PowerTec Digimax Скачать руководство пользователя страница 41

  Page  33

DIGIMAX

®

®

®

®

®

  

Manual

BASIC MASTER  MODE  SETUP --

BASIC MASTER  MODE  SETUP --

BASIC MASTER  MODE  SETUP --

BASIC MASTER  MODE  SETUP --

BASIC MASTER  MODE  SETUP --

The default values (see TABLE I on page 14) will operate a 1750 RPM motor which is in a frame 259

or smaller without modification. The display will read in RPM, and the acceleration and deceleration times

will be 20 seconds from zero speed up to full speed and from full speed back down to zero speed, respectively.

The preset speed will be 200 RPM, the jump up and jump down speed changes will be 100RPM, and the AT

SPEED LED will come on when the speed is within 10 RPM.

When the default parameters are not suitable for the operation of a motor and control, it is necessary

to gather the information from the motor, control, process parameters, and operators in order to set up the

parameter table to accomplish the job. This information is best gathered ahead of time, and it must be

gathered for EACH 

DIGIMAX

® 

to be set up. If it is not gathered in advance there will be delays when the time

comes to do the actual setup

.

REMEMBER TO PRESS [ENT] AFTER EACH ENTRY OF A NUMBER!

EXAMPLE 1:  Suppose you have a 2500 RPM, 75 HP, 288TZ frame motor with a standard Model 3000C

control which is running a process at 100 Yards Per Minute. You wish to set, and see displayed, the speed

in .1 YPM increments. Accell and Decel times are 10 seconds, and a thread speed of 5 YPM is needed. You

wish to use the MOP mode. The operator is the only one authorized to make any changes, and you give him

his birthdate (2/14/52) as a security code.

1.

Press [PGM] (code) [ENT]. The 

DIGIMAX

® 

 will flash P-1 and the current value. If the flashing

parameter is not P-01, use the UP or DOWN key to bring it up, 

OR

 press [ALT] [1] [ENT].

2.

Enter 2500 (the maximum motor speed) in P-01. Press the UP button.

3.

Enter 1000 (100 YPM plus a decimal place) in P-02. Press the UP button.

4.

Enter 1 in P-03 (one decimal place). Press the UP button.

5.

P-04 is not used in the MASTER mode. Enter 10000 since that is the value used in the slave

mode. Press the UP button.

6.

Enter 240 in P-05. The motor has a 60 PPR encoder and the drive has a X4 multiplier.This

makes the feedback rate 240 PPR. Press the UP button.

7.

Enter 100 in P-06 ( the desired accel time is 10.0 seconds), press the UP button, and

enter100 (10.0 seconds) in P-07 ( the desired decel time). Press the UP button.

8.

Put 0 in P-08, if it is not already there. Press the UP button.

9.

Enter 50 in P-09 to obtain 5.0 YPM preset speed. Press the UP button.

10.

Enter 10 in P-10, press the UP button, and enter 10 in P-11. This will cause the MOP mode

to change speed by 1.0 YPM as soon as the UP or DN button is pressed. 1.0 YPM will be the

smallest change allowed. If a smaller minimum change is desired, put a 1 in P-10 and P-11 to

cause a 0.1 YPM change. Press the UP button.

11.

Enter a 1 in P-12. The speed must be within 0.1 YPM (2.5 RPM) before the AT SPEED LED

indicator will come on. Press the UP button.

12.

Enter a 1 in P-13 to activate the MOP mode of operation. Press the UP button.

13.

Enter a 0 in P-14 to cause the MOP to reset to zero speed on each stop. If you want the motor

to accelerate to the set speed on each start, enter a 1. Press the UP button.

14.

Enter a 1 in P-15 to set a 1 second update time on the display. Press the UP button.

15.

To prevent changing of parameters while running, enter a 1 in P-16. Press the UP button.

16.

P-17 and P-18 do not matter unless the RS-422 is used. Press the UP button twice.

17.

Leave a 0 in P-19 for Local control. Press the UP button.

18.

Parameter P-20 does not apply. Press the UP button.

19.

Enter 21452 in parameter #21 for operator access. Now only the maintenance code and

21452 will allow access to the parameters.

20.

If the advanced functions are not to be used (see page 35), press [PGM] to exit the

parameters.

21.

The control is now ready to put in service.

Содержание Digimax

Страница 1: ...Repair Center for Powertec Drives and Motors 460 Milford Parkway Milford OH 45150 www motorsystems com 513 576 1725...

Страница 2: ...NTROLLED DIGITAL SPEED RATIO CONTROLLER MADE IN USA INSTALLATION AND OPERATION INSTRUCTION MANUAL Revision 2A October 6 1993 This manual is fully implemented with software version SFWVER 93271 and lat...

Страница 3: ...Page ii copyright 1992 1996 by Powertec Industrial Motors...

Страница 4: ...9 18 Baud Rate 19 19 Local Remote Keylock 19 20 Speed Ratio SETPOINT 19 21 Operator Security Code 19 22 A to D Low Engineering Units 19 23 A to D High Engineering Units 20 24 A to D Display Mode 20 25...

Страница 5: ...ADVANCED FUNCTIONS 33 List of Illustrations 1 Physical Dimensions 2 2 Rear Terminal Strip connections 5 3 Connections to the DIGIMAX DIGIMAX DIGIMAX DIGIMAX DIGIMAX 8 4 Front panel Display 9 5 Typica...

Страница 6: ...UNLESS YOU HAVE CHECKED FOR THE PROPER CONNECTIONS NOTICE If you are replacing a DIGIMAX III with a DIGIMAX DIGIMAX DIGIMAX DIGIMAX DIGIMAX check TB2 terminals 1 2 and 3 to be sure that there are no...

Страница 7: ...r abuse defective or incorrect installation effects of the DIGIMAX DIGIMAX DIGIMAX DIGIMAX DIGIMAX on other equipment or effects on the DIGIMAX DIGIMAX DIGIMAX DIGIMAX DIGIMAX causedbyotherequipment a...

Страница 8: ...Page vii DIGIMAX Manual...

Страница 9: ...o operators which may be remote from the location of the motor control Control inputs and outputs are isolated for flexibility and immunity to interactions between units Speed or ratio setpoints and o...

Страница 10: ...Page 2 copyright 1992 1996 by Powertec Industrial Motors Figure 1 Physical dimensions of the DIGIMAX...

Страница 11: ...to and from the DIGIMAX DIGIMAX DIGIMAX DIGIMAX DIGIMAX must be kept away from power wiring All relays used in conjunction with or in the vicinity of the DIGIMAX must have arc suppressors if they have...

Страница 12: ...QUENCY OUTPUT This is the output frequency to the controlled drive or drives It is capable of driving up to ten inputs of motor controls or ten other DIGIMAX DIGIMAX DIGIMAX DIGIMAX DIGIMAX inputs or...

Страница 13: ...peripheral device control By connecting relays to these outputs and using the relays to control the drive it is possible to run the DIGIMAX DIGIMAX DIGIMAX DIGIMAX DIGIMAX and motor control entirely...

Страница 14: ...DIGIMAX does NOT cause the drive to reverse A separate simultaneous command must be given to the drive If the drive is given a reverse command it will not reverse until the DIGIMAX DIGIMAX DIGIMAX DIG...

Страница 15: ...able should have conductors no smaller than 24 AWG for distances up to 500 feet Recommended cables are cables such as Belden Wire Company part 9829 or part 88102 Connecting the link together consists...

Страница 16: ...Page 8 copyright 1992 1996 by Powertec Industrial Motors Figure 3 Connections to the DIGIMAX speed controller...

Страница 17: ...g to a newly entered ratio The REMOTE indicator is on when remote operation is on In one REMOTE mode the keypad is locked out unless the unit s LOC REM key is pressed In another mode even the LOC REM...

Страница 18: ...t must be pressed first followed by a security code and then the ENTER button to access the parameters When the PGM CLR key is pressed the display will blank and the numbers of the security code as th...

Страница 19: ...13 and 12 on TB1 The display shows the letter Ao on the left side of the display and the current value of the Analog Output in Engineering units which are controlled and scaled with parameters 28 thr...

Страница 20: ...N function the UP key will only work for the AUXOUT and the PRESET functions It is not necessary to press the ALT key between the PRESET key and the ON key or after the AUXOUT number key before the ON...

Страница 21: ...er the security code a dash will appear for each number entered It is not necessary to enter any leading zeroes Enter 12 if that is the code It is not necessary to enter 00012 although that will work...

Страница 22: ...200 10 Jump UP Change 0 to 99999 10 11 Jump Down Change 0 to 99999 10 12 Up to Speed Tolerance 0 to 255 10 13 Jump MOP 0 to 1 0 14 Float Freeze 0 to 1 0 15 Display Sample Rate 1 to 255 1 16 Setup Dur...

Страница 23: ...termined by parameter 2 in the MASTER mode If a new SETPOINT is entered during acceleration or deceleration run is still active the DIGIMAX goes to the new value changing from acceleration to decelera...

Страница 24: ...ectable feedback rate via switches on the logic board With the Model 500 check switches S1 1 and S1 2 If there is a doubt as to either the encoder PPR or the EPROM multiplier check the motor for a spe...

Страница 25: ...2 Enter 1 for SLAVE mode where direct ratios are entered as SETPOINTs A reference frequency must be supplied to TB2 terminals 13 and 14 The ratio to be entered as a setpoint is SLAVE MASTER The frequ...

Страница 26: ...input is released in less than half a second 0 5 sec the SETPOINT will stay at the new value If the contact stays closed for more than 0 5 second then the SETPOINT will continue to increase at the rat...

Страница 27: ...generates error code 10 Press PGM CLR to clear it 19 19 19 19 19 LOCAL REMOTE KEYLOCK LOCAL REMOTE KEYLOCK LOCAL REMOTE KEYLOCK LOCAL REMOTE KEYLOCK LOCAL REMOTE KEYLOCK Enter 0 for LOCAL keypad oper...

Страница 28: ...HIGH ENGINEERING UNITS A TO D HIGH ENGINEERING UNITS A TO D HIGH ENGINEERING UNITS The input at terminals 15 and 17 on TB2 may range from 0 to 10 VDC This parameter sets in engineering units what the...

Страница 29: ...meter 29 or a number greater than parameter 30 is entered an error code is generated Press PGM CLR to clear the error and try again 29 29 29 29 29 D TO A LOW ENGINEERING UNITS D TO A LOW ENGINEERING U...

Страница 30: ...36 INSTALLED OPTION ENABLE INSTALLED OPTION ENABLE INSTALLED OPTION ENABLE INSTALLED OPTION ENABLE INSTALLED OPTION ENABLE If there is no installed option such as BCD input this parameter should be se...

Страница 31: ...s steps in programming the unit in approximately the order in which they will be faced Refer to the parameter tables on pages 14 and 20 and to the referenced sections SETUPCHOICES SETUPCHOICES SETUPCH...

Страница 32: ...Page 24 copyright 1992 1996 by Powertec Industrial Motors Figure 5 Typical connections of the DIGIMAX to a POWERTEC Model 500 Brushless DC control...

Страница 33: ...ch was entered is correct the DIGIMAX DIGIMAX DIGIMAX DIGIMAX DIGIMAX will enter the parameter entry mode If the security code entered is incorrect the NORMAL mode will be restored There are two main...

Страница 34: ...Page 26 copyright 1992 1996 by Powertec Industrial Motors Figure 6 Typical connections to a POWERTEC Non Regenerative Brushless DC control...

Страница 35: ...al Section3givessomeoftheerror codes with illegal values in parameter entries ERROR CODE 01 SPEED GREATER THAN PARAMETER P 2 SPEED GREATER THAN PARAMETER P 2 SPEED GREATER THAN PARAMETER P 2 SPEED GRE...

Страница 36: ...Page 28 copyright 1992 1996 by Powertec Industrial Motors Figure 7 Standard connections to a POWERTEC Regenerative Brushless DC control...

Страница 37: ...EGALDECIMALLOCATION ILLEGALDECIMALLOCATION ILLEGALDECIMALLOCATION This error is generated if a number greater than 4 is entered into parameter 3 Press ENTER to clear the error code and enter a number...

Страница 38: ...Page 30 copyright 1992 1996 by Powertec Industrial Motors Figure 7 Standard connections to a POWERTEC MILLENNIUM Brushless DC motor control...

Страница 39: ...catch all error statement which is displayed if the microprocessor detects an error that does not fit into one of the above categories If it occurs during parameter entry press PGM to exit program mod...

Страница 40: ...zero with the motor speed When the next run command is given the UP command must be used to get the motor back up to speed or a new speed entered MASTER OR SLAVE MASTER OR SLAVE MASTER OR SLAVE MASTE...

Страница 41: ...a decimal place in P 02 Press the UP button 4 Enter 1 in P 03 one decimal place Press the UP button 5 P 04 is not used in the MASTER mode Enter 10000 since that is the value used in the slave mode Pre...

Страница 42: ...PR encoder and this motor has a 120 PPR encoder Using the formula above 1400 2500 X 120 240 28 Enter 0 2800 in parameter P 04b you may press 2800 leading zeroes are not necessary Press the UP button 7...

Страница 43: ...or press ALT and 3 2 and ENT 3 Press 2 and ENT 4 Exit the SETUP mode press ENT 5 With the DIGIMAX in the RUN mode and TB2 terminal 6 NOT energized enter the first speed or ratio SETPOINT 6 Energize T...

Страница 44: ...Page 36 copyright 1992 1996 by Powertec Industrial Motors...

Страница 45: ...ess such as operators process engineers and lower level maintenance people This number may be changed easily to exclude people who may no longer be allowed access to the parameters There is a second p...

Страница 46: ...Page 38 copyright 1992 1996 by Powertec Industrial Motors...

Отзывы: