background image

Medical Air & Laboratory Air Systems – 7.5 & 10 HP Pumps

Powerex  

  150 Production Drive  

  Harrison, OH  45030  

  USA

P   1.888.769.7979  

  F   513.367.3125  

  www.powerexinc.com

IN594402AV  

  06/2017

Page 9 of 28

• 

Record of all alarms, warnings and service alerts with date and 

time.

• 

Displays model number, serial number, service phone number

• 

If system is expandable, use Plex Mode Input to adjust PLC 

Program to additional pumps.

Alarm Log

Service

To Set Time & Date

This Screen Will Appear

• 

Press Set Time, Date button

• 

Press Offline

Содержание SLAE075

Страница 1: ...ndicates a potentially hazardous situation which if not avoided COULD result in death or serious injury Caution indicates a potentially hazardous situation which if not avoided MAY result in minor or...

Страница 2: ...dures must be employed Controls The disconnects and protection devices in the Powerex control system are for the motor branch circuits accessory supply circuits and for the control circuit only The co...

Страница 3: ...cumulates in the tank Operation at High Altitudes Compressor pumps are sensitive to reduced atmospheric pressure encountered as altitude increases Powerex will adjust the operating set points to compe...

Страница 4: ...points may be selected and holes drilled in the base as needed to accommodate the design auto Operation with closed valves will damage the pump The intake isolation valves have had the handles removed...

Страница 5: ...ave been firmly connected Confirm supply voltage and amps match the system requirements 4 Be sure all pressure connections are tight 5 Check to be certain all safety relief valves etc are unrestricted...

Страница 6: ...tems 7 5 10 HP Pumps Powerex 150 Production Drive Harrison OH 45030 USA P 1 888 769 7979 F 513 367 3125 www powerexinc com IN594402AV 06 2017 Page 6 of 28 Medical Air Flow Schematic This is only a rep...

Страница 7: ...tems 7 5 10 HP Pumps Powerex 150 Production Drive Harrison OH 45030 USA P 1 888 769 7979 F 513 367 3125 www powerexinc com IN594402AV 06 2017 Page 7 of 28 Medical Air Flow Schematic This is only a rep...

Страница 8: ...tem has the touch screen controls the following section will explain how the screen can be used to control and monitor the unit operation Displays Pressure level and Dew Point level Pressure level wil...

Страница 9: ...com IN594402AV 06 2017 Page 9 of 28 Record of all alarms warnings and service alerts with date and time Displays model number serial number service phone number If system is expandable use Plex Mode...

Страница 10: ...888 769 7979 F 513 367 3125 www powerexinc com IN594402AV 06 2017 Page 10 of 28 Press Clock Setting and enter time and date This Screen Will Appear To Return to Run Mode This Screen Will Appear Seque...

Страница 11: ...arrison OH 45030 USA P 1 888 769 7979 F 513 367 3125 www powerexinc com IN594402AV 06 2017 Page 11 of 28 Daily Load Factor Pump Maintenance At specific preset intervals service alerts for the Dew Poin...

Страница 12: ...ou will be able to configure the 260MX S027 Gateway for basic operation You will set the device s network settings and parameters to the proper configuration for initial operation and physically place...

Страница 13: ...ngs to connect the gateway The following steps will connect the gateway properly 1 Connect the 12 24 VDC power source to the device 2 Using the crossover cable connect the device to the PC 3 Insert th...

Страница 14: ...again If you do not know the IP Address use the following procedure 1 Open an MS DOS Command Prompt 2 Type ipconfig and press enter 3 Note the IP address The previous example was 172 16 3 158 4 To te...

Страница 15: ...s must be unique amongst all BACnet devices on the network 3 In the Name field enter a unique name for the device 4 The Description and Location fields are optional Filling in this information is reco...

Страница 16: ...check the enable box 3 If an alarm is enabled then the Low Alarm and High Alarm must be set 4 If the value of the point falls below the Low Alarm the alarm is set and an email is generated if email i...

Страница 17: ...es authentication enter in the Password for the SMTP Mail Username 5 Enter in the SMTP Server that is being used 6 Enter in the Email Address of the sender This is going to be the same field as Step 3...

Страница 18: ...www powerexinc com IN594402AV 06 2017 Page 18 of 28 System Status 1 The main page shows the BACnet Point its current value and whether an alarm is set 2 The Value column will show the current value of...

Страница 19: ...of any page 2 If the Username and or Password is ever forgotten click the Reset Password 3 Click Confirm Reset 4 Physically cycle power on the gateway within 15 minutes to gain access to the web page...

Страница 20: ...dew point at the sensor This is easily corrected by changing or cleaning the filter Since the air from the Powerex system is filtered at the dryer exit filter problems are unlikely Installation Touchi...

Страница 21: ...bushing 10 HP PU202648AV 1 8 Aftercooler SL060000AV 1 per pump 9 Check valve 7 5 HP IP087700AV 1 per pump Check valve 10 HP IS025003AV 1 per pump 10 Pump overpressure safety valve V 215100AV 1 12 Tan...

Страница 22: ...ircuit breaker 7 5 HP 230 V PE000308AV 1 per motor Motor protector circuit breaker 7 5 HP 460 V PE000306AV 1 per motor Motor protector circuit breaker 10 HP 208 V PE000310AV 1 per motor Motor protecto...

Страница 23: ...or less Pressure gauge Inspect Every 2 000 hours or less Tank Drain moisture Verify proper drain operation Air leaks Inspect Electric auto drains Replace Replace every 4 years Air Dryers Item Action...

Страница 24: ...tlet line Then remove the braided stainless flex hose from the set Loosen the bolts holding the L brackets to the baseplate on the side you are pulling so they can lift up over the head of the rail to...

Страница 25: ...y and the two slide bolts on the front edge of the base Keep enough torque on them to take up any slack between the slider and the main base but enough slack to allow the slider to move 2 Tighten the...

Страница 26: ...Medical Air Laboratory Air Systems 7 5 10 HP Pumps Powerex 150 Production Drive Harrison OH 45030 USA P 1 888 769 7979 F 513 367 3125 www powerexinc com IN594402AV 06 2017 Page 26 of 28 Notes...

Страница 27: ...red 7 500 hours of use whichever occurs first During such warranty period Powerex shall be fully liable for all Defects in the Products the Product Defects i e all costs of repair or replacement which...

Страница 28: ...EQUENTAL PUNITIVE SPECULATIVE OR INDIRECT LOSSES OR DAMAGES WHATSOEVER ARISING OUT OF OR IN ANY WAY RELATED TO ANY OF THE PRODUCTS OR GOODS SOLD OR AGREED TO BE SOLD BY POWEREX TO BUYER TO THE EXTENT...

Отзывы: