16: Output voltage calibration 

Interface 

Setting 

 

Parameter 2:

 it always shows 

OP.V

 as output voltage. 

Parameter  3:

  it  shows  the  internal  measurement  value  of  the 

output voltage, and you can calibrate it by pressing 

Up

 or 

Down

 

according  to  the  measurement  from  an  external  voltage  meter. 

The  calibration  result  will  be  effective  by  pressing 

Enter

.  The 

calibration range is limited /-9V. This function is normally 

used for parallel operation.

 

 

17: Phase auto adapt enable/disable 

Interface 

Setting 

 

Parameter 2: 

it always shows 

PH.A

 as phase auto adapt 

function.

 

Parameter 3: 

Enable or disable phase auto adapt function. You 

may choose following two options: 

DIS: 

disable phase auto adapt function. Then, the UPS only can 

accept one condition which the phase difference of L2 and L1 is 

120

º

 and phase difference between L3 and L2 is 120

º

ENA:

 enable phase auto adapt function. Then, the UPS can accept 

either inputs of L1, L2, L3 in the same phase or the phase 

difference between L2 and L1 with 120

º

, L3 and L2 with 120

º

or 

phase difference between L2 and L1 240

º

, and L3 and L2 with 

240

º

3-8. Operating Mode/Status Description 

Following table shows LCD display for operating modes and status.   

(1) If the UPS is in normal operation, it will show four screens one by one, which represents 3 phase input 

voltage (L1, L2, L3) and frequency in turns.   

(2) If parallel UPS systems are successfully set up, it will show one more screen with “

PAR

” in parameter 2 

and assigned number in parameter 3 as below parallel screen diagram.  The master UPS will be default 

assigned as “001” and slave UPSs will be assigned as either “002” or “003”. The assigned numbers may be 

changed dynamically in the operation; 

 

Parallel screen 

  Warning screen 

(3) If some errors occur in the UPS, it will show one more screen to represent the warning situation. In the 

warning  screen,  it  can  show  up  to  3  error  codes  and  each  code  indicates  one  error.  You  can  find  the 

meanings of error codes in the warning code table. 

 

Operating mode/status 

UPS Power On    Description 

When UPS is powered on, it will enter into this mode for a few seconds for 
initializing the CPU and system. 

LCD display 

 

Содержание Centurion 10000 VA

Страница 1: ...Centurion 10000 15000 20000 VA Tower Online UPS Users Manual www powershield com au...

Страница 2: ...distortions The Centurions true online double conversion topology will continuously protect your equipment by internally isolating your equipment from the utility power ensuring that all your equipme...

Страница 3: ...and operating instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading through al...

Страница 4: ...UPS INSTALLATION FOR PARALLEL SYSTEM 10 2 5 SOFTWARE INSTALLATION 12 3 OPERATIONS 13 3 1 BUTTON OPERATION 13 3 2 LED INDICATORS AND LCD PANEL 13 3 3 AUDIBLE ALARM 15 3 4 SINGLE UPS OPERATION 15 3 5 P...

Страница 5: ...Do not connect appliances or devices which would overload the UPS e g big motor type equipment to the UPS output sockets or terminal Place cables in such a way that no one can step on or trip over th...

Страница 6: ...connect the mains Ensure that no liquid or other foreign objects can enter into the UPS system The UPS can be operated by any individuals with no previous experience 1 5 Standards Safety IEC EN 62040...

Страница 7: ...Unpack the package and check the package contents The shipping package contains One UPS One user manual One monitoring software CD One RS 232 cable option One USB cable One parallel cable only availab...

Страница 8: ...ershield com au 7 Diagram 3 15K 20K Rear Panel Diagram 5 15KL 20KL Input Output Terminal Diagram 6 15K 20K Input Output Diagram 7 15K 20K Grounding Terminal Terminal Diagram 4 10K 10KL Input Output Te...

Страница 9: ...execute the following instructions by professional personnel 1 Make sure the mains wire and breakers in the building are enough for the rated capacity of UPS to avoid the hazards of electric shock or...

Страница 10: ...s 5 Remove the terminal block cover on the rear panel of UPS Then connect the wires according to the following terminal block diagrams Connect the earth wire first when making wire connection Disconne...

Страница 11: ...tall the battery pack Pay highly attention to the rated battery voltage marked on the rear panel If you want to change the numbers of the battery pack please make sure you modify the setting simultane...

Страница 12: ...rshield com au 11 NOTE The parallel system can not use one battery pack Otherwise it will cause system permanent failure 5 Refer to the following wiring diagram Wiring diagram of parallel system for 1...

Страница 13: ...w powershield com au 12 Wiring diagram of parallel system for 15K L 20K L 2 5 Software Installation For optimal computer system protection install UPS monitoring software to fully configure UPS shutdo...

Страница 14: ...utton to display next selection in setting menu Mute Down Button Mute the alarm Press and hold the button more than 0 5s to mute the buzzer Please refer to section 3 4 9 for details Down key Press thi...

Страница 15: ...ion Indicates the output voltage frequency or battery voltage Vac output voltage Vdc battery voltage Hz frequency Load information Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicates ove...

Страница 16: ...seconds later UPS operates in Bypass mode and supplies power to the loads via the bypass NOTE When UPS is in Bypass mode the output voltage will directly power from utility after you switch on the in...

Страница 17: ...buzzer will beep according to different battery capacity If the battery capacity is more than 25 the buzzer will beep once every 4 seconds If the battery voltage drops to the alarm level the buzzer w...

Страница 18: ...a fatal error in the UPS Users can get the fault code from display panel Please check the trouble shooting table in chapter 4 for details 2 Please check the loads wiring ventilation utility battery an...

Страница 19: ...ctly b Turn on the output breaker of each UPS c Turn on each UPS in turns After a while the UPSs will enter to AC mode synchronously and then the parallel system is completed 6 Turn on the parallel sy...

Страница 20: ...g UPS and the system will transfer to Bypass mode Set the maintenance switches from BPS to UPS and put the maintenance bypass covers back 5 Turn on the remaining UPS according to the previous section...

Страница 21: ...utdown point for programmable output Y Y Y Y Y Y 12 Reserved Neutral loss detection Y Y Y Y Y Y 13 Battery voltage calibration Y Y Y Y Y Y 14 Charger voltage adjustment Y Y Y Y Y Y 15 Inverter voltage...

Страница 22: ...UPS to CVCF mode If selected the output frequency will be fixed at 50Hz or 60Hz according to setting in parameter 2 The input frequency could be from 46Hz to 64Hz NCF Setting UPS to normal mode not C...

Страница 23: ...10 of the nominal voltage Parameter 3 High voltage point in ECO mode The setting range is from 5 to 10 of the nominal voltage 07 Frequency range for ECO mode Interface Setting Parameter 2 Set low volt...

Страница 24: ...setting point or shutdown time arrives the programmable output will be cut off automatically After the utility is recovering the output will turn on automatically If overload happens the programmable...

Страница 25: ...nter key to make the CHE flash Secondly press the Enter key again to activate the neutral detection check If neutral is detected the alarm will be muted and the UPS will go back to normal mode If neut...

Страница 26: ...hase difference between L2 and L1 with 120 L3 and L2 with 120 or phase difference between L2 and L1 240 and L3 and L2 with 240 3 8 Operating Mode Status Description Following table shows LCD display f...

Страница 27: ...s the UPS has no output Alarm beeps every two minutes LCD display AC mode Description When the input voltage is within acceptable range UPS will provide pure and stable AC power to output The UPS will...

Страница 28: ...e UPS can be set at a constant output frequency 50 Hz or 60 Hz The UPS will still charge battery under this mode LCD display Battery mode Description When the input voltage is beyond the acceptable ra...

Страница 29: ...the UPS will beep once and start Battery Test The line between I P and inverter icons will blink to remind users This operation is used to check the battery status LCD display Warning status Descript...

Страница 30: ...over None 21 Battery SCR short circuited None 03 Bus under None 24 Inverter relay short circuited None 04 Bus unbalance None 29 Battery fuse broken in Battery mode None 06 Converter over current None...

Страница 31: ...de Warning code Warning event Warning code Warning event 01 Battery unconnected 10 L1 IP fuse broken 02 IP Neutral loss or IP L2 L3 fuse broken 21 Line situations are different in parallel system 04 I...

Страница 32: ...UPS output After repetitive overloads the UPS is locked in the Bypass mode Connected devices are fed directly by the mains Remove excess loads from UPS output first Then shut down the UPS and restart...

Страница 33: ...nnection If the connection is ok and the alarm is still displaying please refer to the LCD setting section to enter the neutral loss check menu to see if the parameter3 is CHE if it is please press th...

Страница 34: ...nd with the required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery ter...

Страница 35: ...Time 9 hours recover to 90 capacity Charging Current 1 0 A 10 max 2 0 A 10 max 2 0 A 10 max Charging Voltage 273 VDC 1 Long run Model Type Depending on applications Numbers 18 20 Charging Current 4 0...

Страница 36: ......

Отзывы: