Installation
Instructions
Follow the simple step-by-step instructions for
installation. There are separate instructions for
American and International models.
2
Chapter
Changes or modifications not expressly approved by the
party responsible for compliance could void the user’s
authority to operate the equipment.
NOTE
To reduce the risk of fire or electric shock, install in a
temperature and humidity controlled indoor area free
of conductive contaminants.
UPS Owner’s Manual
11
Installation — American
Models:
Warning
OFF
ON
1 2 3 4 5 6 7 8
Set up the Dip Switches according to the
American Dip Switch Configurations table below.
If any switches are changed while the unit is
running, the changes will not take effect until the
unit is completely powered down and then turned
back on.
No
Position Function
1&2* OFF
120V
1
ON
2
OFF
127V
1
OFF
2
ON
110V
1&2 ON
120V w/ extended operating voltage range
3*
OFF
Enable Site Warning Alarm
3
ON
Disable Site Warning Alarm
4*
OFF
Approx. 2 mins. backup after low battery alarm
4
ON
Approx. 5 mins. backup after low battery alarm
5*
OFF
Enable <5% load auto shutdown
(after 5 mins. on battery)
5
ON
Disable <5% load auto shutdown
6*
OFF
Conditional shutdown delay 5 sec.
6
ON
Conditional shutdown delay 180 sec.
7*
OFF
Not used
8*
OFF
Frequency selection priority 60Hz
8
ON
Not used
* These are the default values.
American Dip Switch
Configurations
Содержание 0 ACE2200
Страница 1: ...THE ELECTRONIC SYSTEM POWER SPECIALISTS Uninterruptible Power System 400VA 2200VA ...
Страница 2: ...Part Number 05141270 Revision C 3 94 ...
Страница 11: ...Model ACE2200 Model ACE2000 UPS Owner s Manual 7 ...
Страница 24: ...Chapter 2 Installation 20 NOTES ...
Страница 36: ...Chapter 5 Specifications 32 NOTES ...
Страница 39: ...The remaining pages were left blank intentionally ...
Страница 40: ......