Select to display Line to Line voltages on the display.
If unselected, voltages display as Line to Neutral
voltages.
Enable THD Alarms
Select to enable Total Harmonic Distortion metering
alarms detected by monitor.
Enable Dual Input Mode
Select for dual input models.
NOTE
Deselecting this option removes all selections
and displays for the second input.
13.
Configure the following Building Alarm Settings:
Feature Setting
Description
Set Custom Alarm Name
Type a name for Building Alarms 1 through 4.
Contact Type
Select if the Building Alarm is connected as
normally−closed.
Action When Active
Select the action to occur when the Building Alarm
becomes active.
NOTE
To revert any changes made on the current page back to default settings before
saving, click
Reload Config
.
14.
Click
Save Config
to save the settings to the EMS−UGK. Depending
on communication speed, updates take effect within 15–20
seconds.