APPENDIX A – INSTALLATION – INDUSTRIAL POWER CONDITIONERS 

 
GENERAL INSTALLATION 

 

This device is designed for permanent mounting inside a control cabinet or to a 

wall or other solid structure using #10 hardware. The conditioner has a dustproof 
and splashproof enclosure and may be mounted in any position.  This device is 
intended for use in hardwired installations.   

 

A Phillips screwdriver is required to remove the power conditioner cover.  Once 

the cover has been removed, carefully set it to one side. 

This power conditioner is installed by connecting input power to terminal block 

TB1 and output power to terminal block TB4. The terminal blocks are designed for a 
maximum wire size of 8 AWG.  Access to these terminal strips is via the side, top or 
bottom knockouts.  Input power should be fed through a properly sized circuit 
breaker at the panelboard.  All applicable electrical codes must be observed for the 
installation of this device.  

 The data plate on the conditioner lists the current and voltage rating of this 

device.  The total current of all connected loads must not exceed the maximum total 
current rating.  An automatically resetting thermal cut-off switch is embedded in the 
transformer to protect against prolonged overcurrent. 

 
 
 
 
 
Unless specified differently at the time of order, the power conditioner has been 

set during manufacture by the factory for a 480-volt input.  The input voltage of the 
power conditioner is selectable from 480, 240, 208 or 120 volts and may be changed 
by moving the jumpers on 

BOTH

 TB2 and TB3.  See Figure 1 that follows for proper 

jumper positioning and an example of how the conditioner may be rewired.  When 
connections are completed, replace the cover before applying power to the power 
conditioner. 

 
 
 
 
 
For the best power conditioning results, all load equipment ground leads should 

be connected to a common point.  A single point ground bus-bar is provided on the 
lower mounting flange for this purpose. 

 

OPERATING INSTRUCTIONS 

  Energize the circuit feeding the power conditioner by placing the panelboard 

circuit breaker in the ON position 

  With a voltmeter, check that the power conditioner output voltage is 120 volts 

  Turn on the load equipment and test for proper operation. 

WARNING:  TO PREVENT ELECTRICAL SHOCK, BE CERTAIN TO TURN OFF ALL 
ELECTRICAL POWER BEFORE CONNECTING THE POWER CONDITIONER TO THE 
POWER LINE AND BEFORE CONNECTING THE LOAD TO THE POWER CONDITIONER.

WARNING:  DO NOT CONNECT INPUT OR OUTPUT POWER CONNECTIONS TO TB2 OR 
TB3.  THESE TERMINAL STRIPS ARE ONLY FOR USE IN SETTING THE POWER 
CONDITIONER’S INPUT OPERATING VOLTAGE.

Caution:  WHEN CHANGING INPUT VOLTAGE SETTINGS, YOU MUST CHANGE JUMPERS 
ON BOTH TB2 AND TB3.  FAILURE TO DO SO MAY DAMAGE THE POWER CONDITIONER 
AND VOID THE PRODUCT WARRANTY. 

Содержание ABC10.0-2S

Страница 1: ...er s Guide Industrial Conditioners GPI Series B Conditioners GPI Series 1 Conditioners 2 15 kVA Single Phase Conditioners GPI Series 1 Conditioners POWERVAR Single Phase Power Conditioners RoHS Compliant ...

Страница 2: ...hanges may periodically be made to the information herein and such changes may be incorporated in new editions of the product and it s accompanying documentation without obligating POWERVAR to update information and or product that has been delivered earlier POWERVAR assumes no liability for typographical errors in this documentation POWERVAR shall not be liable for technical or editorial errors o...

Страница 3: ...ill not be exposed to excessive dust or moisture Make certain that there is adequate airflow around the unit If the unit has air vents do not place objects on top of or near the unit in such a way as to block the vents TECHNICAL AND SERVICE ASSISTANCE Technical and service assistance is available in North America between the hours of 8 00 a m and 5 00 p m Central Time by calling 800 369 7179 in Il...

Страница 4: ...eu of all other warranties No greater degree of liability is imposed on the manufacturer INSTALLATION AND OPERATING INSTRUCTIONS Please consult Appendix A for installation and operating instructions on the following models ABC360 91IND ABC750 91IND ABC1000 91IND ABC1500 91IND Please consult Appendix B for installation and operating instructions on the following models ABC500 91BUI ABC1000 91BUI AB...

Страница 5: ...time of order the power conditioner has been set during manufacture by the factory for a 480 volt input The input voltage of the power conditioner is selectable from 480 240 208 or 120 volts and may be changed by moving the jumpers on BOTH TB2 and TB3 See Figure 1 that follows for proper jumper positioning and an example of how the conditioner may be rewired When connections are completed replace ...

Страница 6: ...Figure 1 INDUSTRIAL POWER CONDITIONERS ...

Страница 7: ...pre configured by the factory for a 120 volt input Series 1 power conditioners are ordered for a specific input voltage and the circuit breaker installed in the unit is the correct one for the selected operating voltage The input voltage of both the GPI Series B and Series 1 can be set to 100 120 208 or 240 volts by changing jumpers on terminal block TB1 as shown in Figure 2 Series B power conditi...

Страница 8: ...013 25 H 5 00 JA2S A38 A 0005 25 H 15 25 JA2S A38 A 1525 25 H 5 50 JA2S A38 A 05R5 25 H 15 50 JA2S A38 A 1550 25 H 6 50 JA2S A38 A 06R5 25 H 17 00 JA2S A38 A 1700 25 H 7 75 JA2S A38 A 7R75 25 H 20 50 JA2S A38 A 2050 25 H 8 50 JA2S A38 A 08R5 25 H 25 50 JA2S A38 A 2550 25 H 8 75 JA2S A38 A 8R75 25 H 30 50 JA2S A38 A 3050 25 H 10 25 JA2S A38 A 1025 25 H OPERATING INSTRUCTIONS GPI Series B Complete a...

Страница 9: ...Figure 2 INPUT VOLTAGE ADJUSTMENT GPI SERIES B AND GPI SERIES 1 ABC500 XX ABC1000 XX ABC1500 XX ABC2000 XX ABC3000 XX ...

Страница 10: ...are accessed by removing the knockouts on the back panel Terminal blocks are designed to accept a maximum wire size of 8 AWG and 8 foot pounds of torque All applicable electrical codes must be observed for the installation of this device When wiring connections are complete replace the cover before applying power to the power conditioner OPERATING INSTRUCTIONS If power was turned off at the panel ...

Страница 11: ...input move circuit breaker lead from point E2 of the printed circuit filter assembly to point E3 To convert 240 volt input to 208 volt input move circuit breaker lead from point E3 of the printed circuit filter assembly to point E2 Factory default setting is 240 volt input unless specified differently at time of order with factory ...

Страница 12: ...on on models ending with suffix 2S only adjust taps on left side of transformer when viewed from rear of conditioner Moving taps permits changing of input operating voltage between 208 and 240 volts Input voltage adjustment taps this side of transformer ...

Страница 13: ...se SM503 RevC 11 23 04 2004 POWERVAR Inc In North America South America and the Caribbean 1450 Lakeside Drive Waukegan IL 60085 Phone 847 596 7000 Toll Free outside Illinois only 800 369 7179 Fax 847 596 7100 In EMEA Unit 5 Birch Kembrey Park Swindon Wiltshire SN2 8UU United Kingdom Phone 44 0 1793 553980 Fax 44 0 1793 535350 Access additional product information and support on the web at http www...

Отзывы: