WARNING: BEFORE MAKING CONNECTIONS TO GPI SERIES B POWER CONDITIONERS
OR BEFORE CONFIGURING INPUT VOLTAGE ON EITHER GPI SERIES B OR SERIES ONE
CONDITIONERS, BE CERTAIN TO TURN OFF ALL ELECTRICAL POWER. FAILURE TO
OBSERVE THIS PRECAUTION MAY RESULT IN ELECTRICAL SHOCK.
APPENDIX B – INSTALLATION – GPI SERIES B AND GPI SERIES 1
The table below lists the appropriate breaker for a variety of input currents.
These breakers may be purchased from:
Eaton Corporation
Commercial Controls Division, Heinemann Products
Phone: (800) 962-0820, Fax: (414) 449-6118
Input Amps
Circuit Breaker Part
Numbers
2.25 JA2S-A38-A-2R25-25-H 10.50 JA2S-A38-A-1050-25-H
2.50 JA2S-A38-A-02R5-25-H 12.75 JA2S-A38-A-1275-25-H
4.50 JA2S-A38-A-04R5-25-H 13.00 JA2S-A38-A-0013-25-H
5.00 JA2S-A38-A-0005-25-H 15.25 JA2S-A38-A-1525-25-H
5.50 JA2S-A38-A-05R5-25-H 15.50 JA2S-A38-A-1550-25-H
6.50 JA2S-A38-A-06R5-25-H 17.00 JA2S-A38-A-1700-25-H
7.75 JA2S-A38-A-7R75-25-H 20.50 JA2S-A38-A-2050-25-H
8.50 JA2S-A38-A-08R5-25-H 25.50 JA2S-A38-A-2550-25-H
8.75 JA2S-A38-A-8R75-25-H 30.50 JA2S-A38-A-3050-25-H
10.25 JA2S-A38-A-1025-25-H
OPERATING INSTRUCTIONS
GPI Series B
•
Complete all input and output connections. Select input operating voltage that is
correct for the application.
•
Tun input circuit breaker ON.
•
Using a voltmeter, carefully measure output voltage to verify that output is
nominal 120 volts.
•
If nominal output voltage is 120 volts, turn all load equipment on.
GPI Series 1
•
Plug GPI Series 1 into appropriate power receptacle and turn input breaker ON.
•
Using a voltmeter, measure output voltage to verify that output is nominal 120
volts.
•
If nominal output voltage is 120 volts, turn all load equipment on.