Communication Port Configuration Table
Pin
Signal Type
Function
1
Input
(0.2 second RS-232
Remote Power Off:
In absence of normal AC Input,
level high pulse)
output power is kept OFF until normal AC returns.
Unit turns off after delay set by the dip switches.
2
Output
(RS-232 level high)
AC Input Failure:
Indicates absence of normal
AC Input.
3
Output
(simulated contact
AC Input Failure:
Indicates absence of normal Input.
closing with pin 4)
4
Common
Signal Common:
Common signal for pins 1, 2, 3, 5,
6, 7, and 8.
5
Output
(simulated contact
Impending Low Battery:
Indicates that the battery has
internal closing with pin 4)
less than 2 or 5 minutes of backup time left.
6
Output
(simulated contact
AC Input Failure:
Indicates absence of normal
opening with pin 4)
Input.
7
Input
(common or RS-232
Remote Output OFF, ON:
UPS output can be turned
low, open, or RS-232 high)
OFF by maintaining low or common. UPS output
output returns when pin is high or open if normal AC
Input is present. UPS ON/OFF Switch must be ON.
8
Output
(+24VDC
+24VDC:
Short circuit protected. +24VDC is present
unregulated)
whenever the UPS is ON.
9
Chassis Ground
Chassis Ground
Signal Ratings:
open circuit voltage: +40VDC
short circuit current: 50mA
Shielded I/O Cables must be used when making
connections to the Communication Port.
Chapter 3. Operation 26
NOTE
Содержание 0 ACE2200
Страница 1: ...THE ELECTRONIC SYSTEM POWER SPECIALISTS Uninterruptible Power System 400VA 2200VA ...
Страница 2: ...Part Number 05141270 Revision C 3 94 ...
Страница 11: ...Model ACE2200 Model ACE2000 UPS Owner s Manual 7 ...
Страница 24: ...Chapter 2 Installation 20 NOTES ...
Страница 36: ...Chapter 5 Specifications 32 NOTES ...
Страница 39: ...The remaining pages were left blank intentionally ...
Страница 40: ......