- AUXILIARY ANALOG INPUT

16

GROUND

17

+ AUXILIARY ANALOG INPUT

The maximum input is +10 VDC, but the input is a differential type input, so a negative

voltage may be accepted by reversing input leads. 

TB2 TERMINAL 17 MUST ALWAYS BE

MORE POSITIVE (ON AN ABSOLUTE SCALE) THAN TB2 TERMINAL 15.

 If TB2 terminal

15 is more positive than TB2 terminal 17, the effective input will be 0.

The auxiliary analog input is for transferring an analog voltage representing a system

value (such as motor current) through the RS-422 communications link. For this type of

operation, parameter #26 must be 0.  #23 is set to read out a +10 VDC input in Engineering

Units (EGU). Parameter #22 is set to low EGU, which may be zero, but doesn't have to be.

The auxiliary analog input may also be used as an analog trim or dancer (see

parameters #20 on page 19, and #26 on page 21). The input leads should be connected to

TB2 terminals 15 and 17 (not ground) and TB2 terminal 16 should be used for the shield.

If parameter #26 is  1, a 5VDC input is zero effect. Increasing voltage increases the setpoint.

If parameter #26 is 2, a 0VDC input is no effect. Increasing voltage increases the setpoint.

If parameter #26 is 3, a 0VDC input is no effect. Increasing voltage decreases the setpoint.

The maximum speed (parameter #1) may not be exceeded in speed mode.

The maximum ratio (parameter #31) may not be exceeded in slave mode.

18

RS-422  - RECEIVE

19

RS-422  + RECEIVE

20

RS-422    No connection

21

RS-422  - TRANSMIT

22

RS-422  + TRANSMIT

In order to ensure good communications, it is required that shielded cable be used in

the RS-422 communications link. The cable should have conductors no smaller than #24

AWG for distances up to 500 feet. Recommended cables are cables such as Belden

®

 Wire

Company part #9829 or part #88102.

Connecting the link together consists of connecting all of the transmit terminals of the

DIGIMAX

DIGIMAX

DIGIMAX

DIGIMAX

DIGIMAX

®

 units in parallel (+ to +, and - to -). Then all receive terminals are connected in

parallel (+ to +, and - to -).

ANSI standards apply to RS-422 communications. The RS-422 standard stipulates

that the number of stations shall be at least 10 without repeaters.  (Repeaters are  amplifiers

which strengthen the signal to feed more stations). The 

DIGIMAX

DIGIMAX

DIGIMAX

DIGIMAX

DIGIMAX

®

 communications may

operate up to 32 units on the link.

After connecting all of the RS-422 terminals together, one end of the chain is tied to the

host (a PLC, a personal computer through an RS-422 output card or an RS-232 to RS-422

converter, or an industrial computer with an RS-422 port).  Normally the "transmits" of the

DIGIMAX

DIGIMAX

DIGIMAX

DIGIMAX

DIGIMAX

®

's will tied to the "recieve" of the host, and the "receives" to the "transmits", but

check the specifications of the host to be used. The unit at the far end of the line, furthest from

the host, must have a resistor equal to the cable's impedance (120 ohms) installed across

its receive terminals.  This is "terminating" the line.  It prevents signal reflections from causing

spurious signals on the line. The transmit line is terminated at the host.

The RS-485 Communications standard may be used with the

 DIGIMAX

DIGIMAX

DIGIMAX

DIGIMAX

DIGIMAX

®

 by tying the

+Transmit to the +Receive and the -Transmit to the -Receive. Terminal 20 is for the shields.

If you are putting together a large system, it is a good idea to consult someone who is

knowledgable and experienced in the art of serial communications.

Содержание Digimax

Страница 1: ...Repair Center for Powertec Drives and Motors 460 Milford Parkway Milford OH 45150 www motorsystems com 513 576 1725...

Страница 2: ...NTROLLED DIGITAL SPEED RATIO CONTROLLER MADE IN USA INSTALLATION AND OPERATION INSTRUCTION MANUAL Revision 2A October 6 1993 This manual is fully implemented with software version SFWVER 93271 and lat...

Страница 3: ...Page ii copyright 1992 1996 by Powertec Industrial Motors...

Страница 4: ...9 18 Baud Rate 19 19 Local Remote Keylock 19 20 Speed Ratio SETPOINT 19 21 Operator Security Code 19 22 A to D Low Engineering Units 19 23 A to D High Engineering Units 20 24 A to D Display Mode 20 25...

Страница 5: ...ADVANCED FUNCTIONS 33 List of Illustrations 1 Physical Dimensions 2 2 Rear Terminal Strip connections 5 3 Connections to the DIGIMAX DIGIMAX DIGIMAX DIGIMAX DIGIMAX 8 4 Front panel Display 9 5 Typica...

Страница 6: ...UNLESS YOU HAVE CHECKED FOR THE PROPER CONNECTIONS NOTICE If you are replacing a DIGIMAX III with a DIGIMAX DIGIMAX DIGIMAX DIGIMAX DIGIMAX check TB2 terminals 1 2 and 3 to be sure that there are no...

Страница 7: ...r abuse defective or incorrect installation effects of the DIGIMAX DIGIMAX DIGIMAX DIGIMAX DIGIMAX on other equipment or effects on the DIGIMAX DIGIMAX DIGIMAX DIGIMAX DIGIMAX causedbyotherequipment a...

Страница 8: ...Page vii DIGIMAX Manual...

Страница 9: ...o operators which may be remote from the location of the motor control Control inputs and outputs are isolated for flexibility and immunity to interactions between units Speed or ratio setpoints and o...

Страница 10: ...Page 2 copyright 1992 1996 by Powertec Industrial Motors Figure 1 Physical dimensions of the DIGIMAX...

Страница 11: ...to and from the DIGIMAX DIGIMAX DIGIMAX DIGIMAX DIGIMAX must be kept away from power wiring All relays used in conjunction with or in the vicinity of the DIGIMAX must have arc suppressors if they have...

Страница 12: ...QUENCY OUTPUT This is the output frequency to the controlled drive or drives It is capable of driving up to ten inputs of motor controls or ten other DIGIMAX DIGIMAX DIGIMAX DIGIMAX DIGIMAX inputs or...

Страница 13: ...peripheral device control By connecting relays to these outputs and using the relays to control the drive it is possible to run the DIGIMAX DIGIMAX DIGIMAX DIGIMAX DIGIMAX and motor control entirely...

Страница 14: ...DIGIMAX does NOT cause the drive to reverse A separate simultaneous command must be given to the drive If the drive is given a reverse command it will not reverse until the DIGIMAX DIGIMAX DIGIMAX DIG...

Страница 15: ...able should have conductors no smaller than 24 AWG for distances up to 500 feet Recommended cables are cables such as Belden Wire Company part 9829 or part 88102 Connecting the link together consists...

Страница 16: ...Page 8 copyright 1992 1996 by Powertec Industrial Motors Figure 3 Connections to the DIGIMAX speed controller...

Страница 17: ...g to a newly entered ratio The REMOTE indicator is on when remote operation is on In one REMOTE mode the keypad is locked out unless the unit s LOC REM key is pressed In another mode even the LOC REM...

Страница 18: ...t must be pressed first followed by a security code and then the ENTER button to access the parameters When the PGM CLR key is pressed the display will blank and the numbers of the security code as th...

Страница 19: ...13 and 12 on TB1 The display shows the letter Ao on the left side of the display and the current value of the Analog Output in Engineering units which are controlled and scaled with parameters 28 thr...

Страница 20: ...N function the UP key will only work for the AUXOUT and the PRESET functions It is not necessary to press the ALT key between the PRESET key and the ON key or after the AUXOUT number key before the ON...

Страница 21: ...er the security code a dash will appear for each number entered It is not necessary to enter any leading zeroes Enter 12 if that is the code It is not necessary to enter 00012 although that will work...

Страница 22: ...200 10 Jump UP Change 0 to 99999 10 11 Jump Down Change 0 to 99999 10 12 Up to Speed Tolerance 0 to 255 10 13 Jump MOP 0 to 1 0 14 Float Freeze 0 to 1 0 15 Display Sample Rate 1 to 255 1 16 Setup Dur...

Страница 23: ...termined by parameter 2 in the MASTER mode If a new SETPOINT is entered during acceleration or deceleration run is still active the DIGIMAX goes to the new value changing from acceleration to decelera...

Страница 24: ...ectable feedback rate via switches on the logic board With the Model 500 check switches S1 1 and S1 2 If there is a doubt as to either the encoder PPR or the EPROM multiplier check the motor for a spe...

Страница 25: ...2 Enter 1 for SLAVE mode where direct ratios are entered as SETPOINTs A reference frequency must be supplied to TB2 terminals 13 and 14 The ratio to be entered as a setpoint is SLAVE MASTER The frequ...

Страница 26: ...input is released in less than half a second 0 5 sec the SETPOINT will stay at the new value If the contact stays closed for more than 0 5 second then the SETPOINT will continue to increase at the rat...

Страница 27: ...generates error code 10 Press PGM CLR to clear it 19 19 19 19 19 LOCAL REMOTE KEYLOCK LOCAL REMOTE KEYLOCK LOCAL REMOTE KEYLOCK LOCAL REMOTE KEYLOCK LOCAL REMOTE KEYLOCK Enter 0 for LOCAL keypad oper...

Страница 28: ...HIGH ENGINEERING UNITS A TO D HIGH ENGINEERING UNITS A TO D HIGH ENGINEERING UNITS The input at terminals 15 and 17 on TB2 may range from 0 to 10 VDC This parameter sets in engineering units what the...

Страница 29: ...meter 29 or a number greater than parameter 30 is entered an error code is generated Press PGM CLR to clear the error and try again 29 29 29 29 29 D TO A LOW ENGINEERING UNITS D TO A LOW ENGINEERING U...

Страница 30: ...36 INSTALLED OPTION ENABLE INSTALLED OPTION ENABLE INSTALLED OPTION ENABLE INSTALLED OPTION ENABLE INSTALLED OPTION ENABLE If there is no installed option such as BCD input this parameter should be se...

Страница 31: ...s steps in programming the unit in approximately the order in which they will be faced Refer to the parameter tables on pages 14 and 20 and to the referenced sections SETUPCHOICES SETUPCHOICES SETUPCH...

Страница 32: ...Page 24 copyright 1992 1996 by Powertec Industrial Motors Figure 5 Typical connections of the DIGIMAX to a POWERTEC Model 500 Brushless DC control...

Страница 33: ...ch was entered is correct the DIGIMAX DIGIMAX DIGIMAX DIGIMAX DIGIMAX will enter the parameter entry mode If the security code entered is incorrect the NORMAL mode will be restored There are two main...

Страница 34: ...Page 26 copyright 1992 1996 by Powertec Industrial Motors Figure 6 Typical connections to a POWERTEC Non Regenerative Brushless DC control...

Страница 35: ...al Section3givessomeoftheerror codes with illegal values in parameter entries ERROR CODE 01 SPEED GREATER THAN PARAMETER P 2 SPEED GREATER THAN PARAMETER P 2 SPEED GREATER THAN PARAMETER P 2 SPEED GRE...

Страница 36: ...Page 28 copyright 1992 1996 by Powertec Industrial Motors Figure 7 Standard connections to a POWERTEC Regenerative Brushless DC control...

Страница 37: ...EGALDECIMALLOCATION ILLEGALDECIMALLOCATION ILLEGALDECIMALLOCATION This error is generated if a number greater than 4 is entered into parameter 3 Press ENTER to clear the error code and enter a number...

Страница 38: ...Page 30 copyright 1992 1996 by Powertec Industrial Motors Figure 7 Standard connections to a POWERTEC MILLENNIUM Brushless DC motor control...

Страница 39: ...catch all error statement which is displayed if the microprocessor detects an error that does not fit into one of the above categories If it occurs during parameter entry press PGM to exit program mod...

Страница 40: ...zero with the motor speed When the next run command is given the UP command must be used to get the motor back up to speed or a new speed entered MASTER OR SLAVE MASTER OR SLAVE MASTER OR SLAVE MASTE...

Страница 41: ...a decimal place in P 02 Press the UP button 4 Enter 1 in P 03 one decimal place Press the UP button 5 P 04 is not used in the MASTER mode Enter 10000 since that is the value used in the slave mode Pre...

Страница 42: ...PR encoder and this motor has a 120 PPR encoder Using the formula above 1400 2500 X 120 240 28 Enter 0 2800 in parameter P 04b you may press 2800 leading zeroes are not necessary Press the UP button 7...

Страница 43: ...or press ALT and 3 2 and ENT 3 Press 2 and ENT 4 Exit the SETUP mode press ENT 5 With the DIGIMAX in the RUN mode and TB2 terminal 6 NOT energized enter the first speed or ratio SETPOINT 6 Energize T...

Страница 44: ...Page 36 copyright 1992 1996 by Powertec Industrial Motors...

Страница 45: ...ess such as operators process engineers and lower level maintenance people This number may be changed easily to exclude people who may no longer be allowed access to the parameters There is a second p...

Страница 46: ...Page 38 copyright 1992 1996 by Powertec Industrial Motors...

Отзывы: