6. Specifications 

CAPACITY* 

10000VA / 8000W 

15000VA / 12000W 

20000VA / 16000W 

INPUT 

Voltage 

Range 

Low Line Loss 

110 VAC(L-N) ±  3 % at 50% Load 

176 VAC(L-N) ±  3 % at 100% Load 

Low Line Comeback 

Low Line Loss V 10V 

High Line Loss 

  300 VAC(L-N) ±  3 % 

High Line Comeback 

High Line Loss Voltage - 10V   

Frequency Range 

46Hz ~ 54 Hz @ 50Hz system 
56Hz ~ 64 Hz @ 60Hz system 

Phase 

Three phase with ground 

Power Factor 

 0.99 at 100% Load 

OUTPUT 

Output voltage 

208/220/230/240VAC 

AC Voltage Regulation   

±  1% 

Frequency Range   
(Synchronized Range) 

46Hz ~ 54 Hz @ 50Hz system 
56Hz ~ 64 Hz @ 60Hz system 

Frequency Range (Batt. Mode) 

50 Hz ±  0.1 Hz or 60Hz ±  0.1 Hz 

Overload 

AC mode 

100%~110%: 10min 

110%~130%: 1min 

>130% : 1sec 

Battery mode 

100%~110%: 30sec 
110%~130%: 10sec 

>130% : 1sec 

Current Crest Ratio 

3:1 max 

Harmonic Distortion 

 2 % @ 100% Linear Load; 

 5 % @ 100% Non-linear Load 

Transfer 

Time 

Line

Battery 

0 ms 

Inverter

Bypass 

0 ms 

Inverter

ECO 

<10 ms 

EFFICIENCY 

AC mode 

> 89% 

>89% 

>89% 

Battery Mode 

> 86% 

>88% 

>87% 

BATTERY 

Standard 

Model 

Type 

12 V / 9 Ah 

12 V / 9 Ah 

12 V / 9 Ah   

Numbers 

20 

2 x 20 

2 x 20 

Recharge Time 

9 hours recover to 90% capacity   

Charging Current   

1.0 A ±  10% (max.) 

2.0 A ±  10% (max.) 

2.0 A ±  10% (max.)

 

Charging Voltage   

273 VDC ±  1%   

Long-run 

Model 

Type 

Depending on applications 

Numbers 

18 - 20 

Charging Current   

4.0 A ±  10% (max.) 

8.0 A ±  10% (max.) 

8.0 A ±  10% (max.) 

Charging Voltage 

273 VDC ±  1%   

PHYSICAL 

Outline 

Dimension, D X W X H   

mm 

592X250X576 

815X250X826 

592X250X576 

815X250X826 

592X250X576 

Net Weight (kgs) 

83 

28 

164 

40 

164 

40 

Packaging 

Dimension, D X W X H   

mm 

700X385X 

815 

690X370X 

670 

920X380X1025 

700X385X815 

920X380X 

1025 

700X385X815 

Net Weight (kgs) 

90 

31 

182 

47 

182 

47 

ENVIRONMENT

 

Operation Temperature 

0 ~ 40°C (the battery life will down when > 25°C) 

Operation Humidity 

<95 % and non-condensing 

Operation Altitude** 

<1000m 

Acoustic Noise Level 

Less than 58dB @ 1 Meter 

Less than 60dB @ 1 Meter 

MANAGEMENT 

Smart RS-232 or USB 

Supports Windows®  2000/2003/XP/Vista/2008, Windows®  7, Linux, Unix, and MAC 

Optional SNMP 

Power management from SNMP manager and web browser 

* Derate capacity to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC. 
**If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m. 

***Product specifications are subject to change without further notice. 

Содержание Centurion 10000 VA

Страница 1: ...Centurion 10000 15000 20000 VA Tower Online UPS Users Manual www powershield com au...

Страница 2: ...distortions The Centurions true online double conversion topology will continuously protect your equipment by internally isolating your equipment from the utility power ensuring that all your equipme...

Страница 3: ...and operating instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading through al...

Страница 4: ...UPS INSTALLATION FOR PARALLEL SYSTEM 10 2 5 SOFTWARE INSTALLATION 12 3 OPERATIONS 13 3 1 BUTTON OPERATION 13 3 2 LED INDICATORS AND LCD PANEL 13 3 3 AUDIBLE ALARM 15 3 4 SINGLE UPS OPERATION 15 3 5 P...

Страница 5: ...Do not connect appliances or devices which would overload the UPS e g big motor type equipment to the UPS output sockets or terminal Place cables in such a way that no one can step on or trip over th...

Страница 6: ...connect the mains Ensure that no liquid or other foreign objects can enter into the UPS system The UPS can be operated by any individuals with no previous experience 1 5 Standards Safety IEC EN 62040...

Страница 7: ...Unpack the package and check the package contents The shipping package contains One UPS One user manual One monitoring software CD One RS 232 cable option One USB cable One parallel cable only availab...

Страница 8: ...ershield com au 7 Diagram 3 15K 20K Rear Panel Diagram 5 15KL 20KL Input Output Terminal Diagram 6 15K 20K Input Output Diagram 7 15K 20K Grounding Terminal Terminal Diagram 4 10K 10KL Input Output Te...

Страница 9: ...execute the following instructions by professional personnel 1 Make sure the mains wire and breakers in the building are enough for the rated capacity of UPS to avoid the hazards of electric shock or...

Страница 10: ...s 5 Remove the terminal block cover on the rear panel of UPS Then connect the wires according to the following terminal block diagrams Connect the earth wire first when making wire connection Disconne...

Страница 11: ...tall the battery pack Pay highly attention to the rated battery voltage marked on the rear panel If you want to change the numbers of the battery pack please make sure you modify the setting simultane...

Страница 12: ...rshield com au 11 NOTE The parallel system can not use one battery pack Otherwise it will cause system permanent failure 5 Refer to the following wiring diagram Wiring diagram of parallel system for 1...

Страница 13: ...w powershield com au 12 Wiring diagram of parallel system for 15K L 20K L 2 5 Software Installation For optimal computer system protection install UPS monitoring software to fully configure UPS shutdo...

Страница 14: ...utton to display next selection in setting menu Mute Down Button Mute the alarm Press and hold the button more than 0 5s to mute the buzzer Please refer to section 3 4 9 for details Down key Press thi...

Страница 15: ...ion Indicates the output voltage frequency or battery voltage Vac output voltage Vdc battery voltage Hz frequency Load information Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicates ove...

Страница 16: ...seconds later UPS operates in Bypass mode and supplies power to the loads via the bypass NOTE When UPS is in Bypass mode the output voltage will directly power from utility after you switch on the in...

Страница 17: ...buzzer will beep according to different battery capacity If the battery capacity is more than 25 the buzzer will beep once every 4 seconds If the battery voltage drops to the alarm level the buzzer w...

Страница 18: ...a fatal error in the UPS Users can get the fault code from display panel Please check the trouble shooting table in chapter 4 for details 2 Please check the loads wiring ventilation utility battery an...

Страница 19: ...ctly b Turn on the output breaker of each UPS c Turn on each UPS in turns After a while the UPSs will enter to AC mode synchronously and then the parallel system is completed 6 Turn on the parallel sy...

Страница 20: ...g UPS and the system will transfer to Bypass mode Set the maintenance switches from BPS to UPS and put the maintenance bypass covers back 5 Turn on the remaining UPS according to the previous section...

Страница 21: ...utdown point for programmable output Y Y Y Y Y Y 12 Reserved Neutral loss detection Y Y Y Y Y Y 13 Battery voltage calibration Y Y Y Y Y Y 14 Charger voltage adjustment Y Y Y Y Y Y 15 Inverter voltage...

Страница 22: ...UPS to CVCF mode If selected the output frequency will be fixed at 50Hz or 60Hz according to setting in parameter 2 The input frequency could be from 46Hz to 64Hz NCF Setting UPS to normal mode not C...

Страница 23: ...10 of the nominal voltage Parameter 3 High voltage point in ECO mode The setting range is from 5 to 10 of the nominal voltage 07 Frequency range for ECO mode Interface Setting Parameter 2 Set low volt...

Страница 24: ...setting point or shutdown time arrives the programmable output will be cut off automatically After the utility is recovering the output will turn on automatically If overload happens the programmable...

Страница 25: ...nter key to make the CHE flash Secondly press the Enter key again to activate the neutral detection check If neutral is detected the alarm will be muted and the UPS will go back to normal mode If neut...

Страница 26: ...hase difference between L2 and L1 with 120 L3 and L2 with 120 or phase difference between L2 and L1 240 and L3 and L2 with 240 3 8 Operating Mode Status Description Following table shows LCD display f...

Страница 27: ...s the UPS has no output Alarm beeps every two minutes LCD display AC mode Description When the input voltage is within acceptable range UPS will provide pure and stable AC power to output The UPS will...

Страница 28: ...e UPS can be set at a constant output frequency 50 Hz or 60 Hz The UPS will still charge battery under this mode LCD display Battery mode Description When the input voltage is beyond the acceptable ra...

Страница 29: ...the UPS will beep once and start Battery Test The line between I P and inverter icons will blink to remind users This operation is used to check the battery status LCD display Warning status Descript...

Страница 30: ...over None 21 Battery SCR short circuited None 03 Bus under None 24 Inverter relay short circuited None 04 Bus unbalance None 29 Battery fuse broken in Battery mode None 06 Converter over current None...

Страница 31: ...de Warning code Warning event Warning code Warning event 01 Battery unconnected 10 L1 IP fuse broken 02 IP Neutral loss or IP L2 L3 fuse broken 21 Line situations are different in parallel system 04 I...

Страница 32: ...UPS output After repetitive overloads the UPS is locked in the Bypass mode Connected devices are fed directly by the mains Remove excess loads from UPS output first Then shut down the UPS and restart...

Страница 33: ...nnection If the connection is ok and the alarm is still displaying please refer to the LCD setting section to enter the neutral loss check menu to see if the parameter3 is CHE if it is please press th...

Страница 34: ...nd with the required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery ter...

Страница 35: ...Time 9 hours recover to 90 capacity Charging Current 1 0 A 10 max 2 0 A 10 max 2 0 A 10 max Charging Voltage 273 VDC 1 Long run Model Type Depending on applications Numbers 18 20 Charging Current 4 0...

Страница 36: ......

Отзывы: